Plan Review Details - Permit 06061453
Plan Review Stops For Permit 06061453
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-25 Cont ID  
Sent By alange Date 2006-07-25 Time 08:15 Rev Time 0.25
Received By alange Date 2006-07-25 Time 08:15 Sent To  
Notes
2006-07-25 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 16:07 Sent To  
Notes
2006-07-15 00:00:00****** UNSAT *******
  
 1) NOTE: PLEASE SEE VALUE SHALL BE BASED
 ON ALL LABOUR AND MATERIALS WHETHER OR
 NOT ANY MATERIALS ARE OWNER SUPPLIED.
 FBC ADMIN SECT 108.3 AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE THAT PLANS ARE
 REQUIRED TO BE DONE BY A PE.
 FS 471.003.
  
 3) NOTE: PLEASE PROVIDE INFORMATION ON
 WHAT TYPE OF RETAIL STORE THIS SYSTEM
 WILL BE SUPPLYING? IF THIS IS GAS
 STATION FURTHER CONSULTATION WILL BE
 REQUIRED AS AN ATS MAY NOT BE PERMITTED.
 PLEASE INDICAT OF ANY EM DEVICES WILL BE
 RE-FED FROM THIS GEN OR DOES ALL
 EXISTING EM DEVICES CONTAIN BATTERY BACK
 UP.
  
 4) NOTE: PLEASE KNOW, THE A/C HEAT LOADS
 SHALL BE FIGURED AT 100%. PLEASE KNOW,
 LOAD SHEDDING AND TIMED DELAY STARTING
 OF UNITS WILL BE PERMITTED.
 PLEASE ALSO KNOW, ALL CONTINUOUS LOADS
 SHALL BE SHOWN AT 125%. 215.3,230.42 ETC
 702.5, 220.31, 90.4
  
 5) NOTE: PLEASE KNOW, ALL PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF ALL PERSONS RESPONSIBLE FOR DESIGN
 ETC.
 FBC 106.1
  
 6) NOTE: PLEASE BE SURE ALL MANUFACTURES
 SPECS INCLUDE THE MIN CLEARENCES
 REQUIRED BY MANUFACTURE FOR EQUIPMENT.
 110.26,110.3 ETC
  
 7) NOTE: PLEASE INDICATE ON SITE PLAN
 WHERE THE NEW MAIN, ATS ETC WILL BE
 LOCATED.
 NEED TO VERIFY GROUPING OF DISCONNECTS
 PER 225.34,230.72 ETC.
  
 8) NOTE: PLEASE CLARIFY WHICH DISCONNECT
 WILL FEED THE 400A ATS, AS BOTH 400A
 MAINS CAN NOT FEED ONE 400A ATS, AS THE
 ATS IS NOT RATED FOR 800A'S.PLEASE
 REVISE RISER, AS SHOWN IS NOT CLEAR WHAT
 IS TAKING PLACE.
 310.16,240.4,215.5, 230.70 ETC.
  
 9) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETS REQUIRED FOR ATS.
 110.3,702.6 ETC.
  
  
 10) NOTE: PLEASE INDICATE THE OCP AT THE
 GEN, AS THE VOLTAGE FOR SERVICE IS NOT
 SHOWN.
 PLEASE HIGH-LIGHT SPECS ALSO.
 106.1.2 FBC ADMIN SECT, 445.13 ETC.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 AS THEY WILL HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 13:50 Sent To  
Notes
2006-07-11 00:00:001. PRODUCT DATA INDICATES THAT THE
 GENERATOR IS PLANNED TO BE NATURAL GAS
 ALTHOUGH THE PLANS ONLY DISPLAYS THE
 GENRATOR NEXT TO BUILDING.
  
 2. HOW IS THE PROPOSED GENRATOR FED WITH
 A GAS SUPPLY AS NONE IS SHOWN ON THE
 SITE PLAN.
  
 3. PLEASE INDICATE ON THE PLANS WHERE
 DOORS, WINDOWS, OR ANY OTHER BUILDING
 OPENINGS ARE PRESENT ON THE ELEVATION
 WHERE THE GENERATOR IS BEING PROPOSED TO
 BE INSTALLED.
  
 4. PLEASE PROVIDE A SURVEY TO DETERMINE
 THE DISTANCE FROM THE GERATOR TO THE
 ADJACENT PROPERTY LINES.
  
 5. THE PLUMBING INSPECTOR WILL NEED TO
 SEE A PIPING LAYOUT AND AND OTHER
 DETAILS ASSOCIATED WITH THE
 INSTALLATION.
  
 6. THE GENERATOR IS TO PROVIDE BACK-UP
 POWER TO WHAT DEVICES OR SYSTEMS. IS THE
 GENERATOR TO SUPPLY BACK-UP POWER TO THE
 RETAIL STORE AND THE FUEL DISPENSING
 PUMPS OR JUST THE FUEL PUMPS. PLEASE
 IDENTIFY EQUIPMENT OR DEVICES.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-08-18 Cont ID  
Sent By pkrauss Date 2006-08-18 Time 15:50 Rev Time 0.00
Received By pkrauss Date 2006-08-18 Time 15:50 Sent To  
Notes
2006-08-18 00:00:00SUBMITTAL DATA ON THE GENERATOR
 INDICATES FUEL SOURCE AS NATURAL GAS, NO
 FUEL OIL PERMIT REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By kstevens Date 2006-08-08 Time 09:53 Rev Time 0.00
Received By kstevens Date 2006-08-08 Time 09:53 Sent To  
Notes
2006-08-08 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED AND
 SHALL BE SUBMITTED WITH GENERATOR
 APPLICATION.
  
 B. THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - IF ADDING TO AN
 EXISTING SYSTEM, PLEASE INDICATE ALL
 PIPE SIZES AND SHOW REQUIREMENTS FROM
 REQUIREMENTS 2, 4, & 5 BELOW.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. NOT USED
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (THIS
 INCLUDES EXISTING SYSTEM IF APPLICABLE).
  
 6. NOT USED
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 (INFORMATION SUBMITTED DOES NOT SHOW
 INSTALLATION INSTRUCTIONS AS FAR AS
 MINIMUM DISTANCE FROM STRUCTURES
 REQUIRED FOR SERVICING ETC.).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 16:00 Rev Time  
Received By pkrauss Date 2006-06-27 Time 08:53 Sent To  
Notes
2006-07-11 00:00:00TO "COMM" BD#22
2006-06-27 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By pkrauss Date 2006-08-18 Time 15:53 Rev Time 0.00
Received By pkrauss Date 2006-08-18 Time 15:38 Sent To  
Notes
2006-08-18 00:00:00DENIED:NATURAL GAS GENERATOR
 1.PLEASE PROVIDE DISTANCES/CLEARANCES
 TO THE BUILDING, PROPERTY LINES, ROOF
 OVERHANG, FRESH AIR INTAKES SUCH AS O.A.
 INTAKES, WINDOWS, DOORS, OR VENTS FROM
 THE GENERATOR EXHAUST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By lfranco Date 2006-07-31 Time 19:05 Rev Time 0.00
Received By lfranco Date 2006-07-31 Time 19:04 Sent To I
Notes
2006-07-31 00:00:00PLANNING AND ZONING DEPARTMENT:FAILED
  
 1. PROVIDE RESPONSES IN WRITING.
  
 2. A MINOR AMENDMENT TO THE IBIS PLANNED
 DEVELOPMENT, MASTER PLAN IS REQUIRED. AN
 APPLICATION WILL NEED TO BE FILED TO THE
 PLANNING AND ZONING DEPARTMENT AND
 APPROVED PRIOR TO SIGN-OFF OF BUILDING
 PERMIT.THE COMMENTS BELOW REFLECT THE
 INFORMATION NEEDED ON SITE PLAN, PRIOR
 TO SUBMITTAL OF THE MINOR AMENDMENT TO
 THE IBIS RESIDENTIAL PLANNED
 DEVELOPMENT.
  
 3. PROVIDE A BETTER DETAIL OF THE AREA
 WHERE THE GENERATOR IS PROPOSED, NOT AN
 ENLARGEMENT.THE SITE PLAN SHALL
 INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF
 WALL/HEDGES AROUND GENERATOR/ FUEL TANK,
 AND SETBACK DISTANCE FROM PROPERTY
 LINE.
  
 4.PURSUANT TO SECTION 94-444(B) OPEN
 SPACE STANDARDS:
 (B) FUEL OR OIL OR PROPANE
 TANKS, GENERATORS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS
 AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL, AN OBSCURING GATE IS REQUIRED
 AS A CONDITION FOR SITE PLAN APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL
 TANK INCLUDING ROOFTOP EXHAUST (TANK, IF
 APPLICABLE AND GENERATOR.
  
 5.PURSUANT TO SECTION 94-305(B)(4)
 SETBACKS
 (B)(4) SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT
 MORE THAN 4 FEET INTO A SETBACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT ME AT THE NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435