Plan Review Details - Permit 06061475
Plan Review Stops For Permit 06061475
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-18 Cont ID  
Sent By lursu Date 2006-07-18 Time 08:52 Rev Time 0.00
Received By lursu Date 2006-06-27 Time 10:58 Sent To  
Notes
2006-07-18 00:00:00EXT #0001 IS ADDED FOR THE UNIT 2114 FOR
 THE SECOND FLOOR UNDER THE MAIN ADDRESS
 901 S FLAGLER DR,PCN =
 74434327350000010.
2006-06-27 00:00:00ADDRESS ON APP READS 901 S FLAGLER
 DR/2ND FLOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-13 Cont ID  
Sent By mjacobs Date 2006-12-13 Time 15:13 Rev Time 0.00
Received By mjacobs Date 2006-12-13 Time 09:55 Sent To PC
Notes
2006-12-13 15:13:18PROVISOR.
  
 NEC 2002: ARTICLE 645.2 #5THE WALL AND FLOORS OF THE
 INFORMATION TECHNOLOGY EQUIPMENT ROOM SHALL HAVE A FIRE
 RATING NOT LESS THAN 1 HOUR. SEE NFPA 75:5.1.3 FOR MORE
 INFORMATION.THE EXISTING WALLS SHALL MEETS THIS
 REQUIREMENT AS WELL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-18 Cont ID  
Sent By mjacobs Date 2006-09-18 Time 13:38 Rev Time 0.00
Received By mjacobs Date 2006-09-18 Time 09:04 Sent To  
Notes
2006-09-18 00:00:00 
 1) THE PRINTED NAME OF THE PERSON
 SEALING THE DRAWINGS SHALL BE ON EACH
 SHEET WHICH IS SEALED BY THAT PERSON.
 SEE SHEETS D-1 - A-2.
  
 2) NFPA 75. 5.1.3.
 THE INFORMATION TECHNOLOGY EQUIPEMENT
 ROOM SHALL BE SEPERATED FROM OTHER
 OCCUPANCIES IN THE INFORMATION
 TECHNOLOGY EQUIPMENT AREA BY A FIRE
 RESISTANCE RATING NOT LESS THAN 1 HOUR.
  
 3) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By mjacobs Date 2006-07-19 Time 09:47 Rev Time 0.00
Received By mjacobs Date 2006-07-18 Time 09:01 Sent To M
Notes
2006-07-18 00:00:001) ALL PLANS SUBMITTED AFTER OCTOBER,
 1,2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 2) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL
 (SEE ALSO SECTION 106.3.5 ).
  
 3) 1509.7 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE
 MOUNTED ON CURBS RAISED A MINIMUM OF 8
 INCHES (203 MM) ABOVE THE ROOF SURFACE,
 OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH ("TABLE
 1509.7".)
  
 4) THE ROOF PIPING SUPPORT DETAIL ON
 SHEE M-3 DOES NOT CORRESPOND WITH THE
 DETAIL ON SHEET A-2. ALSO ON SHEET M-3,
 WHERE IS THE GALVANIZED TROUGH DETAIL?
 NOTE: THE DETAIL SHOWN FOR THE ROOF
 PIPING PENETRATIONS HAS THE POTENTIAL
 FOR WATER INTRUSION IN THE FUTURE.
  
 5) INDICATE THE SLOPE OF THE ROOF
 STRUCTURE WHERE THE MECHINICAL SUPPORTS
 WILL BE INSTALLED. IF THE ROOD IS
 SLOPED, SHOW THE ELEVATIONS OF THE
 MECHNICAL SUPPORTS.
  
 6) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
  
 MYRON JACOBS
 BUILDING PLANS EXAMINER
 TEL:(561) 805-6726
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-05-08 Cont ID  
Sent By dpalmer Date 2007-05-08 Time 17:10 Rev Time 0.00
Received By dpalmer Date 2007-05-08 Time 16:55 Sent To PC
Notes
2007-05-08 17:12:34** UNSAT **
  
 1) NOTE: PLEASE SEE REVIEW NOTES FROM PREVIOUS REVIEW
 AND NOTES AS REDLINED ON PROVISO AS NOTED ON PLANS
 ISSUED FOR PERMIT.
 PLEASE SEE THE TEXT BELOW WHICH WAS SENT TO THE
 ENGINEER VIA E-MAIL.
  
  
  
 MR. STEWART,
  
 UPON REVIEWING THE LOCATIONS OF THE TWO DISCONNECTS ON
 PLANS. THE LOCATIONS ARE TOO FAR APART AND CAN NOT BE
 ACCEPTED.
 PLEASE SEETHAT A DISCONNECT WOULD BE REQUIRED AT A
 LOCATION CLOSER AND IN CLOSE PROXIMITY OF THE EXISTING
 DISCONNECT FOR THIS BUILDING. THIS IS WHAT WAS REDLINED
 AS A "PROVISO" ON ORIGINAL PLANS. WHEN WE SPOKE ON THE
 PHONE I DID NOT HAVE THE PLANS, AND CAN NOW SEE HOW FAR
 THESE DISCONNECTS ACTUALLY ARE. MY DECISIONS IS THE
 SAME AS ON ORIGINAL REDLINED PLANS AND REVIEW UNDER THE
 PERMIT THAT THESE ARE TOO FAR APART.
 I CAN NOT ACCEPT THE SIGNAGE IN LIEU OF GROUPING THE
 DISCONNECTS FOR THIS BUILDING.
 MY NOTES AS STATED PREVIOUSLY WITH RESPECT TO MEETING
 EXCEPTION STILL WOULD STAND IF THAT METHOD/OPTION IT
 TAKEN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 10:08 Sent To  
Notes
2007-04-08 10:10:06** UNSAT **
  
 1) NOTE: PLEASE SEE THAT NOT ALL SHEETS ARE SIGNED,
 DATED AND SEALED BY THE ENGINEER OF RECORD.
 FS 471.025, FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE THE PLANS WERE ISSUED FOR PERMIT
 WITH *NOTES REDLINED* AND ATTACHED TO PLANS. PLEASE SEE
 TO DATE THAT NO DOCUMENTATION AHS BEEN VERIFIED FOR
 COMPLIANCE TO MEET THE EXCEPTIONS OF THE NEC FOR
 DISCONNECTING MEANS ETC AS PREVIOUSLY GONE OVER FOR THE
 DETACHED BUILDING.
 PLEASE SEE 225.31-225.398
 PLEASE SEE THE NOTES BELOW ARE TAKEN FROM THE ISSUED
 PLANS AND PERMITS FOR SCOPE OF WORK.
 PLEASE PROVIDE COMPLETED DOCUMENTATION FOR EXCEPTION OF
 *SAFE PROCEDURES*, *QUALIFIED PERSONNEL* ON-SITE 24/7
 ETC, PAPERWORK AND DOCUMENTATION MUST BE ORIGINAL,
 SIGNED, AND NOTARIZED.
 IF THIS IS NOT MET THEN PLANS AS ORIGINALLY NOTED WILL
 NEED TO BE REVISED TO MEET NEC CODE COMPLIANCE.
  
 3) NOTE: PLEASE ALSO SEE THAT AS TO DATE OUR RECORDS DO
 NOT INDICATE ANY LOW VOLTAGE PERMIT WHICH HAS BEEN
 APPLIED FOR OR ISSUED FOR THIS PROJECT.
 PLEASE SEE NOTES REDLINED ON PLANS WHICH MENTION THIS
 IS TO BE UNDER A SEPARATE PERMIT.
  
  
  
 ************** NOTES REDLINED*******
  
 *** LOW VOLTAGE WIRING UNDER A SEPARATE PERMIT.
  
  
 **** 1) NOTE: PLEASE KNOW UPON READING RESPONSE FROM
 DESIGN TEAM, THIS OFFICE IS WELL AWARE THAT THE
 STRUCTURE MAY BE FED WITH OTHER SYSTEMS AS LISTED IN
 225.30.PLEASE SEE PREVIOUS NOTES WHICH WAS WITH
 RESPECT TO DISCONNECTING MEANS REQUIRED ETC. PLEASE SEE
 THE FOLLOWING EXCEPTION WHICH IS TAKEN DIRECTLY FROM
 THE NEC WILL BE REQUIRED TO BE VERIFIED ON SITE.THIS
 WAS RED-LINED ON E-5.
 "EXCEPTION NO. 1: FOR INSTALLATIONS UNDER SINGLE
 MANAGEMENT, WHERE DOCUMENTED SAFE SWITCHING PROCEDURES
 ARE ESTABLISHED AND MAINTAINED FOR DISCONNECTION, AND
 WHERE THE INSTALLATION IS MONITORED BY "QUALIFIED
 INDIVIDUALS", THE DISCONNECTING MEANS SHALL BE
 PERMITTED TO BE LOCATED ELSEWHERE ON THE PREMISES "
  
 ** PLEASE SEE NEC ART: 100 FOR*QUALIFIED PERSON*. ONE
 WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE
 CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT
 AND INSTALLATIONS AND HAS RECEIVED SAFETY TRAINING ON
 THE HAZARDS INVOLVED.
 EXCERPT FROM HANDBOOK:
 "NEW IN THE 2002 EDITION, THE DEFINITION OF THE TERM
 QUALIFIED PERSON NOW INCLUDES SAFETY TRAINING. NO
 LONGER IS IT ADEQUATE FOR AN ELECTRICAL WORKER TO BE
 *FAMILIAR WITH THE HAZARDS INVOLVED*; THE ELECTRICAL
 WORKER OF TODAY MUST ALSO HAVE SAFETY TRAINING ON THE
 HAZARDS INVOLVED. "
  
 ** PLEASE KNOW THESE QUALIFIED PERSON(S) SHALL BE
 VERIFIED EMPLOYED BY AND ON SITE 24/7, IF THIS CAN NOT
 BE VERIFIED, ELECTRICAL INSTALLATION AS SHOWN MAY NEED
 TO BE ADJUSTED TO MEET CODE.
 THIS PLANS EXAMINER CAN NOT VERIFY AND WILL BE THE
 RESPONSIBILITY OF THE ENGINEERING / DESIGN TEAM,
 LICENSED ELECTRICAL CONTRACTOR AND ELECTRICAL
 INSPECTOR.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-03 Cont ID  
Sent By dpalmer Date 2006-11-03 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2006-11-03 Time 20:04 Sent To  
Notes
2006-11-03 20:47:30************** NOTES REDLINED*******
  
 *** LOW VOLTAGE WIRING UNDER A SEPARATE PERMIT.
  
  
 **** 1) NOTE: PLEASE KNOW UPON READING RESPONSE FROM
 DESIGN TEAM, THIS OFFICE IS WELL AWARE THAT THE
 STRUCTURE MAY BE FED WITHOTHER SYSTEMS AS LISTED IN
 225.30.PLEASE SEE PREVIOUS NOTES WHICH WAS WITH
 REPSECT TO DISCONNECTING MEANS REQUIRED ETC. PLEASE SEE
 THE FOLLOWING EXCEPTION WHICH IS TAKEN DIRECTLY FROM
 THE NEC WILL BE REQUIRED TO BE VERIFIED ON SITE.THIS
 WAS RED-LINED ON E-5.
 "EXCEPTION NO. 1: FOR INSTALLATIONS UNDER SINGLE
 MANAGEMENT, WHERE DOCUMENTED SAFE SWITCHING PROCEDURES
 ARE ESTABLISHED AND MAINTAINED FOR DISCONNECTION, AND
 WHERE THE INSTALLATION IS MONITORED BY "QUALIFIED
 INDIVIDUALS", THE DISCONNECTING MEANS SHALL BE
 PERMITTED TO BE LOCATED ELSEWHERE ON THE PREMISES "
  
 ** PLEASE SEE NECART: 100 FOR "QUALIFIED PERSON".
 "QUALIFIED PERSON. ONE WHO HAS SKILLS AND KNOWLEDGE
 RELATED TO THE CONSTRUCTION AND OPERATION OF THE
 ELECTRICAL EQUIPMENT AND INSTALLATIONS AND HAS RECEIVED
 SAFETY TRAINING ON THE HAZARDS INVOLVED.
 EXCERPT FROM HANDBOOK:
 "NEW IN THE 2002 EDITION, THE DEFINITION OF THE TERM
 QUALIFIED PERSON NOW INCLUDES SAFETY TRAINING. NO
 LONGER IS IT ADEQUATE FOR AN ELECTRICAL WORKER TO BE
 ?FAMILIAR WITH THE HAZARDS INVOLVED?; THE ELECTRICAL
 WORKER OF TODAY MUST ALSO HAVE SAFETY TRAINING ON THE
 HAZARDS INVOLVED. "
  
 ** PLEASE KNOW THESE QUALIFIED PERSON(S) SHALL BE
 VERIFIED EMPLOYED BY AND ON SITE 24/7, IF THIS CAN NOT
 BE VERIFIED , ELECTRICAL INSTALLATION AS SHOWN MAY NEED
 TO BE ADJUSTED TO MEET CODE.
 THIS PLANS EXAMINER CAN NOT VERIFY AND WILL BE THE
 RESPONSIBILTY OF THE ENGINEERING / DESIGN TEAM,
 LICENSED ELECTRICAL CONTRACTOR AND ELECTRICAL
 INSPECTOR.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL., TO DATE, NO
 ONE FROM THE DESIGN TEAM HAS CONTACTED THIS OFFICE FOR
 ANY COMMENTS OR QUESTIONS.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 [email protected]
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-16 Cont ID  
Sent By dpalmer Date 2006-09-16 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2006-09-15 Time 21:29 Sent To  
Notes
2006-09-16 00:00:00*** UNSAT ***
  
 ** PLEASE SEE SOME NOTES FORM PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE VALUE FOR SCOPE OF
 WORK WAS INCREASED BY THE $120K ON
 RESPONSE. THE ADDITIONAL FEE WILL BE
 OWED BEFORE PERMIT CAN BE ISSUED.
 FEE OWED $1332.00
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE WHICH
 REQUESTED ALL MANUFACTURES SPECS/CUT
 SHEETS FOR THE UPS SYSTEM(S) EQUIPMENT,
 ATS EQUIPMENT ETC.
 RESPONSE MENTIONS THIS WERE TO BE
 SUBMITTED , HOWEVER THESE WERE NOT
 SUBMITTED FOR REVIEW.
 110.3,90.7
  
 3) NOTE: PLEASE SEE IT IS STILL UNCLEAR
 IF THIS IS CONSIDERED AS "ONE BUILDING"
 FROM THE DEFINITIONS AS SETFORTH IN THE
 FBC. PLEASESEE DEFINITIONS ,, WALKWAYS,
 ENCLOSED, OPEN ETC AND THE EXTEND OF THE
 SIZE(S) NEEDED FOR THE CONSIDERATION OF
 "ONE BUILDING". PLEASE KNOW, SOME OF
 THIS LAYOUT OR INFORMATION MAY BE
 SUPPLIED OR SHOWN ON SEPARATE SHEETS
 FROM THE ARCHITECT ECT FOR
 CLARIFICATION.
 225.31-225.39
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-09-15 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 07:26 Sent To  
Notes
2006-06-29 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE ADDRESSING SHALL
 CORRELATE, AS THE APPLICATION SHOWS 901
 S FLAGLER, THE PCN USED IS FOR 900 S
 OLIVE, AND PLANS SHOWS 1101 S OLIVE.
 PLEASE KNOW, ALL THESE SHALL CORRELATE
 AND ONCE THE "ADDRESS" IS CORRECTED,
 PLEASE MAKE SURE ALL TITLE BLOCKS ON ALL
 SHEETS ARE CORRECTED.
 FAC 61G1-16.004
  
 2) NOTE: PLEASE SEE COVER SHEETS STATES
 DESIGN PER 2001 FBC, WHERE WE ARE
 CURRENTLY UNDER THE 2004 FBC.
  
 3) NOTE: PLEASE SEE PLANS SHALL INCLUDE
 ALL THE CURRENT CODES ADOPTED AND IN
 AFFECT IN THE STATE OF FLORIDA.
 PLEASE SEE THE FOLLOWING CODES SHALL BE
 STATED ON PLANS AT A MINIMUM.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002, NFPA-75 2003.
  
 4) NOTE: PLEASE SEE VALUE FOR COMPLETE
 SCOPE OF WORK SHALL BE ADJUSTED TO
 INCLUDE ALL LABOR AND MATERIALS.
 PLEASE KNOW, EVEN IF ANY EQUIPMENT IS
 SUPPLIED BY THE OWNER.
 VALUE AT THIS TIME IS LOW.
 FBC ADMIN SECT 108.3
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETSFOR ALL NEW UPS
 EQUIPMENT.
 110.3, 106.1.2
  
 6) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETS FOR THE NEW ATS BEING
 PROPOSED.
 110.3, FBC106.1.2
  
 7) NOTE: PLEASE SEE RISER MENTIONS TAPS
 PER "220.21"? THIS SHOULD BE PER
 "240.21"
 PLEASE ALSO KNOW, NOTE MENTIONS NOT TO
 BE LOCATED MORE THAN 10FT AWAY, HOWEVER
 PLEASE KNOW AND NOTE ON PLANS, THAT ITS
 THE CONDUCTOR LENGTH NOT THE DISTANCE.
 PLEASE ADJUST NOTE.
 240.21, 215.5
  
 8) NOTE: PLEASE CLARIFY PLANS, RISER AS
 PLANS SEEM TO BE SHOWING THE FEEDERS
 COMING FROM A SEPARATE, DETACHED
 BUILDING??
 IF THIS IS THE CASE PLEASE SEE
 225.31-225.39.
 PLEASE ADJUST, AND PLEASE VERIFY THE
 EXISTING AS THIS DOES NOT SEEM TO MEET
 225.31-225.39
 PLEASE ALSO SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM.
  
 9) NOTE: PLEASE PROVIDE VD CALCULATIONS
 FOR THE NEW FEEDERS FROM THE EXISTING
 MAIN ELECTRICAL RM.
 FBC 2004 13-413.1ABC.1
  
 10) NOTE: PLEASE PROVIDE A GROUNDING
 RISER FOR ALL EQUIPMENT,UPS AND
 ATTACHMENT LOCATION(S). 250.30,250.20,
 645.15
  
 ** IMPORTANT**
  
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF THE OLD/VOIDED
 SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-05 Cont ID  
Sent By mawillia Date 2006-12-05 Time 14:33 Rev Time 0.00
Received By mawillia Date 2006-12-05 Time 14:33 Sent To  
Notes
2006-12-05 14:36:51*****APPROVED*****
  
  
  
 COMMENT #5 FROM PREVIOUS FIRE PLAN REVIEWS HAS BEEN
 ADDRESSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-24 Cont ID  
Sent By mawillia Date 2006-10-24 Time 13:06 Rev Time 0.00
Received By mawillia Date 2006-10-24 Time 13:06 Sent To  
Notes
2006-10-24 13:31:18*****UNSAT*****
  
 YOUR RESPONSES TO FIRE PLAN REVIEW COMMENTS OF
 7/10/2006 RECEIVED AS:
  
  
 1.)OK
  
 2.)OK
  
 3.)OK
  
 4.)OK
  
 5.)BE ADVISED AS PER NFPA 101, 2003 EDITION, 10.2,
 INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS AND
 EXIT CORRIDORS SHALL BE CLASS "A" OR "B".
  
 6.)SO NOTED.
  
 7.)SO NOTED.
  
 8.)OK
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 11:52 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 11:39 Sent To  
Notes
2006-07-10 00:00:001. DEMOLITION, CONSTRUCTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. EXITS SHALL REMAIN CLEAR AND
 ACCESSIBLE.
  
 4. PLEASE EXPLAIN STAIR SHOWN IN
 EXISTING COMPUTER ROOM. IS IT AN EXIT OR
 WHERE DOES IT TERMINATE AT THE TOP AND
 BOTTOM, PLEASE EXPLAIN.
  
 5. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED
 FOR PROPOSED PRE-ACTION FIRE SUPPRESSION
 SYSTEM PLANNED FOR USE.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW FIRE ALARM EQUIPMENT PLANNED
 TO BE INSTALLED.
  
 8. PLEASE ILLUSTRATE ALL EXISTING OR NEW
 EMERGENCY LIGHTS OR EXIT SIGNS IN THE
 GENERAL OR VICINITY OF THE WORK BEING
 PROPOSED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 10:03 Rev Time 0.00
Received By shill Date 2007-05-03 Time 10:03 Sent To E
Notes
2007-05-03 10:03:27TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 20:30 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 20:30 Sent To  
Notes
2007-04-02 17:11:58TO COMM BOARD # 5
2007-03-29 20:31:13WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-30 Cont ID  
Sent By adarroug Date 2006-10-30 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-10-30 Time 16:08 Sent To  
Notes
2006-11-01 16:53:45TO "COMM" BD#28
2006-10-30 16:08:22WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-07 Cont ID  
Sent By adarroug Date 2006-09-07 Time 15:53 Rev Time 0.00
Received By adarroug Date 2006-09-07 Time 15:53 Sent To  
Notes
2006-09-13 00:00:00TO "COMM" BD#45
2006-09-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-24 Cont ID  
Sent By pkrauss Date 2006-07-24 Time 13:12 Rev Time 0.00
Received By pkrauss Date 2006-06-28 Time 10:51 Sent To  
Notes
2006-06-28 00:00:00TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2007-05-01 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-12-11 Cont ID  
Sent By hmoser Date 2006-12-11 Time 16:10 Rev Time 0.00
Received By hmoser Date 2006-12-11 Time 16:43 Sent To B1
Notes
2006-12-11 16:16:02PASS PRIVISO
 PAGE M-3PLEASE PROVIDE A ENGINEER DRAWING ON TIE DOWN
 OF CURB TO ROOF FOR ROUGH INSPECTION
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-10-17 Cont ID  
Sent By hmoser Date 2006-10-17 Time 09:26 Rev Time 0.00
Received By hmoser Date 2006-10-17 Time 09:26 Sent To  
Notes
2006-10-17 09:29:581)PAGE M-4 REFRIGERANT PIPING THROUGH ROOF DETAIL
 DOES NOT MATCH RESPONSE # 5
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By pkrauss Date 2006-07-20 Time 13:58 Rev Time 0.00
Received By pkrauss Date 2006-07-20 Time 13:58 Sent To  
Notes
2006-07-20 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET S2 DETAIL 1 & 3,
 INDICATES A NEW CAP PLATE & I-BEAM TO BE
 WELDED ONTO THE EXISTING POST.
 DEMENSION OF 6" BETWEEN THE ROOF SURFACE
 AND BOTTOM OF THE OF THE I-BEAM IS 6"
 WITH THE CONDENSING UNITS LEGS ARE 2'
 LONG.PER 2004 FBC 1509.7 WHERE ROOFING
 MATERIALS EXTEND BENEATH THE UNIT ON
 REAISED EQUIPMENT SUPPORTS, THE MINIMUM
 CLEARANCE SHALL BE IN ACCORDANCE WITH
 TABLE 1509.7 FROM THE ROOF SURFACE WO
 THE BOTTOM OF THE SUPPORT RAIL.THE 6"
 DOES NOT MEET THIS REQUIREMENT.
  
 2.PLEASE CLARIFY DETAIL ON PLAN SHEET
 M-3.REFRIGERANT LINES THROUGH THE
 BUILDING TO THE ROOF SHALL COMPLY WITH
 2004 FBC 1514.2.5 THROUGH 1514.2.5.2
  
 3.PLEASE NOTE, REFRIGERANT LINS SHALL
 COMPLY WITH ASHRAE 62-2001
  
 4.PLAN SHEET A-2 INDICATES A DETAIL
 FOR PATE CURB FOR MULTPLE PIPES
 PENETRATIONS.ARCHITECTURAL PLANS DO
 NOT SHOW DETAIL OF THE GALVANIZED TROUGH
 AS INDICATED ON PLAN SHEET M-3.
  
 5.PLEASE CLARIFY THE REFRIGERANT
 PIPING DETAIL THRU ROOF SHOWN ON PLAN
 SHEET M-4.THIS INDICATES INSULATED
 PIPING THROUGH CONCRETE ROOF SLAB, SHOW
 COMPLIANCE WITH 2004 FMC 1107.2.1.
 DETAIL ALSO INDICATES COUNTER FLASHING
 TO BE SAME MATERIAL AS THE PIPE AND IS
 TO BE SOLDERED TO REFRIGERANT LINE.IS
 THIS CORRECT?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-07 Cont ID  
Sent By tgordon Date 2006-07-07 Time 09:29 Rev Time 1.30
Received By tgordon Date 2006-07-07 Time 09:29 Sent To  
Notes
2006-07-07 00:00:00*** PROVISO ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTES #1
 AND #2, AND CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-23 Cont ID  
Sent By pschmitz Date 2006-09-23 Time 07:51 Rev Time 0.00
Received By pschmitz Date 2006-09-23 Time 07:51 Sent To  
Notes
2006-09-23 00:00:00RE-SUB

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-01 Cont ID  
Sent By pschmitz Date 2006-07-01 Time 06:37 Rev Time 0.00
Received By pschmitz Date 2006-07-01 Time 06:20 Sent To  
Notes
2006-07-01 00:00:00PROVISO:
 SHT. P-2 1ST FLOOR KEY NOTE #1
 3/4" A/C CONDENSATE TO DRY WELL OR
 PLANTER.


Account Summary | Usage Policy | Privacy Policy