Plan Review Details - Permit 06061518
Plan Review Stops For Permit 06061518
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By lursu Date 2006-06-29 Time 09:26 Rev Time 0.00
Received By lursu Date 2006-06-29 Time 09:26 Sent To  
Notes
2006-06-29 00:00:00NEW ADDRESS ASIGNED TO THE VACANT LOT TO
 BUILD A NEW SINGLE RESIDENTIAL HOUSE:
 608 54TH ST .

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-14 Cont ID  
Sent By jgomez Date 2006-09-14 Time 15:00 Rev Time 0.00
Received By jgomez Date 2006-09-14 Time 12:12 Sent To  
Notes
2006-09-14 00:00:00BUILDING REVIEW PROVISO:
 1- SURVEY IS SHOWING LOCATION OF
 PROPOSED SEPTIC TANK. SEPTIC TANK IS NOT
 ALLOWED. REVISE SURVEY AS REQUIRED.
  
 2- PROVIDE COMPLETE AND CORRECT
 INFORMATION FOR STORM SHUTTERS UNDER A
 SEPARATE PERMIT AS AGREED ON WITH
 CONTRACTOR.
  
 3- DADE COUNTY NOA 06-0125.08 IS FOR 2"X
 HEAVY WALL ALUMINUM MULLION.NEED TO
 PROVIDE DADE COUNTY NOA FOR 1" ALUMINUM
 MULLION. MAKE SURE IS NOT EXPIRED AND
 DESIGNER OF RECORD TO REVIEW/APPROVE IT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-06 Cont ID  
Sent By jgomez Date 2006-07-06 Time 16:34 Rev Time 2.00
Received By jgomez Date 2006-07-06 Time 16:30 Sent To  
Notes
2006-07-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE SPECS/SECTION/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 2- PROVIDE PRODUCT APPROVAL FOR:
 A) FIXED WINDOWS. THERE ARE PRODUCT
 APPROVALS FOR TWO DIFFERENT
 MANUFACTURERS. PROVIDE ONLY PRODUCT
 APPROVAL OF COMPANY TO BE USED.
 B) CONCRETE LINTELS. DADE COUNTY NOA
 FOR 8"X8" LINTELS IS EXPIRED. NEED TO
 PROVIDE CURRENT ONE.
 C) ALUMINUM SIDING. PRODUCT APPROVAL
 SUBMITTED IS FOR CEMENTITIOUS SIDING
 PRODUCTS, NOT ALUMINUM AS SPECIFIED ON
 PLANS. NEED SPECIFIED PRODUCT APPROVAL.
 ***NOTE; IF SIDING IS NOT GOING TO BE
 INSTALLED, THEN REVISE ALL PLANS,
 ELEVATIONS AND SECTIONS AS REQUIRED.
 D) ALL SIMPSON STRUCTURAL CONNECTORS
 AS SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED ARE FOR USP AND ONLY ONE WAS
 GOOD FOR THE USP HLPTA75 CONNECTOR. THE
 REST OF THE PRODUCT APPROVALS SUBMITTED
 WERE NOT SPECIFIED ON PLANS.
 E) ALUMINUM VENTS SHOWN ON ELEVATIONS.
 F) ASPHALT SHINGLES NOA THAT MATCHES
 NOA SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL. GO TO WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD CORRECT NOA.
 G) WINDOW MULLIONS. ONE SUBMITTED IS
 EXPIRED.
  
 3- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS, INCLUDING THE STORM SHUTTERS
 AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC.
 ***NOTE: TYPICALLY THIS IS DONE USING
 THE STANDARD REVIEW STAMP USED FOR SHOP
 DRAWINGS REVIEW.
  
 4- STORM SHUTTERS:
 A) PLEASE USE ATTACHED REVISED SAMPLE
 OF STORM SHUTTERS INSTALLATION SCHEDULE
 TO EXPEDITE THE REVIEW PROCESS.
 B) INSTALLATION SCHEDULE:
 * WHY THE DESIGN PRESSURES ARE N/A?.
 THIS IS THE MOST IMPORTANT INFORMATION
 TO VERIFY COMPLIANCE OF PRODUCT BASED ON
 THE CALCULATED DESIGN PRESSURES. NEED
 THIS INFORMATION. SEE PLANS.
 C) VERIFY SIZES FOR PANEL SPAN. EG:
 OPENINGS 8 AND 9. IF THE OPENINGS ARE
 5'X6'-8" HOW COME THE PANEL SPAN IS
 88"?. (CHECK ALSO SIZE OF TRANSOM WINDOW
 ABOVE DOORS). THIS APPLIES TO 4' HIGH
 OPENINGS. WHY USING 68" LONG PANELS?.
 D) VERIFY STRUCTURE TO BE ATTACHED TO.
 THIS IS A CONCRETE BLOCK STRUCTURE, NOT
 POURED CONCRETE. REVISE AS REQUIRED.
  
 5- DRAWING A-1: UPDATE CODE REFERENCE
 SPECIFIED FOR ATTIC ACCESS, FIREBLOCKING
 AND WINDOW/DOOR GLAZING PROTECTION. THIS
 IS A RESIDENCE THE CORRECT CODE THAT
 REGULATES DWELLINGS IS THE RESIDENTIAL
 2004 CODE, NOT THE FBC 2004. REVISE AS
 REQ'D AND CITE CORRECT CODE REFERENCE
 SECTIONS FROM THE RESIDENTIAL CODE.
  
 6- DRAWING A-2: A) BEDROOM #1 WINDOW
 DOESN'T COMPLY WITH EGRESS SECTIONS
 R310.1.1 AND R310.1.2.BOTH WINDOWS IN
 FRONT ELEVATION ARE SHOWN AS 3'X4'
 WINDOWS. ACCORDING TO FLOOR PLAN WINDOW
 IS 3'X5'. CLARIFY/REVISE AS REQUIRED.
 B) WHAT ARE THE LETTERS IDENTIFYING
 THE OPENINGS FOR? THEY DON'T MATCH FLOOR
 PLAN AND THERE IS NOT LEGEND IDENTIFYING
 THIS LETTERS. CLARIFY AS REQUIRED.
 C) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVERS AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004 AND SECTION R806.
  
 7- DRAWING A-3: SECTION "A", WHERE IS
 DETAIL SHT 5?
  
 8- DRAWING A-4: WALL SECTION "A".
 SPECIFY FIREBLOCKING MATERIAL AND
 REVISE REFERENCE FOR FIREBLOCKING. SEE
 RESIDENTIAL 2004 FOR CORRECT CODE
 SECTION.
  
 9- DRAWING S-1: A) PROVIDE DETAIL/SPECS
 FOR 4"X4" WOOD POST AT REAR WOOD DECK.
 NEED TO SPECIFY ATTACHMENT OF WOOD POST
 TO FOOTING. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
 B) SPECIFY TRUSS CONNECTORS ON ROOF
 FRAMING PLAN. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 10- DRAWING S-2: A) TYP. ONE STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. PROVIDE SPECIFIC
 INFORMATION. SECTION R806 2004.
 B) DETAIL H: USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 11- DRAWING S-3: A) REVISE TRUSS ANCHOR
 SCHEDULE. UPLIFT CAPACITY DOESN'T MATCH
 UPLIFT CAPACITY SHOWN ON CURRENT USP
 CATALOGUE. REVISE AS REQUIRED OR PROVIDE
 COMPLETE ENGINEERING PACKAGE SHOWING WHY
 CHANGING THE VALUES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 12- ENERGY CALCULATIONS:
 A) IF THIS IS A MODEL HOUSE. ENERGY
 CALCULATIONS NEED TO BE DONE FOR WORST
 CASE SCENARIO OR MUST BE SITE SPECIFIC
 WITH CORRECT HOUSE ORIENTATION.
 CALCULATIONS SUBMITTED ARE NOT FOR WORST
 CASE SCENARIO.
 B) OVERHANG LENGTH AND HEIGHT DON'T
 MATCH PLANS. REVISE AS REQUIRED.
 C) PROVIDE ENERGY CALCULATIONS FOR
 CORRECT ADDRESS AND COMPLETE INFORMATION
 ON TOP OF FORM. EG: BUILDER, ETC.
  
 13- ARCHITECT'S TITLE BLOCK TO INCLUDE
 ALL INFORMATION REQUIRED BY CHAPTER 481
 FLORIDA STATUTES AND 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. SEE
 ATTACHED COPY.NEED NAME OF ARCHITECT
 SIGNING AND SEALING PLANS.
  
 14- SOIL TEST REPORT:
 A) PROVIDE SOIL TEST REPORT FOR CORRECT
 ADDRESS.
 B) ENGINEER TO PROVIDE THE FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AND
 HIS LICENSE NUMBER AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 15- OWES $341.76 FOR UPDATED VALUATION
 AND RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 07:25 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 07:08 Sent To M
Notes
2006-06-29 00:00:00*** REDLINED ***
  
 SD'S ARE STILL BEING SHOWN ON CIRCUIT
 #2, IF THIS IS THE CASE, THEN CIR# 2
 SHALL BE ARC FAULT. 210.12B
  
 PLEASE SEE MISSING RECEPT PER 210.52

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 09:18 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 09:18 Sent To P
Notes
2008-01-04 09:18:47TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 19:40 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 19:40 Sent To B
Notes
2006-09-09 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-06 Cont ID  
Sent By jgomez Date 2006-07-06 Time 16:44 Rev Time 0.00
Received By jgomez Date 2006-06-28 Time 09:08 Sent To  
Notes
2006-06-28 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By tgordon Date 2006-06-29 Time 10:51 Rev Time 0.30
Received By tgordon Date 2006-06-29 Time 10:51 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-10 Cont ID  
Sent By jleech Date 2008-01-10 Time 08:57 Rev Time 0.00
Received By jleech Date 2008-01-10 Time 08:57 Sent To  
Notes
2008-01-10 08:59:42LETTER FROM ENGINEER REDUCING THE SHOWER WIDTH FROM 32"
 TO 30"

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By jleech Date 2006-06-29 Time 08:37 Rev Time 0.00
Received By jleech Date 2006-06-29 Time 08:37 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By mmclean Date 2006-06-28 Time 11:55 Rev Time 0.00
Received By mmclean Date 2006-06-28 Time 11:55 Sent To E
Notes
2006-06-28 00:00:00NOTE:
 THE PROPOSED A/S UNIT SHALL NOT BE
 CLOSER THAN 6FT FROMSIDE PROPERTY
 LINE.