| Plan Review Stops For Permit 06061586 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-01-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-01-02 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-01-02 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2007-01-02 09:51:03 | REVISED PRODUCT APPROVALS ON FILE WITH MASTER PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-12-21 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-12-21 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2006-12-21 09:55:56 | RESTAMP DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVALS SUBMITTED FOR RESTAMP ARE NOT | | | THE SAME AS THE ONES WITH THE APPROVED PERMIT. IN ORDER | | | TO USE THE PRODUCTS SUBMITTED A REVISION FEE WILL BE | | | REQUIRED. | | | | | | 2)THE ROOFING PRODUCT APPROVAL WILL BE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD FOR THE STRUCTURE PER CITY AMENDMENTS TO FBC | | | 106.3.3. | | | | | | 3) IN ADDITION TO THE FL COVER SHEET FOR THE ROOFING | | | THE INSTALLATION INSTRUCTIONS/EVALUATION REPORT IS | | | REQUIRED. | | | | | | NOTE: THE ROOFING PRODUCT APPROVAL WITH THE PERMITWAS | | | APPROVED IN ERROR. THE NEGATIVE DESIGN PRESSURE IN ZONE | | | 3 IS TOO LOW. THE REQUIRED PRESSURE IS -68.1 PSF. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
|