Plan Review Details - Permit 06061453
| Plan Review Stops For Permit 06061453 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-25 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-25 |
Time |
08:15 |
Rev Time |
0.25 |
| Received By |
alange |
Date |
2006-07-25 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2006-07-25 00:00:00 | DENIED | | | | | | SHOW GENERATOR SLAB DETAIL AND METHOD OF | | | ATTACHMENT TO SLAB. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-15 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | ****** UNSAT ******* | | | | | | 1) NOTE: PLEASE SEE VALUE SHALL BE BASED | | | ON ALL LABOUR AND MATERIALS WHETHER OR | | | NOT ANY MATERIALS ARE OWNER SUPPLIED. | | | FBC ADMIN SECT 108.3 AS ADOPTED BY THE | | | CITY OF WEST PALM BEACH. | | | | | | 2) NOTE: PLEASE SEE THAT PLANS ARE | | | REQUIRED TO BE DONE BY A PE. | | | FS 471.003. | | | | | | 3) NOTE: PLEASE PROVIDE INFORMATION ON | | | WHAT TYPE OF RETAIL STORE THIS SYSTEM | | | WILL BE SUPPLYING? IF THIS IS GAS | | | STATION FURTHER CONSULTATION WILL BE | | | REQUIRED AS AN ATS MAY NOT BE PERMITTED. | | | PLEASE INDICAT OF ANY EM DEVICES WILL BE | | | RE-FED FROM THIS GEN OR DOES ALL | | | EXISTING EM DEVICES CONTAIN BATTERY BACK | | | UP. | | | | | | 4) NOTE: PLEASE KNOW, THE A/C HEAT LOADS | | | SHALL BE FIGURED AT 100%. PLEASE KNOW, | | | LOAD SHEDDING AND TIMED DELAY STARTING | | | OF UNITS WILL BE PERMITTED. | | | PLEASE ALSO KNOW, ALL CONTINUOUS LOADS | | | SHALL BE SHOWN AT 125%. 215.3,230.42 ETC | | | 702.5, 220.31, 90.4 | | | | | | 5) NOTE: PLEASE KNOW, ALL PLANS SHALL | | | CONTAIN THE PRINTED NAME AND SIGNATURE | | | OF ALL PERSONS RESPONSIBLE FOR DESIGN | | | ETC. | | | FBC 106.1 | | | | | | 6) NOTE: PLEASE BE SURE ALL MANUFACTURES | | | SPECS INCLUDE THE MIN CLEARENCES | | | REQUIRED BY MANUFACTURE FOR EQUIPMENT. | | | 110.26,110.3 ETC | | | | | | 7) NOTE: PLEASE INDICATE ON SITE PLAN | | | WHERE THE NEW MAIN, ATS ETC WILL BE | | | LOCATED. | | | NEED TO VERIFY GROUPING OF DISCONNECTS | | | PER 225.34,230.72 ETC. | | | | | | 8) NOTE: PLEASE CLARIFY WHICH DISCONNECT | | | WILL FEED THE 400A ATS, AS BOTH 400A | | | MAINS CAN NOT FEED ONE 400A ATS, AS THE | | | ATS IS NOT RATED FOR 800A'S.PLEASE | | | REVISE RISER, AS SHOWN IS NOT CLEAR WHAT | | | IS TAKING PLACE. | | | 310.16,240.4,215.5, 230.70 ETC. | | | | | | 9) NOTE: PLEASE SUBMIT MANUFACTURES | | | SPECS/CUT SHEETS REQUIRED FOR ATS. | | | 110.3,702.6 ETC. | | | | | | | | | 10) NOTE: PLEASE INDICATE THE OCP AT THE | | | GEN, AS THE VOLTAGE FOR SERVICE IS NOT | | | SHOWN. | | | PLEASE HIGH-LIGHT SPECS ALSO. | | | 106.1.2 FBC ADMIN SECT, 445.13 ETC. | | | | | | ** PLEASE SEE COMMENTS FROM OTHER TRADES | | | AS THEY WILL HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-07-11 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-07-11 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | 1. PRODUCT DATA INDICATES THAT THE | | | GENERATOR IS PLANNED TO BE NATURAL GAS | | | ALTHOUGH THE PLANS ONLY DISPLAYS THE | | | GENRATOR NEXT TO BUILDING. | | | | | | 2. HOW IS THE PROPOSED GENRATOR FED WITH | | | A GAS SUPPLY AS NONE IS SHOWN ON THE | | | SITE PLAN. | | | | | | 3. PLEASE INDICATE ON THE PLANS WHERE | | | DOORS, WINDOWS, OR ANY OTHER BUILDING | | | OPENINGS ARE PRESENT ON THE ELEVATION | | | WHERE THE GENERATOR IS BEING PROPOSED TO | | | BE INSTALLED. | | | | | | 4. PLEASE PROVIDE A SURVEY TO DETERMINE | | | THE DISTANCE FROM THE GERATOR TO THE | | | ADJACENT PROPERTY LINES. | | | | | | 5. THE PLUMBING INSPECTOR WILL NEED TO | | | SEE A PIPING LAYOUT AND AND OTHER | | | DETAILS ASSOCIATED WITH THE | | | INSTALLATION. | | | | | | 6. THE GENERATOR IS TO PROVIDE BACK-UP | | | POWER TO WHAT DEVICES OR SYSTEMS. IS THE | | | GENERATOR TO SUPPLY BACK-UP POWER TO THE | | | RETAIL STORE AND THE FUEL DISPENSING | | | PUMPS OR JUST THE FUEL PUMPS. PLEASE | | | IDENTIFY EQUIPMENT OR DEVICES. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
N |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-18 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-18 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2006-08-18 00:00:00 | SUBMITTAL DATA ON THE GENERATOR | | | INDICATES FUEL SOURCE AS NATURAL GAS, NO | | | FUEL OIL PERMIT REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-08 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-08 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | A. SEPARATE GAS PERMIT REQUIRED AND | | | SHALL BE SUBMITTED WITH GENERATOR | | | APPLICATION. | | | | | | B. THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PLAN REVIEW: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. - IF ADDING TO AN | | | EXISTING SYSTEM, PLEASE INDICATE ALL | | | PIPE SIZES AND SHOW REQUIREMENTS FROM | | | REQUIREMENTS 2, 4, & 5 BELOW. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. NOT USED | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). (THIS | | | INCLUDES EXISTING SYSTEM IF APPLICABLE). | | | | | | 6. NOT USED | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | (INFORMATION SUBMITTED DOES NOT SHOW | | | INSTALLATION INSTRUCTIONS AS FAR AS | | | MINIMUM DISTANCE FROM STRUCTURES | | | REQUIRED FOR SERVICING ETC.). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-18 |
Time |
16:00 |
Rev Time |
|
| Received By |
pkrauss |
Date |
2006-06-27 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | TO "COMM" BD#22 | | 2006-06-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-18 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-18 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2006-08-18 00:00:00 | DENIED:NATURAL GAS GENERATOR | | | 1.PLEASE PROVIDE DISTANCES/CLEARANCES | | | TO THE BUILDING, PROPERTY LINES, ROOF | | | OVERHANG, FRESH AIR INTAKES SUCH AS O.A. | | | INTAKES, WINDOWS, DOORS, OR VENTS FROM | | | THE GENERATOR EXHAUST. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2006-07-31 |
Time |
19:05 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2006-07-31 |
Time |
19:04 |
Sent To |
I |
|
| Notes |
| 2006-07-31 00:00:00 | PLANNING AND ZONING DEPARTMENT:FAILED | | | | | | 1. PROVIDE RESPONSES IN WRITING. | | | | | | 2. A MINOR AMENDMENT TO THE IBIS PLANNED | | | DEVELOPMENT, MASTER PLAN IS REQUIRED. AN | | | APPLICATION WILL NEED TO BE FILED TO THE | | | PLANNING AND ZONING DEPARTMENT AND | | | APPROVED PRIOR TO SIGN-OFF OF BUILDING | | | PERMIT.THE COMMENTS BELOW REFLECT THE | | | INFORMATION NEEDED ON SITE PLAN, PRIOR | | | TO SUBMITTAL OF THE MINOR AMENDMENT TO | | | THE IBIS RESIDENTIAL PLANNED | | | DEVELOPMENT. | | | | | | 3. PROVIDE A BETTER DETAIL OF THE AREA | | | WHERE THE GENERATOR IS PROPOSED, NOT AN | | | ENLARGEMENT.THE SITE PLAN SHALL | | | INCLUDE THE FOLLOWING: | | | | | | A. SCREENING AND ELEVATION OF | | | WALL/HEDGES AROUND GENERATOR/ FUEL TANK, | | | AND SETBACK DISTANCE FROM PROPERTY | | | LINE. | | | | | | 4.PURSUANT TO SECTION 94-444(B) OPEN | | | SPACE STANDARDS: | | | (B) FUEL OR OIL OR PROPANE | | | TANKS, GENERATORS SHALL NOT BE PERMITTED | | | UNLESS APPROPRIATE SCREENING IS | | | PROVIDED. SCREENING SHALL BE CONSTRUCTED | | | OF BRICK, DECORATIVE CONCRETE, OTHER | | | DECORATIVE MASONRY, OR COMPARABLY | | | DURABLE WOOD AND STEEL. | | | | | | WALLS SHALL BE LANDSCAPED WITH SHRUBS | | | AND HEDGES PLANTED AT TWO-FOOT | | | INTERVALS.A FOUR-SIDED ENCLOSURE | | | WITH MASONRY, OR COMPARABLY DURABLE WOOD | | | AND STEEL, AN OBSCURING GATE IS REQUIRED | | | AS A CONDITION FOR SITE PLAN APPROVAL. | | | | | | THE SCREENING SHALL ENCLOSE BOTH FUEL | | | TANK INCLUDING ROOFTOP EXHAUST (TANK, IF | | | APPLICABLE AND GENERATOR. | | | | | | 5.PURSUANT TO SECTION 94-305(B)(4) | | | SETBACKS | | | (B)(4) SETBACK ENCROACHMENT: | | | MECHANICAL EQUIPMENT SHALL NOT PROJECT | | | MORE THAN 4 FEET INTO A SETBACK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT ME AT THE NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1435 |
|
|
|