Plan Review Details - Permit 06061539
Plan Review Stops For Permit 06061539
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-01-07 Cont ID  
Sent By rmcdouga Date 2008-01-07 Time 13:46 Rev Time 0.00
Received By rmcdouga Date 2008-01-07 Time 13:46 Sent To  
Notes
2008-01-07 13:48:19SUBMITTED SIGNED AND SEALED FLOOR TRUSS DRAWINGS AND
 TRUSS REPAIR DETAILS FOR TRUSSES FT1 AND FT8.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-12-21 Cont ID  
Sent By rmcdouga Date 2007-12-21 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2007-12-21 Time 06:56 Sent To  
Notes
2007-12-21 07:41:34REVISIONS
  
 1) REVISED PLAN SHEETS S3, S4 AND S5 HAVE BEEN REVIEWED
 FOR CODE COMPLIANCE.
  
 2) ITEM NUMBER 5 OF THE ENGINEER'S LETTER, THE SEALED
 COPY OF TRUSS REPAIR DETAIL, WAS NOT SUBMITTED.
  
 3) THE TRUSS DRAWINGS THAT WERE SUBMITTED ARE DENIED.
 THEY ARE REQUIRED TO BE REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD FOR THE PROJECT. THE DESIGNER OF
 RECORD SHOULD PLACE THEIR SHOP DRAWING STAMP ON THE
 TRUSS LAYOUT TO NOTE THAT IT HAS BEEN REVIEWED. SEE FAC
 61G15-31.003 THE TRUSS LAYOUT FOR THE DRAWINGS WAS NOT
 SUBMITTED. THIS INFORMATION CAN BE GIVEN TO THE FIELD
 INSPECTOR AT THE TRUSS INSPECTION.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-10-30 Cont ID  
Sent By rmcdouga Date 2007-10-30 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2007-10-30 Time 10:48 Sent To  
Notes
2007-10-30 14:06:07REVISED SHEET A-5 REVIEWED FOR CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-08-31 Cont ID  
Sent By rmcdouga Date 2007-08-31 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2007-08-31 Time 16:28 Sent To E
Notes
2007-08-31 16:45:372004 FBC
 REVISION TO CHANGE OVERHEAD GARAGE DOORS FROM 4- 8'
 WIDE DOORS TO 2- 17'-4" DOORS.
  
 DENIED BY BUILDING
  
 1) TWO SETS OF REVISED PLAN SHEETS ARE REQUIRED.
  
 2) SUBMIT PRODUCT APPROVALS FOR THE 17'-4" WIDE
 OVERHEAD GARAGE DOORS. NOTE:
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THE RED-LINED CHANGES THAT WERE MADE TO THE PLANS ON
 SHEET A6 FOR DOOR 101 IN THE DOOR SCHEDULE AND ON THE
 DOOR ELEVATIONS FOR THE TYPE K DOOR (WHICH WAS CHANGED
 FROM A STOREFRONT DOOR)ARE NOT REFLECTED ON THE
 REVISED A6 SHEET.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2007-06-19 Cont ID  
Sent By rmcdouga Date 2007-06-19 Time 11:48 Rev Time 0.00
Received By rmcdouga Date 2007-06-19 Time 11:48 Sent To  
Notes
2007-06-19 13:02:05PLAN RESTAMP FOR 3601 POINSETTIA AVE.
  
 ALL OF THE SUBMITTED PLANS SHEETS WERE RESTAMPED,
 EXCEPT FOR SHEET D1 WHICH WAS MISSING THE TILE BLOCK
 AND WAS NOT SIGNED AND SEALED BY THE DESIGNER OF
 RECORD. THIS SHEET WILL BE REQUIRED TO BE RESUBMITED
 AND A RESTAMP FEE CHARGED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-31 Cont ID  
Sent By rmcdouga Date 2007-05-31 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2007-05-31 Time 12:11 Sent To  
Notes
2007-05-31 14:32:15BUILDING PROVISO
  
 1) SHOP DRAWINGS ARE REQUIRED TO BE SUBMITTED AND
 APPROVED FOR THE ALUMINUM GUARDRAILS BEFORE THEY ARE
 INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-25 Cont ID  
Sent By rmcdouga Date 2007-04-25 Time 14:07 Rev Time 0.00
Received By rmcdouga Date 2007-04-25 Time 07:02 Sent To  
Notes
2007-04-25 14:28:11DENIED BY BUILDING
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT
 FEES.
  
 2) SUBMIT PRODUCT APPROVALS FOR THE LARGE MISSLE IMPACT
 RATED GLASS WALL STOREFRONT SYSTEM AND DOORS SPECIFIED
 ON THE PLANS FOR DOORS 101 AND 102. SEE TYPE K DOORS ON
 SHEET A6 OF THE PLANS. SEE ITEM 12 OF PREVIOUS REVIEW.
  
 3) THE INFORMATION SUBMITTED FOR THE PGT MODEL CD100
 CABANA DOOR IS NOT ACCEPTABLE. SUBMIT STATE OF FLORIDA
 PRODUCT APPROVAL WITH COVERSHEET WITH THE FL# OR A
 CURRENT MIAMI DADE NOA IF THE PRODUCT DOES NOT HAVE A
 STATE APPROVAL. ANOTHER OPTION IS TO HAVE THE
 MANUFACTURER APPLY FOR LOCAL PRODUCT APPROVAL IN
 ACCORDANCE WITH RULE 9B-72.
  
 4) SHOP DRAWINGS WILL BE REQUIRED TO BE SUBMITTED AND
 APPROVED FOR THE ALUMINUM GUARDRAILS BEFORE THEY ARE
 INSTALLED.
  
 5) SPECIFY THE ROOF SHEATHING MATERIAL AND THE FASTENER
 TYPE AND SPACING ON THE PLANS. SEE ITEM #1 FROM
 PREVIOUS REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-02 Cont ID  
Sent By rmcdouga Date 2007-02-02 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2007-02-01 Time 09:36 Sent To  
Notes
2007-02-02 12:58:36DENIED BY BUILDING
  
 1) THE ROOF SHEATHING FASTENING NOTE THAT HAS BEEN
 GLUED TO SHEET S3 IS NOT ACCEPTABLE. THIS INFORMATIONIS
 REQUIRED TO BE ON THE SIGNED AND SEALED DRAWINGS.
  
 2) THE 2' X 2' MASONRY COLUMNS AT THE EXTERIOR ON THE
 BALCONY FRAMING PLAN ON S/3 ARE MIOSLABELED AS C3. SEE
 RED MARKINGS ON THEPLAN.
  
 3)SECTIONS 7/S5 SHOWN ON S3 THROUGH THE NEW BALCONY
 IS IN THE WRONG LOCATION. SEE RED MARK ON PLANS.
  
 4) SECTIONS 7/S5 AND 9/S5 BOTH SHOWN AT THE EAST
 CABANA/OUTSIDE LIVING AREA ON S3 DO NOT CONCUR. ONE HAS
 A PARAPET HEIGHT OF 11' AND THE OTHER HAS 15'-8". SEE
 MARKS ON THE PLAN.
  
 5) THE ELEVATIONS FOR THE CABANA/OUTDOOR LIVING AREA ON
 A3 DO NOT CORRESPOND WITH THE ONES IN THE SECTIONS ON
 S5. PLEASE CORRECT.
  
 6) PROVIDE BUCK DETAILS FOR THE OVERHEAD GARAGE DOORS.
  
 7) PROVIDE WALL SECTIONS OF THENON-LOAD INTERIOR
 BEARING PARTIONS. SPECIFY THE FRAMING MATERIAL,
 SPACING, FINISHES, ETC.
  
 8) PROVIDE EXTERIOR WALL SECTIONS, SPECIFYING THE
 FURRING, INSULATION, INTERIOR AND EXTERIOR COVERINGS,
 ETC.
  
 9) SPECIFY THE FINISH/COVERING OF THE CABANA/OUTDOOR
 LIVING AREA CEILING.
  
 10)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 11)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. BOTH COPIES OF PRODUCT
 APPROVALS TO BE SIGNED.
  
 12) SUBMIT PRODUCT APPROVALS FOR LARGE MISSILE IMPACT
 RATED GLASS WALL STOREFRONTS AND STOREFRONT DOORS.
  
 13)SUBMIT CURRENT PRODUCT APPROVALS FOR THE ALUMINUM
 RAILING SYSTEM. THE ONE THAT WAS SUBMITTED IS EXPIRED.
  
 14) SUBMIT CURRENT PRODUCT APPROVALS FOR THE PGT LARGE
 MISSILE IMPACT RATED OUTSWING ALUMINUM FRENCH DOOR. THE
 ONE THAT WAS SUBMITTED IS EXPIRED.
  
 15)THE DRAWINGS ON SHEETS 1-13 OF THE PRODUCT
 APPROVAL FOR THE PGT LARGE MISSILE IMPACT RATED
 CASEMENT WINDOWS ARE MISSING THE TOP OF THE PAGES.
 PLEASE REPLACE THESE WITH COMPLETE PAGES.
  
 16) ON THE PRODUCT APPROVAL FOR THE ROOF COVERING
 SPECIFY THE SYSTEM THAT WILL BE INSTALLED. UNDER THE
 SYSTEM CIRCLE THE FASTENING OPTION AND DESIGN PRESSURE.
 IF THE DESIGN PRESSURE IS LESS THAN REQUIRED IN THE
 PERIMETER AND CORNER ZONES AND THE LIMITATIONS ALLOW
 ENHANCED FASTENING PROVIDE RAS 117 CALCULATIONS. IF
 LIMITATION #7 REQUIRES THESE CALCULATIONS FROM AN
 ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT,
 SUBMIT THE SIGNED AND SEALED CALCULATIONS.
  
 17) SUBMIT THE LISTING INFORMATION (UL OR OTHER
 APPROVED AGENCY) AND MANUFACTURER'S SPECIFICATIONS FOR
 THE PREFAB VENTLESS INTERIOR FIREPLACES LOCATED ON THE
 1ST AND 2ND FLOORS OF THE RESIDENCE.
  
 18) SUBMIT THE LISTING INFORMATION FOR THE OUTDOOR GAS
 FIREPLACE.
  
 19) SUBMIT THE LISTING INFORMATION FOR THE BUILT-IN
 BBQ. PROVIDE DOCUMENTATION THAT ALLOWS IT TO BE
 INSTALLED ON A COVERED PORCH.
  
 20) SUBMIT THE LISTING INFORMATION FOR THE WALL HOOD.
 PROVIDE DOCUMENTATION THAT ALLOWS IT TO BE INSTALLED ON
 A COVERED PORCH.
  
 21) SUBMIT SIGNED AND SEALED TRUSS DRAWING AND LAYOUT,
 WHICH HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD FOR THE STRUCTURE PRIOR TO INSTALLATION. SEE
 2004 FBC RESIDENTIAL R 802.1.6.1.
  
 22)PLEASE REMOVE THE EXPIRED PRODUCT APPROVALS AND
 ONES THAT ARE NOT BEING USED FROM THE SUBMITTAL
 PACKAGE.
  
 23)PLEASE REMOVE THE OLD SHEETS FROM THE PLANS AND
 INSERT THE NEW REVISED SHEETS INTO THE PLANS, SO THAT
 TWO COMPLETE SETS OF PLANS ARE CREATED. THE SHEETS WITH
 THE IMPACT FEE STAMP ON THEM SHOULD BE LEFT IN THE
 PLANS. ONE SET OF THE OLD SHEETS CAN BE RESUBMITTED
 ALONG WITH THE TWO NEW SETS OF PLANS FOR REFERENCE
 PURPOSES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By amorse Date 2006-07-24 Time 13:06 Rev Time 0.00
Received By amorse Date 2006-07-24 Time 13:06 Sent To PC
Notes
2006-07-24 00:00:00 
  
 DERNIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. DUE TO THE CHANGE OF
 OCCUPANCY AND OWNER IMPACT FEES MAY BE
 REQUIRED
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) GARAGE IS ON LOT #3 AND HAS A
 SEPERATE PCN# PLEASE PROVIDE UNITY OF
 TITLE (SEE ZONING COMMENTS)
  
 4) HISTORIC REVIEW AND STAMP IS REQUIRED
 PRIOR TO BUILDING APPROVAL
  
 5) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 6) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC. LICENCE NUMBER IS
 MISSING FROM ALL BUT STRUCTURAL PAGES
  
 7) PLEASE SEE RED LINED REMARKS TO COVER
 PAGE, NO WHITE OUT, WRONG FLOOD ZONE,
 ETC.
  
 8) PROVIDE THE ROOF SHEATHING SIZE AND
 SPECIAL NAILING ZONES THAT COMPLY WITH
 TABLE 2304.9.1 FBC
  
 9) SHOW COMPLIANCE WITH THE PROVISIONS
 OF 717.2.7 FBC FOR CONCEALED SLEEPER
 SPACES
  
 10) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ************NOTE*************
 THE FOLLOWING PRODUCT APPROVALS ARE
 REQUIRED FRENCH DOORS W/WO SIDELITES,
 CASEMENT WINDOWS, FIXED TRANSOM WINDOWS,
 AND MULLIONS IF WINDOWS ARE NOT SINGLE
 UNITS.
 ALSO WINDOW WALL PANELS(STOREFRONTS) ARE
 ONLY SMALL IMPACT RATED AND WOULD
 REQUIRE IMPACT PROTECTION (SEE 1609.1.4
 FBC) LOWER 30 FEET SHALL BE LARGE MISSLE
 RATED.
 ROOFING SYSTEM CHOSEN DOES NOT MEET THE
 REQUIRED DESIGN PRESSURES AND ENHANCED
 FASTENING CANNOT BE USED (SEE LIMITATION
 #9
 WHERE POSSIBLE THE CITY OF WEST PALM
 REQUIRES THE STATE OF FLORIDA PRODUCT
 APPROVAL SHEETS
  
 11) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 12) PROVIDE WINDOW SIZES TO ASCERTAIN
 THAT DESIGN PRESSURES FROM PRODUCT
 APPROVALS ARE MET. ALSO FOR THE GLASS
 BLOCK BE SURE TO KEEP SIZE WITHIN THE
 MAXIMUM WIDTH AND HEIGHT.
  
 13) DRAWING SHOWS FIREPLACE UNDER ROOFED
 PATIO AT GARAGE BUT NO CHIMNEY IS SHOWN
 PLEASE CLARIFY, ALSO SUPPLY
 MANUFACTURERS SPECIFICATIONS
  
 14) COLUMNS C2 ON S/3, IS THIS THE
 TYPICAL MASONARY DETAIL P2 ON DETAIL 10
 S/4 PLEASE CLARIFY
  
 15) PLEASE CLARIFY ELEVATIONS BETWEEN
 ARCHITECTURAL AND STRUCTURAL SEE A/3
 PATIO OPENINGS ARE 11'-4" HIGH AND THE
 ROOF HEIGHT ON SECTION 8 & 9 IS 9'-4" ON
 S/5, ALSO SECTION 7 HAS NO HEIGHT STATED
 BUT THE PARAPET HEIGHT IS THE SAME AS
 THE MAIN GARAGE PARAPET AND DIFFERS FROM
 THE PARAPET HEIGHT ON SECTION 9.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-10-29 Cont ID  
Sent By btrobaug Date 2007-10-29 Time 08:01 Rev Time 0.00
Received By btrobaug Date 2007-10-29 Time 07:24 Sent To M
Notes
2007-10-29 07:59:22 
  
  
 PROVISO
  
 THE RISER DIAGRAM HAS BEEN REDLINED TO CORRECT
 GROUNDING AND LINE AND LOAD IN THE SAME CONDUIT ISSUES.
 SEE 230.7, 250.66, 250.122, AND 225.32, 2005 NEC.
 CORRECT THE RISER PRIOR TO CALLING THE SERVICE
 INSPECTION, AND SUBMIT FOR REVIEW. SEE THAT THE
 DESIGNER OF RECORD GETS THE REDLINED COPY SO HE CAN
 READ THOSE ARTICLES CONCERNED AND MAKE THE CORRECTIONS
 NECESSARY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-09-07 Cont ID  
Sent By btrobaug Date 2007-09-07 Time 15:12 Rev Time 0.00
Received By btrobaug Date 2007-09-07 Time 15:10 Sent To PC
Notes
2007-09-07 15:12:05 
  
 ELECTRICAL REVISION, SHEET E1, FLOOR BOXES ADDED./WRT.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-09-04 Cont ID  
Sent By btrobaug Date 2007-09-04 Time 10:07 Rev Time 0.00
Received By btrobaug Date 2007-09-04 Time 07:57 Sent To PC
Notes
2007-09-04 10:06:58 
  
  
  
 DENIED
 THESE COMMENTS WERE APROVISO ON THE PREVIOUS REVIEW
 AND HAVE NOT BEEN CORRECTED AS REQUIRED.
  
 THE SERVICE RISER HAS CHANGED SINCE THE PREVIOUS
 REVIEW. MAKE THE FOLLOWING CHANGES FOR CODE COMPLIANCE
 AND RESUBMIT FOR REVIEW PRIOR TO CALLING AN INSPECTION
 ON THE SERVICE.
  
 1} ON SHEET E-1 THERE IS A "MAIN DISCONNECT" SHOWN AT
 THE SERVICE, THE RISER THERE IS SHOWN SEPERATE
 DISCONNECTS FOR "A" "B" AND "C". CORRELATE SAME.
 DISCONNECT "C" IS ON THE GARAGE, NOT AT THE HOUSE.
  
 2} THE GROUNDING ELECTRODE NEEDS TO BE AT THE METER OR
 GUTTER, NOT AT THE PANELS. SEE REDLINED PLAN.
  
 3}THE GROUNDING CONDUCTOR MUST BE A MINIMUM #2 CU PER
 250.66. INDICATE SAME ON PLANS.
  
 4} LOCATE THE DISCONNECTS AHEAD OF THE PANELS ON THE
 RISER, NOT IN PARALLEL WITH THEM. SEE REDLINE. INDICATE
 AMPERAGE ON THE DISCONNECTS.
  
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW AT
 LEAST ONE WEEK (PER TRADE) FOR PLAN
 REVIEW.
  
 THESE ARE COMMENTS FROM THE REVIEW DONE ON 9/4/07
  
 1} THIS WAS SUBMITTED AS A RESTAMP AS IN FACT A
 REVISION. TWO SETS OF PLANS ARE REQUIRED FOR A REVISION
 PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-04 Cont ID  
Sent By btrobaug Date 2007-05-04 Time 15:43 Rev Time 1.50
Received By btrobaug Date 2007-05-04 Time 14:46 Sent To B
Notes
2007-05-04 15:43:36 
  
 PROVISO
 THE SERVICE RISER HAS CHANGED SINCE THE PREVIOUS
 REVIEW. MAKE THE FOLLOWING CHANGES FOR CODE COMPLIANCE
 AND RESUBMIT FOR REVIEW PRIOR TO CALLING AN INSPECTION
 ON THE SERVICE.
  
 1} ON SHEET E-1 THERE IS A "MAIN DISCONNECT" SHOWN AT
 THE SERVICE, THE RISER THERE IS SHOWN SEPERATE
 DISCONNECTS FOR "A" "B" AND "C". CORRELATE SAME.
 DISCONNECT "C" IS ON THE GARAGE, NOT AT THE HOUSE.
  
 2} THE GROUNDING ELECTRODE NEEDS TO BE AT THE METER OR
 GUTTER, NOT AT THE PANELS. SEE REDLINED PLAN.
  
 3}THE GROUNDING CONDUCTOR MUST BE A MINIMUM #2 CU PER
 250.66. INDICATE SAME ON PLANS.
  
 4} LOCATE THE DISCONNECTS AHEAD OF THE PANELS ON THE
 RISER, NOT IN PARALLEL WITH THEM. SEE REDLINE. INDICATE
 AMPERAGE ON THE DISCONNECTS.
  
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW AT
 LEAST ONE WEEK (PER TRADE) FOR PLAN
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-11 Cont ID  
Sent By btrobaug Date 2007-04-11 Time 11:39 Rev Time 2.00
Received By btrobaug Date 2007-04-11 Time 07:56 Sent To P
Notes
2007-04-11 09:31:03NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE DISCONNECTING MEANS FOR PANEL"C" IN THE GARAGE
 MUST BE LOCATED ON THE GARAGE, NOT ON THE HOUSE. SEE
 225.32 FOR CLARITY.
  
 2} IT IS ASSUMED THAT THE GARAGE FEED ORIGINATES FROM
 THE 200 AMP MAIN DISCONNECT, WHICH IS APPARANTLY DOUBLE
 LUGGED. BUT CIRCUIT #37 IN PANEL "B" LISTS' PNL "C"
 GARAGE" FED WITH A # 12 CONDUCTOR FROM A 20 AMP
 BREAKER. PLEASE CORRELATE.
  
 3} A/C #1 IS IS BEING FED FROM PANEL "B" IN THE
 SCHEDULE, AND PANEL "A" ON THE RISER DIAGRAM.
  
 4} THE LOAD CALCULATIONS LISTS 3-10,000 WATT HEAT
 STRIPS. THERE ARE ONLY 2 AHU'S IN THE PANEL SCEDULES @
 10K, AND ONLY TWO LISTED ON THE MECHANICAL SHEET,
 M-1.PLEASE CORRELATE, CORRECT CALCULATION.
  
 5} THERE ARE 5 SMALL APPLIANCE CIRCUITS LISTED ON
 SCHEDULE"A", AND 1 IN SCHEDULE "C", BUT ONLY 4 IN THE
 CALCULATIONS .PLEASE NOTE PER 210.52(B), THERE IS NO
 REQUIREMENT FOR A SMALL APPLIANCE CIRCUIT IN PANEL "C",
 UNLESS THE GARAGE HAD A SEPARATE KITCHEN.
  
 6} SHEET "E-1" SHOWS A 100 GALLON GAS WATER HEATER. THE
 LOAD CALCULATIONS LIST AN 80 GALLON WATER HEATER @ 5500
 WATTS. PANEL "A" CIRCUIT 30 LISTS A WATER HEATER FED
 FROM A 50 AMP BREAKER ON #12 WIRE, WHICH VIOLATES
 310.16, 240.4(D) AND 422.11(E)(3). THE HEATER IS ALSO
 LISTED AS ELECTRIC IN THE EMNERGY CALCULATIONS, SHEET
 SP.
  
 7} THE DRYER IN SCHEDULE "A" IS FED WITH #12 WIRE ON A
 50 AMP BREAKER THE DRYER IS RATED AT 5000 WATTS (PER
 220.18) IN THE CALCULATION. 5000/240=20.8 AMPS, 25AMP
 BREAKER PER 240.4.
  
 8} THE COOKTOP IN THE CALCULATION IS SHOWN AT 5000
 WATTS ON A 20 AMP BREAKER, AND ON A 50 AMP BREAKER ON
 #12 WIRE IN SCHEDULE "A". SEE 310.16.
  
 9} OVENS 1&2 HAVE #12 WIRE ON A 50 AMP BREAKER,
 310.16.
  
 10} THE AIR HANDLERS IN SCHEDULE "B" HAVE #8 CONDUCTORS
 ON A 60 AMP BREAKER. 310.16.
 10000/240=41.66X125%(424.3(B) NEC)=52 AMPS. #6
 CONDUCTORS, 310.16.
  
 11} THE CALCULATION INDICATES A "MISC" LOAD OF 6000
 WATTS ON A 2 POLE 50 AMP BREAKER, PLEASE LIST THE
 SPECIFIC LOAD PER 220 SECTION I OR SECTION III.
  
 12} THE DISCONNECTS FOR PANELS "A" & "B" SHOWN ON SHEET
 E-1, ARE NOT LOCATED ON THE RISER.
  
 THE LOAD AS IT IS CALCULATED ON THIS PLAN, EXCEEDS THE
 200 AMP SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-19 Cont ID  
Sent By btrobaug Date 2006-12-19 Time 17:15 Rev Time 1.00
Received By btrobaug Date 2006-12-19 Time 15:33 Sent To M
Notes
2006-12-19 16:48:27NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} PER THE RISER DIAGRAM AND FLOOR PLAN, THE PANELS "A"
 & B" IN THE RESIDENCE, THE DISCONNECTING MEANS DO NOT
 COMPLY WITH 230.70(A)(1) READILY ACCESSIBLE LOCATION.
 THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS.DISCONNECTS MUST BE
 OUTSIDE AT THE SERVICE LOCATION.
  
 3} THERE IS NO FEEDER LISTED IN THE
 SCHEDULE, FROM PANEL "A" TO THE GARAGE
 PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By btrobaug Date 2006-07-12 Time 16:47 Rev Time 1.00
Received By btrobaug Date 2006-07-12 Time 12:51 Sent To P
Notes
2006-07-12 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} REGARDING THE GARAGE,225.31
 DISCONNECTING MEANS.
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING
 OR STRUCTURE.THE DISCONNECTING MEANS
 SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE
 OF THE CONDUCTORS.
  
 3} REGARDING THE PANEL LOCATION IN THE
 RESIDENCE, THEY TOO WOULD REQUIRE A
 DISCONNECT OUTSIDE OR IMMEDIATELY INSIDE
 AT THE POINT OF ENTRANCE, SEE 230.6 FOR CLARIFICATION
 ON THIS. ALSO IF THE
 DISCONNECT IS OUTSIDE AND THERE IS A
 GENERATOR ADDED LATER ALL THAT RELATED
 EQUIPMENT COULD BE GROUPED AND THERE
 FORE COMPLIANT.
  
 4} PANEL "C" IS SHOWN IN THE GARAGE. THE
 RISER INDICATES ONLY A "FUTURE POOL"
 PANEL. THE GARAGE CIRCUITS ARE NOT ON
 ANY SCHEDULE. PLEASE CORRECT THIS , ALSO
 CORRECTLY DESIGNATE THE PANEL IN
 QUESTION ON THE PLAN AND ON THE RISER.
  
 5} THERE IS NO FEEDER LISTED IN THE
 SCHEDULE, FROM PANEL "A" TO THE GARAGE
 PANEL.
  
 5} THE REQUIRED BATH CIRCUITS ARE NOT ON
 THE PANEL SCXHEDULE. PLEASE ADD SAME. 210.11(C)(3).
  
 6} THE BEDROOM AFCI CIRCUITS REQUIRED
 PER 210.12, DO NOT APPEAR ON THE PANEL
 SCHEDULES.
  
 7} A SMOKE DETECTORS MUST BE INSTALLED
 TO COMPLY WITH R313.1 3 RESIDENTIAL
 FLORIDA BUILDING CODE, AT THE STAIR ON
 THE FIRST FLOOR.
  
 8} RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A) (1) AND 210.52 (A)(2), SEE
 REVIEWED PLAN FOR LOCATIONS THAT DO NOT
 COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-01-07 Cont ID  
Sent By adarroug Date 2008-01-07 Time 09:58 Rev Time 0.00
Received By adarroug Date 2008-01-07 Time 09:58 Sent To B
Notes
2008-01-07 09:58:32TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 17:14 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 17:14 Sent To B
Notes
2007-12-19 17:14:23TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 08:27 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 08:27 Sent To E
Notes
2007-10-26 08:28:10TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 12:14 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 12:14 Sent To E
Notes
2007-08-30 12:14:55TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 12:12 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 12:12 Sent To B
Notes
2007-08-30 12:12:55TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 10:06 Sent To B
Notes
2007-06-07 10:06:46TO "RMCDOUGAL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 13:48 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 13:48 Sent To E
Notes
2007-05-03 13:49:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 11:58 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 11:58 Sent To E
Notes
2007-04-10 11:58:33TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-04 Cont ID  
Sent By spalmer Date 2007-04-04 Time 17:59 Rev Time 0.00
Received By spalmer Date 2007-04-04 Time 17:59 Sent To Z
Notes
2007-04-04 17:59:35TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 13:15 Sent To E
Notes
2006-12-18 13:15:20TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-07 Cont ID  
Sent By adarroug Date 2006-12-07 Time 15:00 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 15:00 Sent To Z
Notes
2006-12-07 15:01:03TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-08 Cont ID  
Sent By adarroug Date 2006-07-08 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-07-08 Time 15:57 Sent To E
Notes
2006-07-08 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-24 Time   Rev Time 0.00
Received By adarroug Date 2006-06-28 Time 11:44 Sent To  
Notes
2006-06-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-29 Cont ID  
Sent By tgordon Date 2007-10-29 Time 10:52 Rev Time 0.40
Received By tgordon Date 2007-10-29 Time 10:52 Sent To B
Notes
2007-10-29 11:13:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) PROVIDE FOR RETURN AIR TO THE MEDIA ROOM, SEE FBC/R
 M1602.4.
  
 2) RETURN AIR GRILL IN THE RECREATION ROOM NEEDS TO BE
 SIZED (SEE YELLOW HIGH LIGHT ON MECH. PLAN).
  
 3) SUPPLY AIR DUCT FROM AIR HANDLER TO MIXING BOX ABOVE
 MASTER BATHROOM NEEDS TO BE SIZED (SEE YELLOW HIGH
 LIGHT ON MECH. PLAN).
  
 4) RETURN AIR DUCT FROM AIR HANDLER TO BEDROOM #3 NEEDS
 TO BE SIZED (SEE YELLOW HIGH LIGHT ON MECH. PLAN).
  
 5) RETURN AIR DUCT FROM AIR HANDLER TO MASTER BEDROOM
 NEEDS TO BE SIZED (SEE YELLOW HIGH LIGHT ON MECH.
 PLAN).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-21 Cont ID  
Sent By tgordon Date 2006-12-21 Time 08:21 Rev Time 0.35
Received By tgordon Date 2006-12-21 Time 08:21 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By tgordon Date 2006-07-17 Time 08:49 Rev Time 0.45
Received By tgordon Date 2006-07-17 Time 08:49 Sent To B
Notes
2006-07-17 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 TWO 13 SEER A/C SYSTEMS, AND THE MECH.
 PLANS ARE CALLING FOR TWO 12.25 SEER A/C
 SYSTEMS, THE TWO MUST COINCIDE PLEASE
 CORRECT.
  
 2) MANUAL J CAL'S.SYSTEM 2 ARE CALLING
 FOR 29,301 SENSIBLE BTU'S, MECH. PLANS
 SYSTEM 2 ARE CALLING FOR 43,800 SENSIBLE
 BTU'S, THE MECH. PLANS CAN ONLY CALL FOR
 20% MORE THAN THE MANUAL J CAL'S., PER
 2004 FBC 13-607.1.ABC.1.1 . PLEASE
 CORRECT.
  
 3) RETURN AIR DUCT TO MASTER SUITE NEED
 TO BE 14" PER 2004 FBC/R M1602.4 .
  
 4) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR NEW GAS FIREPLACES.
  
 5) PLEASE PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER, AND GAS WATER HEATER, PER
 2005 FBC/R M1701.1 .
  
 6) PLEASE SHOW LOCATION OF CLOTHES DRYER
 VENT ,AND BATYROON EXHAUST FANS ON MECH.
 PLANS.
  
 7) OPEN GAS GRILL IN COVERED OUTDOOR
 LIVING SPACE WILL NEED AN APPROVED
 EXHAUST HOOD, PER 2004 FBC/M 505.3 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-19 Cont ID  
Sent By mperson Date 2007-04-19 Time 08:18 Rev Time 0.45
Received By mperson Date 2007-04-19 Time 08:18 Sent To B
Notes
2007-04-19 08:31:51****************PROVISO****************
 A} BEDROOM #3 BATH TUB SHOULD BE A SHOWER PER SHEET
 A-2 FLOOR PLAN.
 B} PER FBC-2004 PLUMBING, SECTION 708.3.5 A TWO-WAY
 CLEANOUT IS REQUIRED AT THE JUNCTION OF THE BUILDING
 DRAIN AND BUILDING SEWER.
 C} PER FBC-2004 PLUMBING, SECTION 802.1.6 DOMESTIC
 DISHWASHING MACHINES SHALL DISCHARGE INTO A WYE-BRANCH
 FITTING ON THE TAILPIECE OF THE KITCHEN SINK OR THE
 DISHWASHER CONNECTION OF A FOOD WASTE GRINDER.
 D} PER FBC-2004 PLUMBING, SECTION 802.4 THE WASHING
 MACHINE STANDPIPE SHALL EXTEND A MINIMUM OF 18 INCHES
 AND A MAXIMUM OF 42 INCHES ABOVE THE TRAP WEIR.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-04 Cont ID  
Sent By mperson Date 2007-01-04 Time 16:42 Rev Time 0.45
Received By mperson Date 2007-01-03 Time 16:42 Sent To B
Notes
2007-01-03 17:00:42DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE PER THE
 PREVIOUS PLUMBING PLAN REVIEW:
  
 1. SHEET P-1 ICE MAKER, DRAIN REQUIRED PER FBC-2004
 PLUMBING, SECTION 802.1.3, AND THE SUBMITTED
 MANUFACTURER SHEETS. THE RESUBMITTED DRAWINGS INDICATE
 THE ICE MAKER IN THE CABANA BEING DELETED, IS THIS THE
 INTENT OR IS A DRAIN NEED TO BE PROVIDED FOR THAT ICE
 MAKER AS WELL. PLEASE CLARIFY AND PLEASE ADD DRAINS
 WHERE NEEDED ON THE RESUBMITTAL.
  
 2. SHEET P-1 SANITARY RISER DIAGRAM, THE FIRST FLOOR
 LAV IN THE MEDIA ROOM BATH IS STILL WRONG. THE SECOND
 FLOOR BATHROOM RISERS CAN'T DISCHARGE INTO THAT LAVS
 VENT PER FBC-2004 PLUMBING, SEC. 909.1 AND 909.1.1.
 PLEASE CORREC ON THE RESUBMITTAL.
  
 3.(OK)
  
 4. (OK)
  
 THE FOLLOWING ARE NEW COMMENTS THAT NEED TO BE
 ADDRESSED DUE TO THE RESUBMITTAL OF NEW P-1 SHEET:
  
 5. PLEASE DELETE THE S.V. ON THE KITCHEN SINK ON THE
 RESUBMITTAL DUE TO THE FACT THAT THE SINK IS INDICATING
 A 3" V.T.R.
  
 6. SHEET P-1, PLUMBING NOTES: #19. PLEASE DELETE SFBC
 SECT. 4613 THAT CODE IS NO LONGER IN USE AS OF 2001.
 PLEASE ADD THE FOLLOWING, FBC-2004 TABLE 604.3 WATER
 DISTRIBUTION DESIGN CRITERIA REQUIRED CAPACITY AT
 FIXTURE SUPPLY OUTLETS.
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By jleech Date 2006-07-17 Time 07:22 Rev Time 0.00
Received By jleech Date 2006-07-17 Time 07:22 Sent To M
Notes
2006-07-17 00:00:00DENIED;
 1.ICE MACHINES IN BAR AND CABANA AREA;
 HOW WILL THEY DRAIN? SENT IN SPEC. SHEET
 FOR ICE MACHINES.
 2.THE SECOND FLOOR BATHROOM RISERS CAN
 NOT DICHARGE INTO THE VENT OF THE
 KITCHEN AND THE LAVATORY ON THE FIRST.
 3.THE VEGETABLE SINK IS NOT SHOWN ON
 RISER DIAGRAM.
 4.THE BRANCH DRAIN FOR THE AUTOMATIC
 CLOTHES WASHER IS 3" SEE FBC-2004
 PLUMBING SECTION 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-04-05 Cont ID  
Sent By jroach Date 2007-04-05 Time 17:00 Rev Time 0.00
Received By jroach Date 2007-04-05 Time 17:00 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-16 Cont ID  
Sent By mmclean Date 2006-12-16 Time 07:43 Rev Time 0.00
Received By mmclean Date 2006-12-16 Time 07:43 Sent To I
Notes
2006-12-16 08:07:02DENIED.
 1. THE SITEPLANS SUBMITTED DOES NOT PROVIDE THE FRONT
 SETBACK AND SIDE SETBACK (WEST) FROM PROPERTY LINE.
 SETBACKS ARE NOT SHOWN ON REVISED SITEPLAN.
 2. SITEPLAN MUST PROVIDE THE DISTANCE OF THE MAIN
 STRUCTURE FROM GARAGE. DISTANCE NOT SHOWN ON REVISED
 SITEPLAN.
 3. ELEVATIONS FOR THE EAST AND WEST OF THE MAIN
 STRUCTURE IS NOT INCLUDED IN PACKAGE. PLEASE PROVIDE
 ELEVATIONS TWO SETS.
 4. THE HEIGHT OF THE MAIN STRUCTURE IS EXEEDS THE
 HEIGHT REQUIREMENTS.
 SEC94-306 HEIGHT EXCEPTIONS - EXEMPTIONS OF HEIGHT
 LIMITS CHIMNEYS MAY EXCEED DISTRICT HEIGHT REQUIREMENT
 BY TEN PERCENT. SF14 MAXIMUM BUILDING HEIGHT SHALL BE
 30FT. MAXIMUM HEIGTH ALLOWED IS 33FT. HEIGHT SHOWS AT
 34+FT.
 5. ELEVATION FOR THE GARAGE IS NOT INCLUDED IN PACKAGE,
 PLEASE PROVIDE THE ELEVATIONS PLANS FOR THE GARAGE.
 6. SEC 94-304 - ACCESSORY STRUCTURE MAXIMUM SQUARE
 FOOTAGE TOTAL FLOOR AREA OF ALL ROOFED ACCESSORY
 BUILDING ON A PROPERTY SHALL NOT EXCEED 75% OF THE
 GROSS FLOOR AREA OF THE PRIMARY STRUCTURE WITH A
 MAXIMUM FLOOR AREA OF 1000SQ FT.
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF LANDSCAPE
 WITHIN THE FIRST 25FT FRONT SETBACK.
 NOTE: SEPARATE PERMIT FOR
 FENCE/GATE/WALLS/POOLS/SPA/DECK. FENCE MUST INCLUSED
 EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH
 UTITILITY DEPT. AND WALL DETAILS FOR WALLS.
 NOTE: SEPARATE PERMIT FOR GENERATOR.
 NOTE: SHALL NOT OBSCURED THE 20FT VISIBILITY TRIANGLE
 CORNER OF 35TH STREET & POINSETTIA AVE (NORTH DIXIE
 HIGHWAY).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-06 Cont ID  
Sent By mmclean Date 2006-07-06 Time 10:53 Rev Time 0.00
Received By mmclean Date 2006-07-06 Time 10:53 Sent To I
Notes
2006-07-06 00:00:00DENIED,
 1. MUST PROVIDE A COPY OF THE UNITY
 TITLE FOR PROPERTIES LOT 5 BLOCK 5, LOT
 4 BLOCK 5 AND LOT 3 BLOCK 5
 2. MUST PROVIDE TWO COPY OF SURVEY
 MERGING ALL PROPERTIES (ONE PROPERTY
 CONTROL NUMBER).
 3. SITEPLAN MUST SHOW THE FRONT
 SETBACK OF PROPOSED STRUCTURE AND SIDE
 SETBACK (WEST SIDE).
 4. PLEASE PROVIDE THE DIMENSION OF THE
 PROPOSED MOTOR COURT (LENGTH & WIDTH)
 AND STATE THE TYPE OF MATERIAL
 (CONCRETE, ASPHALT, PAVERS).
 5. MUST PULL A SEPERATE PERMIT FOR
 FENCE/GATE WITH EASMENT APPROVAL FROM
 THE CITY OF WEST PALM BEACH UTILITY
 DEPT.
 6. MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK.
 7. THE STRUCTURE IS OVER THE HEIGHT
 REQUIREMENT. (30FT PLUS 10% FOR CHIMNEY)
 TOTAL 33FT.
 8. HISTORIC IS TO REVIEW BEFORE PERMIT
 APPLICATION IS RELEASED FOR ANY
 CORRECTONS.
 9. MUST SHOW ACCESS TO THE ADDITIONAL
 PARKING FROM THE ALLEY (PLANS DOES NOT
 SHOW ANY ALLEY ACCESS).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved