Plan Review Details - Permit 06061662
Plan Review Stops For Permit 06061662
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By mjacobs Date 2006-10-23 Time 11:13 Rev Time 0.00
Received By mjacobs Date 2006-10-23 Time 10:47 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-01 Cont ID  
Sent By mjacobs Date 2006-09-01 Time 09:08 Rev Time 0.00
Received By mjacobs Date 2006-08-31 Time 15:35 Sent To PC
Notes
2006-09-01 00:00:00 
 1) OK.
  
 2) OK
  
 3) SHOW THE EXIT DOOR IN THE REAR OF THE
 BUILDING WHERE THE EXIT LIGHT IS. SEE
 REFLECTED CEILING PLAN SHEET A-2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By mjacobs Date 2006-07-17 Time 16:59 Rev Time 0.00
Received By mjacobs Date 2006-07-17 Time 14:53 Sent To  
Notes
2006-07-17 00:00:001) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF FLOORS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
  
 2) 11-7.2 SALES AND SERVICE COUNTERS,
 TELLER WINDOWS, INFORMATION COUNTERS.
 (1) IN DEPARTMENT STORES AND
 MISCELLANEOUS RETAIL STORES WHERE
 COUNTERS HAVE CASH REGISTERS AND ARE
 PROVIDED FOR SALES OR DISTRIBUTION OF
 GOODS OR SERVICES TO THE PUBLIC, AT
 LEAST ONE OF EACH TYPE SHALL HAVE A
 PORTION OF THE COUNTER WHICH IS AT LEAST
 36 INCHES (915 MM) IN LENGTH WITH A
 MAXIMUM HEIGHT OF 36 INCHES (915 MM)
 ABOVE THE FINISH FLOOR. IT SHALL BE ON
 AN ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 . THE ACCESSIBLE COUNTERS
 MUST BE DISPERSED THROUGHOUT THE
 BUILDING OR FACILITY. IN ALTERATIONS
 WHERE IT IS TECHNICALLY INFEASIBLE TO
 PROVIDE AN ACCESSIBLE COUNTER, AN
 AUXILIARY COUNTER MEETING THESE
 REQUIREMENTS MAY BE PROVIDED. PROVIDE
 THE ELEVATION DETAILS OF THE CHECK OUT
 COUNTER.
  
 3) SHOW THE EXIT DOOR IN THE REAR OF THE
 BUILDING WHERE THE EXIT LIGHT IS. SEE
 REFLECTED CEILING PLAN SHEET A-2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 16:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 15:58 Sent To  
Notes
2006-10-01 00:00:00IN ELEC
 ** UNSAT 3RD REVIEW **
  
 1) NOTE: PLEASE SEE THE OVER-RIDE
 DEVICES SHALL ALL BE SHOWN ON PLANS
 WHICH OVER RIDE "SYSTEM". PLEASE SEE
 INGRESS /EGRESS AREAS WHICH ONE "S" IS
 SHOWN HOWEVER PLANS DO NOT DELINEATE THE
 DEVICE BEING USED FOR OVER RIDE."TYPE"?.
 PLEASE SEE ALSO ENTRANCE "S' WHICH IS
 ALSO REQUIRED OVER-RIDE SYSTEM. SAME
 NOTE.
 PLEASE KNOW AS STATED ON PREVIOUS REVIEW
 THE TYPE OF DEVICES MUST STATE THE MAX
 TIME ON OVER-RIDE DEPENDING ON DEVICE
 BEING CHOSEN.
 MOTION/OCUPANT SENSOR TYPE (30MINS MAX),
 TIMER TYPE 4HRS MAX).
  
 2) NOTE: PLEASE SEE LPD'S AS PREVIOUSLY
 REQUESTED CAN NOT BE VERIFIED AS THE
 FIXTURE SCHEDULE DOES NOT PROVIDE THE
 FIXTURE WATTAGE, TYPE ETC.
 IF DOING A SPACE BY SPACE METHOD ,
 PROVIDE BREAKDOWN OF AREAS.
 NOT ENOUGH INFORMATION TO VERIFY. MAX
 LPD'S.
 13-415.2, 13-415.2.ABC.1.
  
 3) NOTE: PLEASE SEE ATTACHED NOTICE
 GIVEN WITH RESPECT TO DESIGN
 PROFESSIONALS AND FS 553.80(2)(B).
 THIS IS BEING GIVEN AS A NOTICE AT THIS
 TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-24 Cont ID  
Sent By dpalmer Date 2006-08-24 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2006-08-23 Time 20:20 Sent To  
Notes
2006-08-24 00:00:00** UNSAT **
  
 ** PLEASE SEE SOME COMMENTS FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE ONE NEW COMMENT.
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AS NOTED.
  
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE TIME CLOCK,
 SCHEDULING, LOCATION IS NOT SHOWN.
 PLEASE SEE MISSING OVER RIDES FOR TC AND
 FOR SEPARATE SPACES.
 PLEASE SEE MISSING DEVICES TYPES, ETC.
 PLEASE SEE MISSING LPD FOR MAX WATTAGE
 PERMITTED AND DESIGN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13
 13-415.1.ABC.1.1, .1.2, AND .1.3 FOR
 LIGHTING CONTROLS, SCHEDULING,
 OVER-RIDES DEVICES AND LOCATIONS.
 PLEASE ALSO INDICATE THE TYPE OF OVER
 RIDE DEVICE(S) ALONG WITH MAX TIME OF
 4HRS PERMITTED FOR TIMER TYPE DEVICES
 AND 30 MINS FOR OCC SENSOR, TYPES.
 PLEASE PROVIDE LPD FOR SPACE.
 13-415.2.ABC.1, 415.2.C.1, 415.2.B.1
  
 4) NOTE:OK, HOWEVER PLEASE BE SURE TO
 DO THE SAME WHEN CHNAGING OUT PLANS FOR
 NEW SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 **IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND BEFORE
 PLANS ARE RESUBMITTED, PLEASE COMPLETELY
 REVMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE ONLY.
 ** PLEASE KNOW, THIS WILL HELP IN
 EXPEDITING THE PROJECT AND AVOID ANY
 POSSIBLE DELAYS.
  
 5) NOTE: NO, PLEASE SEE ONLY ONE OF THE
 BELOW ARE STATED ON THE COVER SHEET.
 PLEASE BE SURE DESIGN CODES ARE ON
 ELECTRICAL PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ALL THE CURRENT
 ADOPTED CODES AS FOLLOWS SHALL BE
 REFERENCED ON PLANS.
 PLANS STATE LATEST ADOPTED ETC.
 PLEASE PROVIDE THE FOLLOWING AT A MIN,
 2004 FBC, 2002 NFPA-70(NEC), 2002
 NFPA-72, 2003 NFPA-101.
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES.
  
 ** NEW NOTE **
  
 6) NOTE: PLEASE VERIFY NEW OR EXISTING
 SHOW WINDOW RECEPTS LOCATIONS.
 PLEASE SEE A NOTE ON PLANS MENTIONS THE
 SHOW WINDOW RECEPTS BEING CONTROLLED,
 HOWEVER NO RECEPTS SHOWN ON PLANS AND NO
 CIRCUITS LISTED ON PANEL SCHEDULE.
 210.62, 220.12
  
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 20:03 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 19:44 Sent To  
Notes
2006-07-15 00:00:00********** UNSAT **********
  
 1) NOTE: PLEASE VERIFY "TAPPED"
 CONDUCTORS FROM GUTTER TO PANEL AND A/C
 DISCONNECT.
 240.21,310.16, 215.5
  
 2) NOTE: PLEASE SEE RISER MENTIONS TO
 REPLACE EXISTING 100A BRKR WITH NEW 150A
 BRKR, HOWEVER IS IS UNCLEAR THE RATING
 OF THE BRKR ENCLOSURE AND METER IS??
 PLEASE PROVIDE INFORMATION ON THIS.
 FBC 106.1.2, ADMIN SECT.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13
 13-415.1.ABC.1.1, .1.2, AND .1.3 FOR
 LIGHTING CONTROLS, SCHEDULING,
 OVER-RIDES DEVICES AND LOCATIONS.
 PLEASE ALSO INDICATE THE TYPE OF OVER
 RIDE DEVICE(S0 ALONG WITH MAX TIME OF
 4HRS PERMITTED FOR TIMER TYPE DEVICES
 AND 30 MINS FOR OCC SENSOR, TYPES.
 PLEASE PROVIDE LPD FOR SPACE.
 13-415.2.AABC.1, 415.2.C.1, 415.2.B.1
  
 4) NOTE: **IMPORTANT**
  
 ONCE ALL REVIEWS ARE DONE AND BEFORE
 PLANS ARE RESUBMITTED, PLEASE COMPLETELY
 REVMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE ONLY.
 ** PLEASE KNOW, THIS WILL HELP IN
 EXPEDITING THE PROJECT AND AVOID ANY
 POSSIBLE DELAYS.
  
 5) NOTE: PLEASE KNOW, ALL THE CURRENT
 ADOPTED CODES AS FOLLOWS SHALL BE
 REFERENCED ON PLANS.
 PLANS STATE LATEST ADOPTED ETC.
 PLEASE PROVIDE THE FOLLOWING AT A MIN,
 2004 FBC, 2002 NFPA-70(NEC), 2002
 NFPA-72, 2003 NFPA-101.
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-18 Cont ID  
Sent By mwennerg Date 2006-10-18 Time 10:46 Rev Time 0.00
Received By mwennerg Date 2006-10-18 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-31 Cont ID  
Sent By mwennerg Date 2006-08-31 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2006-08-31 Time 11:16 Sent To  
Notes
2006-08-31 00:00:00***DENIED***
  
 PLEASE SEE SOME FIRE COMMENTS FROM FIRST
 REVIEW AND NEW COMMENT:
  
 1) NO RESPONSE FOUND.
  
 2) NO RESPONSE FOUND.
  
 3) NO RESPONSE FOUND.
  
 4) NO RESPONSE FOUND.
  
 5) OK
  
 6) OK- PLEASE INCLUDE MANUFACTURER SPEC
 SHEETS.
  
 7) OK
  
 NEW COMMENT
  
 8) PLEASE SHOW LOCATIONS OF 2A-10B,C
 RATED FIRE EXTINGUISHER(S).
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 14:20 Sent To  
Notes
2006-07-11 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. GASOLINE POWERED DEMOLITION EQUIPMENT
 SHALL NOT BE USED WITHOUT ADEQUATE
 VENTILATION. CARBON MONOXIDE WHICH IS
 COLORLESS, ODORLESS, AND TASTELESS CAN
 BE PRODUCED AND CAUSE SERIOUS ILLNESS OR
 DEATH.
  
 4. WHY IS THERE AN EXIT SIGN IN THE REAR
 OF THE SPACE WHEN THERE APPEARS TO BE NO
 REAR EXIT DOOR. PLEASE REVISE PLANS AS
 NECESSARY.
  
 5. PLANS NEED TO ILLUSTRATE TENANT
 SEPARATION WALLS.
  
 6. WHAT TYPE OF LIGHT BULBS ARE PLANNED
 TO BE USED IN THE MANICURE AREA.
 FLAMMABLE AND COMBUSTIBLE VAPORS WILL BE
 PRESENT DIRECTLY UNDER LIGHT FIXTURE
 BULBS. PROBLEMS HAVE OCCURRED IN THE
 PAST IN THESE PARTICULAR AREAS WHERE
 SIGNIFICANT CONCENTRATION OF THESE
 VAPORS ARE PRESENT.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-08 Cont ID  
Sent By adarroug Date 2006-12-08 Time 14:35 Rev Time 0.00
Received By adarroug Date 2006-12-08 Time 14:35 Sent To E
Notes
2006-12-08 14:36:48TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-28 Cont ID  
Sent By adarroug Date 2006-09-28 Time 13:20 Rev Time 0.00
Received By adarroug Date 2006-09-28 Time 13:20 Sent To  
Notes
2006-09-29 00:00:00TO "BOB"#14
2006-09-28 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 10:39 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 10:39 Sent To  
Notes
2006-08-22 00:00:00TO "BOB"#13
2006-08-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-17 Time   Rev Time 0.00
Received By adarroug Date 2006-07-01 Time 16:04 Sent To  
Notes
2006-07-05 00:00:00TO "BOB"#17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-06 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 11:36 Rev Time 0.30
Received By tgordon Date 2006-07-06 Time 13:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-14 Cont ID  
Sent By jleech Date 2006-10-14 Time 13:58 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-26 Cont ID  
Sent By jleech Date 2006-08-26 Time 10:24 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 10:24 Sent To  
Notes
2006-08-26 00:00:00DENIED;
 1.(SECOND REQUEST) SHOW BACKFLOW
 PREVENTOR ON PLANS, WITH DETAIL OF AIR
 GAP DRAIN AND POINT OF DISPOSAL.
 2.SHOW BATHROOM FLOOR DRAIN WITH TRAP
 PRIMER ON DRAWINGS. FLOOR PLAN, AND
 RISER DIAGRAMS.
 3.WATER HEATER DIAGRAM; COLD WATER SHUT
 OFF VALVE TO BE INSTALLED BEFORE THE
 EXPANSION TANK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 14:24 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 14:24 Sent To  
Notes
2006-07-08 00:00:00DENIED;
 1.SUBMIT SPECIFICATION SHEET FOR
 PEDICURE CHAIRS AND ADD A DETAIL SHOWING
 HOW THE CHAIRS WILL BE INSTALLED.
 2.SHOW BACKFLOW PREVENTOR ON PLANS WITH
 DETAIL OF AIR GAP DRAIN AND POINT OF
 TERMINATION.
 3.HANDICAP DRINKING FOUNTAIN IS REQUIRED
 TO HAVE A CUP DISPENSOR FOR PEOPLE WITH
 BAD BACKS SEC.11-4.1.3(10).
 4.PEDICURE CHAIR'S SANITARY BRANCH
 DRAINS ARE NOT VENTED.
 5.SHOW ON DRAWINGS COMPLIANCE TO
 FBC-2004 PLUMBING TABLE 403.1 2(B) LIST
 EMPLOYEES AND CUSTOMERS.
 6.SANITARY ISOMETRIC; AUTOMATIC CLOTHES
 WASHER BRANCH DRAIN IS REQUIRED TO BE 3"
 SEC.406.3.
 7.WATER HEATER DETAIL; SHOW LOCATION AND
 TERMINATION OF FUNNEL, AND PAN DRAINS.
 8.SHOW ON WATER HEATER DETAIL THE
 LOCATION OF THE EXPANSION TANK, ON COLD
 WATER SIDE AFTER THE W/H SHUTOFF VALVE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved