Plan Review Details - Permit 06061640
Plan Review Stops For Permit 06061640
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-04 Cont ID  
Sent By shill Date 2006-08-04 Time 16:47 Rev Time 0.00
Received By shill Date 2006-08-04 Time 16:47 Sent To  
Notes
2006-08-04 00:00:00PROVISO - PROVIDE CORRECTED ENGINEERING
 AT INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-04 Cont ID  
Sent By shill Date 2006-08-04 Time 16:45 Rev Time 0.00
Received By shill Date 2006-08-04 Time 16:45 Sent To  
Notes
2006-08-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)THE ENGINEER'S CALCULATION FOR THE
 ENHANCED FASTENING FOR ZONES 2 AND 3
 SPECIFY A DESIGN PRESSURE OF -60PSF.
 THE APPROVED ASSEMBLY YOU HAVE CHOSEN
 HAS A DESIGN PRESSURE OF -52.5.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-17 Cont ID  
Sent By shill Date 2006-07-17 Time 15:52 Rev Time 0.00
Received By shill Date 2006-07-17 Time 15:52 Sent To  
Notes
2006-07-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 SEE PRODUCT LIMITATION #7, FLINTLASTIC
 NOA; REQUIRES CALCULATIONS FROM AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-05 Cont ID  
Sent By shill Date 2006-07-05 Time 15:23 Rev Time 0.00
Received By shill Date 2006-07-05 Time 15:23 Sent To  
Notes
2006-07-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
  
 _XX_1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE
 MEAN ROOF HEIGHT ON THE APPLICATION.
  
 ____3.)CONTRACTOR IS TO PROVIDE THE
 ROOF PITCH ON THE APPLICATION.
  
 ____4.)CONTRACTOR IS TO PROVIDE THE
 ROOF DECK TYPE ON THE APPLICATION.
  
 _XX_5.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____7.)THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ____.
  
 ____8.)THE SYSTEM PROVIDED STATES
 LIMITATION #9, ENHANCED FASTENING NOT
 ALLOWED.
  
 ____9.)PROVIDE AN ENGINEER?S LETTER
 TO CONFIRM THAT THE ROOF WHICH CURRENTLY
 HAS SHINGLES INSTALLED CAN ACCOMMODATE
 THE ADDITIONAL WEIGHT OF THE PROPOSED
 TILE.
  
 ____ 10.)ON THE TILE PRODUCT APPROVAL,
 INDICATE WHICH METHOD OF ATTACHMENT YOU
 ARE USING.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 14:53 Sent To B
Notes
2006-07-27 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 15:38 Sent To B
Notes
2006-07-17 00:00:00TO "SHILL" DESK/RESUB