| Plan Review Stops For Permit 06061662 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-23 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-23 |
Time |
10:47 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-01 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-08-31 |
Time |
15:35 |
Sent To |
PC |
|
| Notes |
| 2006-09-01 00:00:00 | | | | 1) OK. | | | | | | 2) OK | | | | | | 3) SHOW THE EXIT DOOR IN THE REAR OF THE | | | BUILDING WHERE THE EXIT LIGHT IS. SEE | | | REFLECTED CEILING PLAN SHEET A-2. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-07-17 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-07-17 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2006-07-17 00:00:00 | 1) 110.2* W. P. B. ADMINISTRATIVE CODE, | | | INFORMATION THAT IS REQUIRED FOR RECORD | | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | ------------------------------------- | | | ) NUMBER OF FLOORS | | | ) SQ. FT. FOOTPRINT | | | ) SQ. FT. UNDER ROOF (TOTAL) | | | ) OCCUPANT LOAD | | | ) FLOOD ZONE | | | | | | 2) 11-7.2 SALES AND SERVICE COUNTERS, | | | TELLER WINDOWS, INFORMATION COUNTERS. | | | (1) IN DEPARTMENT STORES AND | | | MISCELLANEOUS RETAIL STORES WHERE | | | COUNTERS HAVE CASH REGISTERS AND ARE | | | PROVIDED FOR SALES OR DISTRIBUTION OF | | | GOODS OR SERVICES TO THE PUBLIC, AT | | | LEAST ONE OF EACH TYPE SHALL HAVE A | | | PORTION OF THE COUNTER WHICH IS AT LEAST | | | 36 INCHES (915 MM) IN LENGTH WITH A | | | MAXIMUM HEIGHT OF 36 INCHES (915 MM) | | | ABOVE THE FINISH FLOOR. IT SHALL BE ON | | | AN ACCESSIBLE ROUTE COMPLYING WITH | | | SECTION 11-4.3 . THE ACCESSIBLE COUNTERS | | | MUST BE DISPERSED THROUGHOUT THE | | | BUILDING OR FACILITY. IN ALTERATIONS | | | WHERE IT IS TECHNICALLY INFEASIBLE TO | | | PROVIDE AN ACCESSIBLE COUNTER, AN | | | AUXILIARY COUNTER MEETING THESE | | | REQUIREMENTS MAY BE PROVIDED. PROVIDE | | | THE ELEVATION DETAILS OF THE CHECK OUT | | | COUNTER. | | | | | | 3) SHOW THE EXIT DOOR IN THE REAR OF THE | | | BUILDING WHERE THE EXIT LIGHT IS. SEE | | | REFLECTED CEILING PLAN SHEET A-2. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-12-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-09 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-09 |
Time |
16:16 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-01 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-01 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2006-10-01 00:00:00 | IN ELEC | | | ** UNSAT 3RD REVIEW ** | | | | | | 1) NOTE: PLEASE SEE THE OVER-RIDE | | | DEVICES SHALL ALL BE SHOWN ON PLANS | | | WHICH OVER RIDE "SYSTEM". PLEASE SEE | | | INGRESS /EGRESS AREAS WHICH ONE "S" IS | | | SHOWN HOWEVER PLANS DO NOT DELINEATE THE | | | DEVICE BEING USED FOR OVER RIDE."TYPE"?. | | | PLEASE SEE ALSO ENTRANCE "S' WHICH IS | | | ALSO REQUIRED OVER-RIDE SYSTEM. SAME | | | NOTE. | | | PLEASE KNOW AS STATED ON PREVIOUS REVIEW | | | THE TYPE OF DEVICES MUST STATE THE MAX | | | TIME ON OVER-RIDE DEPENDING ON DEVICE | | | BEING CHOSEN. | | | MOTION/OCUPANT SENSOR TYPE (30MINS MAX), | | | TIMER TYPE 4HRS MAX). | | | | | | 2) NOTE: PLEASE SEE LPD'S AS PREVIOUSLY | | | REQUESTED CAN NOT BE VERIFIED AS THE | | | FIXTURE SCHEDULE DOES NOT PROVIDE THE | | | FIXTURE WATTAGE, TYPE ETC. | | | IF DOING A SPACE BY SPACE METHOD , | | | PROVIDE BREAKDOWN OF AREAS. | | | NOT ENOUGH INFORMATION TO VERIFY. MAX | | | LPD'S. | | | 13-415.2, 13-415.2.ABC.1. | | | | | | 3) NOTE: PLEASE SEE ATTACHED NOTICE | | | GIVEN WITH RESPECT TO DESIGN | | | PROFESSIONALS AND FS 553.80(2)(B). | | | THIS IS BEING GIVEN AS A NOTICE AT THIS | | | TIME. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-24 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-23 |
Time |
20:20 |
Sent To |
|
|
| Notes |
| 2006-08-24 00:00:00 | ** UNSAT ** | | | | | | ** PLEASE SEE SOME COMMENTS FROM FIRST | | | REVIEW STILL NEED TO BE ADDRESSED. | | | PLEASE SEE ONE NEW COMMENT. | | | NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW AS NOTED. | | | | | | | | | | | | 1) NOTE: OK. | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: NO, PLEASE SEE TIME CLOCK, | | | SCHEDULING, LOCATION IS NOT SHOWN. | | | PLEASE SEE MISSING OVER RIDES FOR TC AND | | | FOR SEPARATE SPACES. | | | PLEASE SEE MISSING DEVICES TYPES, ETC. | | | PLEASE SEE MISSING LPD FOR MAX WATTAGE | | | PERMITTED AND DESIGN. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE FBC CHAPTER 13 | | | 13-415.1.ABC.1.1, .1.2, AND .1.3 FOR | | | LIGHTING CONTROLS, SCHEDULING, | | | OVER-RIDES DEVICES AND LOCATIONS. | | | PLEASE ALSO INDICATE THE TYPE OF OVER | | | RIDE DEVICE(S) ALONG WITH MAX TIME OF | | | 4HRS PERMITTED FOR TIMER TYPE DEVICES | | | AND 30 MINS FOR OCC SENSOR, TYPES. | | | PLEASE PROVIDE LPD FOR SPACE. | | | 13-415.2.ABC.1, 415.2.C.1, 415.2.B.1 | | | | | | 4) NOTE:OK, HOWEVER PLEASE BE SURE TO | | | DO THE SAME WHEN CHNAGING OUT PLANS FOR | | | NEW SHEETS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | **IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND BEFORE | | | PLANS ARE RESUBMITTED, PLEASE COMPLETELY | | | REVMOVE ALL OLD/VOIDED SHEETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | ONE SET OF THE OLD/VOIDED SHEETS SHOULD | | | BE SUBMITTED FOR REFERENCE ONLY. | | | ** PLEASE KNOW, THIS WILL HELP IN | | | EXPEDITING THE PROJECT AND AVOID ANY | | | POSSIBLE DELAYS. | | | | | | 5) NOTE: NO, PLEASE SEE ONLY ONE OF THE | | | BELOW ARE STATED ON THE COVER SHEET. | | | PLEASE BE SURE DESIGN CODES ARE ON | | | ELECTRICAL PLANS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE KNOW, ALL THE CURRENT | | | ADOPTED CODES AS FOLLOWS SHALL BE | | | REFERENCED ON PLANS. | | | PLANS STATE LATEST ADOPTED ETC. | | | PLEASE PROVIDE THE FOLLOWING AT A MIN, | | | 2004 FBC, 2002 NFPA-70(NEC), 2002 | | | NFPA-72, 2003 NFPA-101. | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES. | | | | | | ** NEW NOTE ** | | | | | | 6) NOTE: PLEASE VERIFY NEW OR EXISTING | | | SHOW WINDOW RECEPTS LOCATIONS. | | | PLEASE SEE A NOTE ON PLANS MENTIONS THE | | | SHOW WINDOW RECEPTS BEING CONTROLLED, | | | HOWEVER NO RECEPTS SHOWN ON PLANS AND NO | | | CIRCUITS LISTED ON PANEL SCHEDULE. | | | 210.62, 220.12 | | | | | | | | | ** PLEASE SEE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
20:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-15 |
Time |
19:44 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | ********** UNSAT ********** | | | | | | 1) NOTE: PLEASE VERIFY "TAPPED" | | | CONDUCTORS FROM GUTTER TO PANEL AND A/C | | | DISCONNECT. | | | 240.21,310.16, 215.5 | | | | | | 2) NOTE: PLEASE SEE RISER MENTIONS TO | | | REPLACE EXISTING 100A BRKR WITH NEW 150A | | | BRKR, HOWEVER IS IS UNCLEAR THE RATING | | | OF THE BRKR ENCLOSURE AND METER IS?? | | | PLEASE PROVIDE INFORMATION ON THIS. | | | FBC 106.1.2, ADMIN SECT. | | | | | | 3) NOTE: PLEASE SEE FBC CHAPTER 13 | | | 13-415.1.ABC.1.1, .1.2, AND .1.3 FOR | | | LIGHTING CONTROLS, SCHEDULING, | | | OVER-RIDES DEVICES AND LOCATIONS. | | | PLEASE ALSO INDICATE THE TYPE OF OVER | | | RIDE DEVICE(S0 ALONG WITH MAX TIME OF | | | 4HRS PERMITTED FOR TIMER TYPE DEVICES | | | AND 30 MINS FOR OCC SENSOR, TYPES. | | | PLEASE PROVIDE LPD FOR SPACE. | | | 13-415.2.AABC.1, 415.2.C.1, 415.2.B.1 | | | | | | 4) NOTE: **IMPORTANT** | | | | | | ONCE ALL REVIEWS ARE DONE AND BEFORE | | | PLANS ARE RESUBMITTED, PLEASE COMPLETELY | | | REVMOVE ALL OLD/VOIDED SHEETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | ONE SET OF THE OLD/VOIDED SHEETS SHOULD | | | BE SUBMITTED FOR REFERENCE ONLY. | | | ** PLEASE KNOW, THIS WILL HELP IN | | | EXPEDITING THE PROJECT AND AVOID ANY | | | POSSIBLE DELAYS. | | | | | | 5) NOTE: PLEASE KNOW, ALL THE CURRENT | | | ADOPTED CODES AS FOLLOWS SHALL BE | | | REFERENCED ON PLANS. | | | PLANS STATE LATEST ADOPTED ETC. | | | PLEASE PROVIDE THE FOLLOWING AT A MIN, | | | 2004 FBC, 2002 NFPA-70(NEC), 2002 | | | NFPA-72, 2003 NFPA-101. | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES. | | | | | | | | | ** PLEASE SEE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-10-18 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-10-18 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-08-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-31 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-31 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2006-08-31 00:00:00 | ***DENIED*** | | | | | | PLEASE SEE SOME FIRE COMMENTS FROM FIRST | | | REVIEW AND NEW COMMENT: | | | | | | 1) NO RESPONSE FOUND. | | | | | | 2) NO RESPONSE FOUND. | | | | | | 3) NO RESPONSE FOUND. | | | | | | 4) NO RESPONSE FOUND. | | | | | | 5) OK | | | | | | 6) OK- PLEASE INCLUDE MANUFACTURER SPEC | | | SHEETS. | | | | | | 7) OK | | | | | | NEW COMMENT | | | | | | 8) PLEASE SHOW LOCATIONS OF 2A-10B,C | | | RATED FIRE EXTINGUISHER(S). | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-07-11 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-07-11 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. GASOLINE POWERED DEMOLITION EQUIPMENT | | | SHALL NOT BE USED WITHOUT ADEQUATE | | | VENTILATION. CARBON MONOXIDE WHICH IS | | | COLORLESS, ODORLESS, AND TASTELESS CAN | | | BE PRODUCED AND CAUSE SERIOUS ILLNESS OR | | | DEATH. | | | | | | 4. WHY IS THERE AN EXIT SIGN IN THE REAR | | | OF THE SPACE WHEN THERE APPEARS TO BE NO | | | REAR EXIT DOOR. PLEASE REVISE PLANS AS | | | NECESSARY. | | | | | | 5. PLANS NEED TO ILLUSTRATE TENANT | | | SEPARATION WALLS. | | | | | | 6. WHAT TYPE OF LIGHT BULBS ARE PLANNED | | | TO BE USED IN THE MANICURE AREA. | | | FLAMMABLE AND COMBUSTIBLE VAPORS WILL BE | | | PRESENT DIRECTLY UNDER LIGHT FIXTURE | | | BULBS. PROBLEMS HAVE OCCURRED IN THE | | | PAST IN THESE PARTICULAR AREAS WHERE | | | SIGNIFICANT CONCENTRATION OF THESE | | | VAPORS ARE PRESENT. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-08 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-08 |
Time |
14:35 |
Sent To |
E |
|
| Notes |
| 2006-12-08 14:36:48 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-28 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-28 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | TO "BOB"#14 | | 2006-09-28 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-08-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-14 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-14 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2006-08-22 00:00:00 | TO "BOB"#13 | | 2006-08-14 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-07-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-01 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2006-07-05 00:00:00 | TO "BOB"#17 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-01 |
Time |
11:36 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-07-06 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-14 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-14 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-08-26 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-08-26 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2006-08-26 00:00:00 | DENIED; | | | 1.(SECOND REQUEST) SHOW BACKFLOW | | | PREVENTOR ON PLANS, WITH DETAIL OF AIR | | | GAP DRAIN AND POINT OF DISPOSAL. | | | 2.SHOW BATHROOM FLOOR DRAIN WITH TRAP | | | PRIMER ON DRAWINGS. FLOOR PLAN, AND | | | RISER DIAGRAMS. | | | 3.WATER HEATER DIAGRAM; COLD WATER SHUT | | | OFF VALVE TO BE INSTALLED BEFORE THE | | | EXPANSION TANK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-08 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-08 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2006-07-08 00:00:00 | DENIED; | | | 1.SUBMIT SPECIFICATION SHEET FOR | | | PEDICURE CHAIRS AND ADD A DETAIL SHOWING | | | HOW THE CHAIRS WILL BE INSTALLED. | | | 2.SHOW BACKFLOW PREVENTOR ON PLANS WITH | | | DETAIL OF AIR GAP DRAIN AND POINT OF | | | TERMINATION. | | | 3.HANDICAP DRINKING FOUNTAIN IS REQUIRED | | | TO HAVE A CUP DISPENSOR FOR PEOPLE WITH | | | BAD BACKS SEC.11-4.1.3(10). | | | 4.PEDICURE CHAIR'S SANITARY BRANCH | | | DRAINS ARE NOT VENTED. | | | 5.SHOW ON DRAWINGS COMPLIANCE TO | | | FBC-2004 PLUMBING TABLE 403.1 2(B) LIST | | | EMPLOYEES AND CUSTOMERS. | | | 6.SANITARY ISOMETRIC; AUTOMATIC CLOTHES | | | WASHER BRANCH DRAIN IS REQUIRED TO BE 3" | | | SEC.406.3. | | | 7.WATER HEATER DETAIL; SHOW LOCATION AND | | | TERMINATION OF FUNNEL, AND PAN DRAINS. | | | 8.SHOW ON WATER HEATER DETAIL THE | | | LOCATION OF THE EXPANSION TANK, ON COLD | | | WATER SIDE AFTER THE W/H SHUTOFF VALVE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|