| Plan Review Stops For Permit 06061623 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-20 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-10 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-10 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2007-08-10 17:24:33 | BUILDING PLAN REVIEW | | | PERMIT:06061623 | | | ADD: 5403 N.HAVERHILL RD | | | CONT: MILESTONE CUSTOMS HOMES | | | TEL: (561)436-4733 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW REV. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | *****NO RESPONSE NOT ADDRESSED | | | | | | SUBMIT A LETTER DATED/SIGN/SEALED AND NOTORIZE FROM THE | | | REGISTERED ARCHITECT OR ENGINEER WHO IS TAKING ALL | | | PROFESSIONAL AND LEGAL RESPONSIBILITY AS STATED IN THE | | | FLORIDA ADMINISTRATIVE CODE SECTION BELOW. | | | 2)61G1-18.002PROCEDURES FOR A SUCCESSOR ARCHITECT | | | ADOPTING AS HIS OWN THE WORK OF ANOTHER ARCHITECT. (1) | | | A SUCCESSOR REGISTERED ARCHITECT SEEKING TO REUSE | | | ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR | | | REGISTERED ARCHITECT'S SEAL MUST BE ABLE TO DOCUMENT | | | AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT | | | RECREATED ALL THE WORK DONE BY THE ORIGINAL REGISTERED | | | ARCHITECT. FURTHER, THE SUCCESSOR REGISTERED ARCHITECT | | | MUST TAKE ALL PROFESSIONAL AND LEGAL RESPONSIBILITY FOR | | | THE DOCUMENTS WHICH HE SEALED AND SIGNED AND CAN IN NO | | | WAY EXEMPT HIMSELF FROM SUCH FULL RESPONSIBILITY. PLANS | | | NEED NOT BE REDRAWN BY THE SUCCESSOR REGISTERED | | | ARCHITECT; HOWEVER, JUSTIFICATION FOR SUCH ACTION MUST | | | BE AVAILABLE THROUGH WELL KEPT AND COMPLETE | | | DOCUMENTATION ON THE PART OF THE SUCCESSOR REGISTERED | | | ARCHITECT AS TO HIS HAVING RETHOUGHT AND REWORKED THE | | | ENTIRE DESIGN PROCESS. A SUCCESSOR REGISTERED ARCHITECT | | | MUST USE HIS OWN TITLE BLOCK, SEAL AND SIGNATURE AND | | | MUST REMOVE THE TITLE BLOCK, SEAL AND SIGNATURE OF THE | | | ORIGINAL REGISTERED ARCHITECT BEFORE SEALING, SIGNING | | | AND DATING ANY SEALED CONTRACT DOCUMENTS. | | | (2) PRIOR TO SEALING, SIGNING AND DATING WORK, A | | | SUCCESSOR REGISTERED ARCHITECT SHALL BE REQUIRED TO | | | NOTIFY THE ORIGINAL REGISTERED ARCHITECT, HIS | | | SUCCESSORS, OR ASSIGNS BY CERTIFIED LETTER TO THE LAST | | | KNOWN ADDRESS OF THE ORIGINAL REGISTERED ARCHITECT OF | | | THE SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL | | | REGISTERED ARCHITECT'S WORK. THE SUCCESSOR REGISTERED | | | ARCHITECT WILL TAKE FULL RESPONSIBILITY FOR THE DRAWING | | | AS THOUGH THEY WERE THE SUCCESSOR REGISTERED | | | ARCHITECT'S ORIGINAL PRODUCT. | | | SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED | | | 481.221(4) FS. HISTORY?NEW 1-16-86, AMENDED 5-16-89, | | | FORMERLY 21B-18.002. | | | | | | 3)SUBMIT TWO COMPLETE SETS OF DRAWINGS NOT LOOSE | | | PAGES WITH THE REQUIRED INFORMATION AS STATED ABOVE. | | | SEE F.A.C.61G15-23.002 (2) ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON | | | EACH SHEET.61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) "A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT." | | | | | | 4)RWB LINARES ARCHITECTURE SHALL SUBMIT AN ORIGINAL | | | LEGIBLE SIGN/ SEAL AND NOTORIZE LETTER TAKING FULL | | | RESPONSIBLILTY OF THE PROJECT. ALL SIGNATURES ON THE | | | LETTER SHALL BE ORIGINAL. | | | NEW*************************************************** | | | * | | | | | | A)SHEET A3.09 #3 THE DOORS SHALL BE REMOVED TO | | | PROVIDE THE FORWARD APPROACH. FBC 11-4.21.5 | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-04-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-11 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-11 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2007-04-11 18:04:12 | BUILDING PLAN REVIEW | | | PERMIT:06061623 | | | ADD: 5403 N.HAVERHILL RD | | | CONT: MILESTONE CUSTOMS HOMES | | | TEL: (561)436-4733 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW REV. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)61G1-18.002PROCEDURES FOR A SUCCESSOR ARCHITECT | | | ADOPTING AS HIS OWN THE WORK OF ANOTHER ARCHITECT. (1) | | | A SUCCESSOR REGISTERED ARCHITECT SEEKING TO REUSE | | | ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR | | | REGISTERED ARCHITECT'S SEAL MUST BE ABLE TO DOCUMENT | | | AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT | | | RECREATED ALL THE WORK DONE BY THE ORIGINAL REGISTERED | | | ARCHITECT. FURTHER, THE SUCCESSOR REGISTERED ARCHITECT | | | MUST TAKE ALL PROFESSIONAL AND LEGAL RESPONSIBILITY FOR | | | THE DOCUMENTS WHICH HE SEALED AND SIGNED AND CAN IN NO | | | WAY EXEMPT HIMSELF FROM SUCH FULL RESPONSIBILITY. PLANS | | | NEED NOT BE REDRAWN BY THE SUCCESSOR REGISTERED | | | ARCHITECT; HOWEVER, JUSTIFICATION FOR SUCH ACTION MUST | | | BE AVAILABLE THROUGH WELL KEPT AND COMPLETE | | | DOCUMENTATION ON THE PART OF THE SUCCESSOR REGISTERED | | | ARCHITECT AS TO HIS HAVING RETHOUGHT AND REWORKED THE | | | ENTIRE DESIGN PROCESS. A SUCCESSOR REGISTERED ARCHITECT | | | MUST USE HIS OWN TITLE BLOCK, SEAL AND SIGNATURE AND | | | MUST REMOVE THE TITLE BLOCK, SEAL AND SIGNATURE OF THE | | | ORIGINAL REGISTERED ARCHITECT BEFORE SEALING, SIGNING | | | AND DATING ANY SEALED CONTRACT DOCUMENTS. | | | (2) PRIOR TO SEALING, SIGNING AND DATING WORK, A | | | SUCCESSOR REGISTERED ARCHITECT SHALL BE REQUIRED TO | | | NOTIFY THE ORIGINAL REGISTERED ARCHITECT, HIS | | | SUCCESSORS, OR ASSIGNS BY CERTIFIED LETTER TO THE LAST | | | KNOWN ADDRESS OF THE ORIGINAL REGISTERED ARCHITECT OF | | | THE SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL | | | REGISTERED ARCHITECT'S WORK. THE SUCCESSOR REGISTERED | | | ARCHITECT WILL TAKE FULL RESPONSIBILITY FOR THE DRAWING | | | AS THOUGH THEY WERE THE SUCCESSOR REGISTERED | | | ARCHITECT'S ORIGINAL PRODUCT. | | | SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED | | | 481.221(4) FS. HISTORY?NEW 1-16-86, AMENDED 5-16-89, | | | FORMERLY 21B-18.002. | | | | | | 3)SUBMIT TWO COMPLETE SETS OF DRAWINGS NOT LOOSE | | | PAGES WITH THE REQUIRED INFORMATION AS STATED ABOVE. | | | SEE F.A.C.61G15-23.002 (2) ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON | | | EACH SHEET.61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 4)RWB LINARES ARCHITECTURE SHALL SUBMIT AN ORIGINAL | | | LEGIBLE LETTER TAKING FULL RESPONSIBLILTY OF THE | | | PROJECT. ALL SIGNATURES ON THE LETTER SHALL BE | | | ORIGINAL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-09-26 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-09-26 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2006-09-26 00:00:00 | 1. 713.13(2) F.S.THE NOTICE OF | | | COMMENCEMENT MUST BE RE-RECORDED BECAUSE | | | THE DESCRIBED IMPROVEMENT OR | | | CONSTRUCTION DID NOT COMMENCE WITHIN 90 | | | DAYS OF RECORDING.SHOW DISCRIPTION OF | | | PROJECT ON NOTICE OF COMMENCEMENT. | | | | | | | | | IMPORTANT: | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE AND REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-19 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-19 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2006-07-19 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | SHOW HOW PLANS WILL COMPLY WITH THE | | | SECTION(S) SELECTED.2004 FBC EXISTING | | | BUILDING 301.5 | | | | | | 3.MEZZANINE SHALL BE OPEN AND | | | UNOBSTRUCTED TO THE ROOM IN WHICH SUCH | | | MEZZANINE IS LOCATED EXCEPT FOR WALLS | | | NOT MORE THAN 42 INCHES HIGH, COLUMNS | | | AND POSTS. FBC 505.4 OPENNESS | | | | | | 4.FBC 106.3.5 MINIMUM PLAN REVIEW | | | CRITERIA FOR BUILDINGS. | | | THE EXAMINATION OF THE DOCUMENTS BY THE | | | BUILDING OFFICIAL SHALL INCLUDE THE | | | FOLLOWING MINIMUM CRITERIA AND | | | DOCUMENTS. | | | LIFE SAFTEY PLAN INCLUDING EGRESS, | | | INTERIOR ELEVATIONS, OCCUPANT LOADS, | | | CONSTRUCTION TYPE, ROOM HEIGHT AND IF | | | BUILDING HAS SPRINKLERS. | | | | | | 5.SHOW STAIR DETAILS COMPLYING WITH | | | FBC 1009.3 | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-06-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-27 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-06-27 |
Time |
06:57 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-05-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-01 |
Time |
08:08 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-05-01 |
Time |
07:35 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-09 |
Time |
10:30 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-04-09 |
Time |
07:43 |
Sent To |
PC |
|
| Notes |
| 2007-04-09 10:30:16 | | | | | | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | 1} PLEASE PROVIDE THE PANEL DESIGNATION AND CIRCUIT | | | NUMBERS FOR ALL RECEPTACLES AND LIGHT FIXTURES AFFECTED | | | UNDER THIS PERMIT. 106.3.5.1.2 FBC AS AMENDED. | | | | | | 2} THE RECEPTACLE FOR THE REFRIGERATOR IN THE | | | KITCHENETTE, SHEET E3.01, MUST BE GFI PER 210.8(B)(3), | | | 2002 NEC. | | | | | | 3} PLEASE SHOW COMPLIANCE WITH MEANS OF ILLUMINATION | | | FOR THE STAIRWELLS PER 1006.2FBC AND 7.9 NFPA-101. | | | | | | 4} PLEASE GIVE THE RATING OF THE DISCONNECT FOR THE | | | "NEW A/C UNIT" ON SHEET E3.01, AS WAS DONE FOR THE TWO | | | EXISTING. | | | | | | 5} THE LOADS HAVE BEEN REMOVED FROM THE PANEL SCHEDULES | | | ON SHEET E3.03. PROVIDE THE CALCULATIONS PER 220 NEC | | | AND SHOW CONNECTED LOADS. | | | | | | 5} INDICATE THE LOCATIION AND ADD TO THE PANEL SCHEDULE | | | THE ROOFTOP RECEPTACLE REQUIRED BY 210.63, NEC. | | | AS APPLICABLE. | | | | | | PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE NOT | | | ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE BY | | | THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481, AS | | | APPLICABLE. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-09-19 |
Time |
09:52 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-09-19 |
Time |
09:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-07-14 |
Time |
18:22 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-07-14 |
Time |
18:05 |
Sent To |
|
|
| Notes |
| 2006-07-14 00:00:00 | | | | | | | SHOW COMPLIANCE WITH CHAPTER 13 ENERGY | | | CODE. INDICATE WHICH METHOD USED. SHOW | | | LOCATIONS OF OCCUPANCY SENSORS, TIME | | | CLOCKS ETC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-08-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-20 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-20 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2007-08-20 11:35:05 | *****APPROVED***** | | | | | | | | | STAIRS ARE EXISTING AND THE TENANTS ARE OCCUPYING THE | | | SPACE UNDER A TCO. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2007-08-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-12 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-12 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2007-08-12 12:43:19 | *****DENIED***** | | | | | | | | | THE INFORMATION REQUESTED IN REFERENCE TO THE STAIRS | | | STILL HAS NOT BEEN ADDRESSED.A COPY OF THE (3) | | | PREVIOUS FIRE PLAN REVIEW HAS BEEN INCLUDED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-04-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-04-13 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-04-13 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2007-04-13 12:21:06 | ***DENIED*** | | | | | | 1) THOUGH REQUESTED FROM FIRST FIRE REVIEW, | | | NO ADDITIONAL INFORMATION FOUND | | | REGARDING STAIRS. ALL STAIRS SHALL | | | COMPLY WITH NFPA 101, 2003 EDITION, | | | SECTION 7.2.2.2.19(A). PLEASE PROVIDE | | | NOTE REGARDING PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR HANDRAILS AND GUARDS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-19 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-19 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2006-09-19 00:00:00 | ***PROVISO*** | | | | | | THOUGH REQUESTED FROM FIRST FIRE REVIEW, | | | NO ADDITIONAL INFORMATION FOUND | | | REGARDING STAIRS. ALL STAIRS SHALL | | | COMPLY WITH NFPA 101, 2003 EDITION, | | | SECTION 7.2.2.2.19(A). PLEASE PROVIDE | | | NOTE REGARDING PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR HANDRAILS AND GUARDS. | | | | | | THIS WRITER UNDERSTANDS PRIOR APPROVAL, | | | HOWEVER UPDATED OR NEW PLANS WILL BE | | | REFERENCED DURING INSPECTION, AND SHOULD | | | REFLECT REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-07-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-07-10 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-07-10 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2006-07-10 00:00:00 | 1. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL OF THE | | | EXISTING FIRE SPRINKLER SYSTEM. | | | | | | 2. ALL NEW ACOUSTICAL CEILING TILES TO | | | COMPLY WITH MINIMUM INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 3. PLEASE PROVIDE DETAILS ON MEZZANINE | | | STAIRS. THIS INFORMATION TO INCLUDE RISE | | | AND RUN OF STAIRS, TREAD SIZES AND | | | DETAILS REGARDING HANDRAILS AND | | | GUARDRAILS. PLEASE PROVIDE PRESCRIPTIVE | | | STRENGTH REQUIREMENTS FOR HANDRAILS AND | | | GUARDRAILS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-10 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-10 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2007-08-10 08:39:45 | TO BOB BOARD #12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-03 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-03 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2007-08-03 14:13:18 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-24 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-24 |
Time |
17:01 |
Sent To |
P |
|
| Notes |
| 2007-06-24 17:01:48 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-06-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-22 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-22 |
Time |
14:30 |
Sent To |
E |
|
| Notes |
| 2007-06-22 14:38:14 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-04-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-30 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-30 |
Time |
16:01 |
Sent To |
E |
|
| Notes |
| 2007-04-30 16:03:27 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-03-30 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-03-30 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2007-03-30 18:12:07 | TO BOB # 2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-03-30 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-03-30 |
Time |
17:36 |
Sent To |
E |
|
| Notes |
| 2007-03-30 17:36:30 | TO BILL TROBAUGH |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-23 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-14 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2006-10-14 15:03:08 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2006-09-08 00:00:00 | TO "BOB"#8 | | 2006-09-06 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-19 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-06 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2006-07-06 00:00:00 | TO "BOB"#4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-02 |
Time |
09:04 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2007-04-02 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2007-04-02 09:10:55 | MECHANICAL REVISION | | | *** DENIED *** | | | 1) NEED TO SUBMIT A LETTER FROM THE ENGINEER MARIO H. | | | GUTIERREZ, AND THE ARCHITECT BUSINESS WOLFBERG/ ALVAREZ | | | & PARTNERS, REMOVING THEM SELF'S FROM THE PROJECT. THE | | | LETTER MAY NOT BE A COPY. | | | | | | 2) PLEASE BE ADVISED ALL PAGES TO THE PLANS WILL NEED | | | TO BE REVISED AS THE SET MAY NOT HAVE TWO DIFFERENT | | | ARCHITECTS AND ENGINEERS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-11 |
Time |
15:56 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-09-11 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-06 |
Time |
14:36 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-07-06 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2006-07-06 00:00:00 | *** DENIED *** | | | 1) PAGE M3.01 OFFICE 032A AND 032B, 6" | | | RETURN AIR TRANSFER DUCT NEES TO BE 8", | | | SEE NOTE #4 (A). | | | | | | 2) PAGE M3.02 OFFICE 031G AND 031H, 8" | | | RETURN AIR TRANSFER DUCT NEEDS TO BE 10" | | | SEE NOTE #4 (A). | | | | | | 3) PLEASE ADD NOTE TO PAGE M3.03 . | | | BATHROOM EXHAUST OUTLETS MUST BE A MIN. | | | OF 10 FEET FROM OUTSIDE AIR INTAKES. | | | PER 2004 FBC/M 401.5 . | | | | | | 4) BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-07-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-24 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-24 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-04-02 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-04-02 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2007-04-02 07:37:32 | DENIED; | | | 1.REVISED DRAWINGS ARE NOT DRAWN BY THE DESIGN | | | PROFESSIONALS ON RECORD. | | | 2.PAGE A3.09 KITCHENETTE ; CABINET TO BE OPEN UNDER THE | | | SINK FOR KNEE SPACE SEEFBC-2004 BUILDING SECTION | | | 11-4.24.3. | | | 3.SUBMIT SANITARY AND WATER RISER DIAGRAMS. | | | 4.LIST PLUMBING FIXTURES, SHOW MANUFACTURE OF 2 | | | COMPARTMENT SINK AND FLOOR SINK. | | | 5.PAGE P3.01, KEY NOTES; NOTE 1 CALLS FOR HOT WATER, NO | | | WATER HEATER SHOWN ON PLANS AND NO ELECTICAL SHOWN ON | | | PANEL RISER DIAGRAM. | | | NOTE 53" CONDENSATE DRAIN TO RUN DOWN | | | STREAM OF THE BATHROOM GROUP, SEE FBC-2004 SECTION | | | 909.1.NOTE 6, TRAP TO BE 1 1/2" FOR SINK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-23 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-23 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-09-09 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-09-09 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2006-09-09 00:00:00 | DENIED; | | | PAGE A3.09 KITCHETTE VIEW # 2 FORWARD | | | APPROACH UNDER SINK IS REQUIRED SEC. | | | 11-4.3 KNEE CLEARANCE BASE AND CABINET | | | DOORS TO BE REMOVED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-10 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-10 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2006-07-10 00:00:00 | DENIED; | | | 1.A DRINKING FOUNTAIN IS REQUIRED TO BE | | | ADDED TO THE PLUMBING SYSTEM. FBC-2004 | | | PLUMBING TABLE 403.1. | | | 2.BATHROOM ON MESSANINE MUST MEET | | | HANDICAP REQUIREMENTS. SECTION | | | 14.1.3(11). EACH COMMON USE TOILET ROOM | | | SHALL COMPLY. VANITY WILL NOT ALLOW A | | | FRONTAL APPROACH TO LAVITORY. | | | 3.PAGE 6.01 (DIVISION 15); SECTION | | | 15440: DELETE PLUMBING FIXTURES THAT | | | WILL NOT BE INSTALLED. TWO SINKS ARE | | | LISTED, IF SERVICE SINK IS REMOVED IN | | | KITCHENETTE AND A KITCHEN SINK IS | | | INSTALLED IT MUST MEET HANDICAP | | | REQUIREMENTS SEE SEC. 11-4.24.1 THRU | | | 11-4.24.7. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-09-08 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-09-08 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|