Plan Review Details - Permit 06061623
Plan Review Stops For Permit 06061623
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2007-08-20 Time 11:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-10 Cont ID  
Sent By mjacobs Date 2007-08-10 Time 17:24 Rev Time 0.00
Received By mjacobs Date 2007-08-10 Time 16:28 Sent To  
Notes
2007-08-10 17:24:33BUILDING PLAN REVIEW
 PERMIT:06061623
 ADD: 5403 N.HAVERHILL RD
 CONT: MILESTONE CUSTOMS HOMES
 TEL: (561)436-4733
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW REV.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 *****NO RESPONSE NOT ADDRESSED
  
 SUBMIT A LETTER DATED/SIGN/SEALED AND NOTORIZE FROM THE
 REGISTERED ARCHITECT OR ENGINEER WHO IS TAKING ALL
 PROFESSIONAL AND LEGAL RESPONSIBILITY AS STATED IN THE
 FLORIDA ADMINISTRATIVE CODE SECTION BELOW.
 2)61G1-18.002PROCEDURES FOR A SUCCESSOR ARCHITECT
 ADOPTING AS HIS OWN THE WORK OF ANOTHER ARCHITECT. (1)
 A SUCCESSOR REGISTERED ARCHITECT SEEKING TO REUSE
 ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR
 REGISTERED ARCHITECT'S SEAL MUST BE ABLE TO DOCUMENT
 AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT
 RECREATED ALL THE WORK DONE BY THE ORIGINAL REGISTERED
 ARCHITECT. FURTHER, THE SUCCESSOR REGISTERED ARCHITECT
 MUST TAKE ALL PROFESSIONAL AND LEGAL RESPONSIBILITY FOR
 THE DOCUMENTS WHICH HE SEALED AND SIGNED AND CAN IN NO
 WAY EXEMPT HIMSELF FROM SUCH FULL RESPONSIBILITY. PLANS
 NEED NOT BE REDRAWN BY THE SUCCESSOR REGISTERED
 ARCHITECT; HOWEVER, JUSTIFICATION FOR SUCH ACTION MUST
 BE AVAILABLE THROUGH WELL KEPT AND COMPLETE
 DOCUMENTATION ON THE PART OF THE SUCCESSOR REGISTERED
 ARCHITECT AS TO HIS HAVING RETHOUGHT AND REWORKED THE
 ENTIRE DESIGN PROCESS. A SUCCESSOR REGISTERED ARCHITECT
 MUST USE HIS OWN TITLE BLOCK, SEAL AND SIGNATURE AND
 MUST REMOVE THE TITLE BLOCK, SEAL AND SIGNATURE OF THE
 ORIGINAL REGISTERED ARCHITECT BEFORE SEALING, SIGNING
 AND DATING ANY SEALED CONTRACT DOCUMENTS.
 (2) PRIOR TO SEALING, SIGNING AND DATING WORK, A
 SUCCESSOR REGISTERED ARCHITECT SHALL BE REQUIRED TO
 NOTIFY THE ORIGINAL REGISTERED ARCHITECT, HIS
 SUCCESSORS, OR ASSIGNS BY CERTIFIED LETTER TO THE LAST
 KNOWN ADDRESS OF THE ORIGINAL REGISTERED ARCHITECT OF
 THE SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL
 REGISTERED ARCHITECT'S WORK. THE SUCCESSOR REGISTERED
 ARCHITECT WILL TAKE FULL RESPONSIBILITY FOR THE DRAWING
 AS THOUGH THEY WERE THE SUCCESSOR REGISTERED
 ARCHITECT'S ORIGINAL PRODUCT.
 SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED
 481.221(4) FS. HISTORY?NEW 1-16-86, AMENDED 5-16-89,
 FORMERLY 21B-18.002.
  
 3)SUBMIT TWO COMPLETE SETS OF DRAWINGS NOT LOOSE
 PAGES WITH THE REQUIRED INFORMATION AS STATED ABOVE.
 SEE F.A.C.61G15-23.002 (2) ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET.61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) "A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT."
  
 4)RWB LINARES ARCHITECTURE SHALL SUBMIT AN ORIGINAL
 LEGIBLE SIGN/ SEAL AND NOTORIZE LETTER TAKING FULL
 RESPONSIBLILTY OF THE PROJECT. ALL SIGNATURES ON THE
 LETTER SHALL BE ORIGINAL.
 NEW***************************************************
 *
  
 A)SHEET A3.09 #3 THE DOORS SHALL BE REMOVED TO
 PROVIDE THE FORWARD APPROACH. FBC 11-4.21.5
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-11 Cont ID  
Sent By mjacobs Date 2007-04-11 Time 18:04 Rev Time 0.00
Received By mjacobs Date 2007-04-11 Time 16:11 Sent To  
Notes
2007-04-11 18:04:12BUILDING PLAN REVIEW
 PERMIT:06061623
 ADD: 5403 N.HAVERHILL RD
 CONT: MILESTONE CUSTOMS HOMES
 TEL: (561)436-4733
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW REV.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G1-18.002PROCEDURES FOR A SUCCESSOR ARCHITECT
 ADOPTING AS HIS OWN THE WORK OF ANOTHER ARCHITECT. (1)
 A SUCCESSOR REGISTERED ARCHITECT SEEKING TO REUSE
 ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR
 REGISTERED ARCHITECT'S SEAL MUST BE ABLE TO DOCUMENT
 AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT
 RECREATED ALL THE WORK DONE BY THE ORIGINAL REGISTERED
 ARCHITECT. FURTHER, THE SUCCESSOR REGISTERED ARCHITECT
 MUST TAKE ALL PROFESSIONAL AND LEGAL RESPONSIBILITY FOR
 THE DOCUMENTS WHICH HE SEALED AND SIGNED AND CAN IN NO
 WAY EXEMPT HIMSELF FROM SUCH FULL RESPONSIBILITY. PLANS
 NEED NOT BE REDRAWN BY THE SUCCESSOR REGISTERED
 ARCHITECT; HOWEVER, JUSTIFICATION FOR SUCH ACTION MUST
 BE AVAILABLE THROUGH WELL KEPT AND COMPLETE
 DOCUMENTATION ON THE PART OF THE SUCCESSOR REGISTERED
 ARCHITECT AS TO HIS HAVING RETHOUGHT AND REWORKED THE
 ENTIRE DESIGN PROCESS. A SUCCESSOR REGISTERED ARCHITECT
 MUST USE HIS OWN TITLE BLOCK, SEAL AND SIGNATURE AND
 MUST REMOVE THE TITLE BLOCK, SEAL AND SIGNATURE OF THE
 ORIGINAL REGISTERED ARCHITECT BEFORE SEALING, SIGNING
 AND DATING ANY SEALED CONTRACT DOCUMENTS.
 (2) PRIOR TO SEALING, SIGNING AND DATING WORK, A
 SUCCESSOR REGISTERED ARCHITECT SHALL BE REQUIRED TO
 NOTIFY THE ORIGINAL REGISTERED ARCHITECT, HIS
 SUCCESSORS, OR ASSIGNS BY CERTIFIED LETTER TO THE LAST
 KNOWN ADDRESS OF THE ORIGINAL REGISTERED ARCHITECT OF
 THE SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL
 REGISTERED ARCHITECT'S WORK. THE SUCCESSOR REGISTERED
 ARCHITECT WILL TAKE FULL RESPONSIBILITY FOR THE DRAWING
 AS THOUGH THEY WERE THE SUCCESSOR REGISTERED
 ARCHITECT'S ORIGINAL PRODUCT.
 SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED
 481.221(4) FS. HISTORY?NEW 1-16-86, AMENDED 5-16-89,
 FORMERLY 21B-18.002.
  
 3)SUBMIT TWO COMPLETE SETS OF DRAWINGS NOT LOOSE
 PAGES WITH THE REQUIRED INFORMATION AS STATED ABOVE.
 SEE F.A.C.61G15-23.002 (2) ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET.61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4)RWB LINARES ARCHITECTURE SHALL SUBMIT AN ORIGINAL
 LEGIBLE LETTER TAKING FULL RESPONSIBLILTY OF THE
 PROJECT. ALL SIGNATURES ON THE LETTER SHALL BE
 ORIGINAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By alange Date 2006-09-26 Time 08:16 Rev Time 0.00
Received By alange Date 2006-09-26 Time 08:03 Sent To  
Notes
2006-09-26 00:00:001. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.SHOW DISCRIPTION OF
 PROJECT ON NOTICE OF COMMENCEMENT.
  
  
 IMPORTANT:
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE AND REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By alange Date 2006-07-19 Time 08:29 Rev Time 0.00
Received By alange Date 2006-07-19 Time 08:29 Sent To  
Notes
2006-07-19 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 3.MEZZANINE SHALL BE OPEN AND
 UNOBSTRUCTED TO THE ROOM IN WHICH SUCH
 MEZZANINE IS LOCATED EXCEPT FOR WALLS
 NOT MORE THAN 42 INCHES HIGH, COLUMNS
 AND POSTS. FBC 505.4 OPENNESS
  
 4.FBC 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS.
 LIFE SAFTEY PLAN INCLUDING EGRESS,
 INTERIOR ELEVATIONS, OCCUPANT LOADS,
 CONSTRUCTION TYPE, ROOM HEIGHT AND IF
 BUILDING HAS SPRINKLERS.
  
 5.SHOW STAIR DETAILS COMPLYING WITH
 FBC 1009.3
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-06-27 Cont ID  
Sent By btrobaug Date 2007-06-27 Time 06:57 Rev Time 0.00
Received By btrobaug Date 2007-06-27 Time 06:57 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-01 Cont ID  
Sent By btrobaug Date 2007-05-01 Time 08:08 Rev Time 1.00
Received By btrobaug Date 2007-05-01 Time 07:35 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-09 Cont ID  
Sent By btrobaug Date 2007-04-09 Time 10:30 Rev Time 1.00
Received By btrobaug Date 2007-04-09 Time 07:43 Sent To PC
Notes
2007-04-09 10:30:16 
  
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE PROVIDE THE PANEL DESIGNATION AND CIRCUIT
 NUMBERS FOR ALL RECEPTACLES AND LIGHT FIXTURES AFFECTED
 UNDER THIS PERMIT. 106.3.5.1.2 FBC AS AMENDED.
  
 2} THE RECEPTACLE FOR THE REFRIGERATOR IN THE
 KITCHENETTE, SHEET E3.01, MUST BE GFI PER 210.8(B)(3),
 2002 NEC.
  
 3} PLEASE SHOW COMPLIANCE WITH MEANS OF ILLUMINATION
 FOR THE STAIRWELLS PER 1006.2FBC AND 7.9 NFPA-101.
  
 4} PLEASE GIVE THE RATING OF THE DISCONNECT FOR THE
 "NEW A/C UNIT" ON SHEET E3.01, AS WAS DONE FOR THE TWO
 EXISTING.
  
 5} THE LOADS HAVE BEEN REMOVED FROM THE PANEL SCHEDULES
 ON SHEET E3.03. PROVIDE THE CALCULATIONS PER 220 NEC
 AND SHOW CONNECTED LOADS.
  
 5} INDICATE THE LOCATIION AND ADD TO THE PANEL SCHEDULE
 THE ROOFTOP RECEPTACLE REQUIRED BY 210.63, NEC.
 AS APPLICABLE.
  
 PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE NOT
 ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE BY
 THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481, AS
 APPLICABLE.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By btrobaug Date 2006-09-19 Time 09:52 Rev Time 1.00
Received By btrobaug Date 2006-09-19 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 18:22 Rev Time 0.50
Received By btrobaug Date 2006-07-14 Time 18:05 Sent To  
Notes
2006-07-14 00:00:00 
  
 SHOW COMPLIANCE WITH CHAPTER 13 ENERGY
 CODE. INDICATE WHICH METHOD USED. SHOW
 LOCATIONS OF OCCUPANCY SENSORS, TIME
 CLOCKS ETC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 11:35 Rev Time 0.00
Received By mawillia Date 2007-08-20 Time 11:33 Sent To  
Notes
2007-08-20 11:35:05*****APPROVED*****
  
  
 STAIRS ARE EXISTING AND THE TENANTS ARE OCCUPYING THE
 SPACE UNDER A TCO.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-08-12 Cont ID  
Sent By mawillia Date 2007-08-12 Time 12:43 Rev Time 0.00
Received By mawillia Date 2007-08-12 Time 12:26 Sent To  
Notes
2007-08-12 12:43:19*****DENIED*****
  
  
 THE INFORMATION REQUESTED IN REFERENCE TO THE STAIRS
 STILL HAS NOT BEEN ADDRESSED.A COPY OF THE (3)
 PREVIOUS FIRE PLAN REVIEW HAS BEEN INCLUDED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 12:18 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 12:18 Sent To  
Notes
2007-04-13 12:21:06***DENIED***
  
 1) THOUGH REQUESTED FROM FIRST FIRE REVIEW,
 NO ADDITIONAL INFORMATION FOUND
 REGARDING STAIRS. ALL STAIRS SHALL
 COMPLY WITH NFPA 101, 2003 EDITION,
 SECTION 7.2.2.2.19(A). PLEASE PROVIDE
 NOTE REGARDING PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By mwennerg Date 2006-09-19 Time 11:15 Rev Time 0.00
Received By mwennerg Date 2006-09-19 Time 11:15 Sent To  
Notes
2006-09-19 00:00:00***PROVISO***
  
 THOUGH REQUESTED FROM FIRST FIRE REVIEW,
 NO ADDITIONAL INFORMATION FOUND
 REGARDING STAIRS. ALL STAIRS SHALL
 COMPLY WITH NFPA 101, 2003 EDITION,
 SECTION 7.2.2.2.19(A). PLEASE PROVIDE
 NOTE REGARDING PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 THIS WRITER UNDERSTANDS PRIOR APPROVAL,
 HOWEVER UPDATED OR NEW PLANS WILL BE
 REFERENCED DURING INSPECTION, AND SHOULD
 REFLECT REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 12:23 Sent To  
Notes
2006-07-10 00:00:001. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL OF THE
 EXISTING FIRE SPRINKLER SYSTEM.
  
 2. ALL NEW ACOUSTICAL CEILING TILES TO
 COMPLY WITH MINIMUM INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 3. PLEASE PROVIDE DETAILS ON MEZZANINE
 STAIRS. THIS INFORMATION TO INCLUDE RISE
 AND RUN OF STAIRS, TREAD SIZES AND
 DETAILS REGARDING HANDRAILS AND
 GUARDRAILS. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 08:39 Sent To  
Notes
2007-08-10 08:39:45TO BOB BOARD #12

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 14:12 Sent To  
Notes
2007-08-03 14:13:18WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 17:01 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 17:01 Sent To P
Notes
2007-06-24 17:01:48TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 14:37 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 14:30 Sent To E
Notes
2007-06-22 14:38:14TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 16:01 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 16:01 Sent To E
Notes
2007-04-30 16:03:27TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 18:11 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 18:11 Sent To  
Notes
2007-03-30 18:12:07TO BOB # 2

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 17:36 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 17:36 Sent To E
Notes
2007-03-30 17:36:30TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-23 Cont ID  
Sent By jleech Date 2006-10-23 Time 12:37 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 15:02 Sent To  
Notes
2006-10-14 15:03:08TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 16:32 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 16:32 Sent To  
Notes
2006-09-08 00:00:00TO "BOB"#8
2006-09-06 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-19 Cont ID  
Sent By alange Date 2006-07-19 Time 08:58 Rev Time 0.00
Received By alange Date 2006-07-06 Time 08:18 Sent To  
Notes
2006-07-06 00:00:00TO "BOB"#4

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-04-02 Cont ID  
Sent By tgordon Date 2007-04-02 Time 09:04 Rev Time 0.35
Received By tgordon Date 2007-04-02 Time 09:04 Sent To  
Notes
2007-04-02 09:10:55MECHANICAL REVISION
 *** DENIED ***
 1) NEED TO SUBMIT A LETTER FROM THE ENGINEER MARIO H.
 GUTIERREZ, AND THE ARCHITECT BUSINESS WOLFBERG/ ALVAREZ
 & PARTNERS, REMOVING THEM SELF'S FROM THE PROJECT. THE
 LETTER MAY NOT BE A COPY.
  
 2) PLEASE BE ADVISED ALL PAGES TO THE PLANS WILL NEED
 TO BE REVISED AS THE SET MAY NOT HAVE TWO DIFFERENT
 ARCHITECTS AND ENGINEERS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 15:56 Rev Time 0.30
Received By tgordon Date 2006-09-11 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-06 Cont ID  
Sent By tgordon Date 2006-07-06 Time 14:36 Rev Time 0.45
Received By tgordon Date 2006-07-06 Time 14:36 Sent To  
Notes
2006-07-06 00:00:00*** DENIED ***
 1) PAGE M3.01 OFFICE 032A AND 032B, 6"
 RETURN AIR TRANSFER DUCT NEES TO BE 8",
 SEE NOTE #4 (A).
  
 2) PAGE M3.02 OFFICE 031G AND 031H, 8"
 RETURN AIR TRANSFER DUCT NEEDS TO BE 10"
 SEE NOTE #4 (A).
  
 3) PLEASE ADD NOTE TO PAGE M3.03 .
 BATHROOM EXHAUST OUTLETS MUST BE A MIN.
 OF 10 FEET FROM OUTSIDE AIR INTAKES.
 PER 2004 FBC/M 401.5 .
  
 4) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-07-24 Cont ID  
Sent By jleech Date 2007-07-24 Time 09:07 Rev Time 0.00
Received By jleech Date 2007-07-24 Time 08:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-04-02 Cont ID  
Sent By jleech Date 2007-04-02 Time 07:38 Rev Time 0.00
Received By jleech Date 2007-04-02 Time 07:11 Sent To  
Notes
2007-04-02 07:37:32DENIED;
 1.REVISED DRAWINGS ARE NOT DRAWN BY THE DESIGN
 PROFESSIONALS ON RECORD.
 2.PAGE A3.09 KITCHENETTE ; CABINET TO BE OPEN UNDER THE
 SINK FOR KNEE SPACE SEEFBC-2004 BUILDING SECTION
 11-4.24.3.
 3.SUBMIT SANITARY AND WATER RISER DIAGRAMS.
 4.LIST PLUMBING FIXTURES, SHOW MANUFACTURE OF 2
 COMPARTMENT SINK AND FLOOR SINK.
 5.PAGE P3.01, KEY NOTES; NOTE 1 CALLS FOR HOT WATER, NO
 WATER HEATER SHOWN ON PLANS AND NO ELECTICAL SHOWN ON
 PANEL RISER DIAGRAM.
 NOTE 53" CONDENSATE DRAIN TO RUN DOWN
 STREAM OF THE BATHROOM GROUP, SEE FBC-2004 SECTION
 909.1.NOTE 6, TRAP TO BE 1 1/2" FOR SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By jleech Date 2006-10-23 Time 12:38 Rev Time 0.00
Received By jleech Date 2006-10-23 Time 12:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-09 Cont ID  
Sent By jleech Date 2006-09-09 Time 11:55 Rev Time 0.00
Received By jleech Date 2006-09-09 Time 11:55 Sent To  
Notes
2006-09-09 00:00:00DENIED;
 PAGE A3.09 KITCHETTE VIEW # 2 FORWARD
 APPROACH UNDER SINK IS REQUIRED SEC.
 11-4.3 KNEE CLEARANCE BASE AND CABINET
 DOORS TO BE REMOVED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-10 Cont ID  
Sent By jleech Date 2006-07-10 Time 15:01 Rev Time 0.00
Received By jleech Date 2006-07-10 Time 09:40 Sent To  
Notes
2006-07-10 00:00:00DENIED;
 1.A DRINKING FOUNTAIN IS REQUIRED TO BE
 ADDED TO THE PLUMBING SYSTEM. FBC-2004
 PLUMBING TABLE 403.1.
 2.BATHROOM ON MESSANINE MUST MEET
 HANDICAP REQUIREMENTS. SECTION
 14.1.3(11). EACH COMMON USE TOILET ROOM
 SHALL COMPLY. VANITY WILL NOT ALLOW A
 FRONTAL APPROACH TO LAVITORY.
 3.PAGE 6.01 (DIVISION 15); SECTION
 15440: DELETE PLUMBING FIXTURES THAT
 WILL NOT BE INSTALLED. TWO SINKS ARE
 LISTED, IF SERVICE SINK IS REMOVED IN
 KITCHENETTE AND A KITCHEN SINK IS
 INSTALLED IT MUST MEET HANDICAP
 REQUIREMENTS SEE SEC. 11-4.24.1 THRU
 11-4.24.7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2007-04-02 Cont ID  
Sent By jroach Date 2006-09-08 Time 08:39 Rev Time 0.00
Received By jroach Date 2006-09-08 Time 08:39 Sent To  
Notes
***NONE***