| Plan Review Stops For Permit 06061436 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-07-07 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-07-07 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2006-07-07 00:00:00 | A COPY OF APPL. GIVEN TO LILI | | | SITE ADDRESS 6707 PAMELA LN WAS EXISTING | | | IN PAPA ; CP HAS BEEN UPDATED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-08-14 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-14 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-08-14 |
Time |
09:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-18 |
Time |
08:40 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-07-18 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2006-07-18 00:00:00 | DENIED | | | | | | SHOW GENERATOR SLAB DETAIL AND METHOD OF | | | ATTACHMENT TO SLAB. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-11 |
Time |
13:24 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-11 |
Time |
13:09 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-07-07 |
Time |
17:53 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-07-07 |
Time |
17:42 |
Sent To |
P |
|
| Notes |
| 2006-07-07 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE MANUFACTURERS | | | SPECIFICATIONS/RECOMMENDATION, REGARDING | | | CLEARANCES. | | | | | | 2} PROVIDE SPECIFICATIONS FOR THE | | | TRANSFER SWITCH. | | | | | | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, GENERATOR, | | | TRANSFER SWITCH, DISCONNECTS AND PANELS, | | | SO THAT COMPLIANCE WITH ARTICLES 225 AND | | | 230 CAN BE REVIEWED. | | | | | | 4} THERE MUST BE A DISCONNECT FROM THE | | | GENERATOR WHERE THE CONDUCTORS ENTER THE | | | BUILDING. DOES THE ATS OR THE NEW PANEL | | | CONTAIN MAIN OCP? | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-11 |
Time |
14:23 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2006-08-11 |
Time |
14:23 |
Sent To |
B |
|
| Notes |
| 2006-08-11 00:00:00 | REFERENCE: GAS PERMIT #06061438 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-07-11 |
Time |
15:43 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2006-07-11 |
Time |
15:43 |
Sent To |
B |
|
| Notes |
| 2006-07-11 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLAN REVIEW FOR A GAS PERMIT: | | | | | | 1. TYPE OF GAS, (LP OR NATURAL) PLEASE | | | INDICATE THIS ON THE DRAWING. | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). PLEASE INDICATE THE GENERATOR | | | BTU LOAD ON DRAWING. | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. PLEASE | | | PROVIDE MANUFACTURE SHEETS FOR THE 1ST | | | AND 2ND STAGE REGULATORS AND INDICATE | | | THEIR LOCATION ON THE ISOMETRIC DRAWING. | | | 4. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). PLEASE INDICATE ON THE | | | SURVEY AND ISOMETRIC DRAWING THE PROPANE | | | TANK SIZE AND IF THE TANK IS ABOVE OR | | | BELOW GROUND. | | | 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | | NAME, AND ALSO DATE DRAWING. PLEASE DO | | | THIS PRIOR TO RESUBMITTING. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-02 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-02 |
Time |
17:21 |
Sent To |
E |
|
| Notes |
| 2006-08-02 00:00:00 | SENT "BT DESK" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-07 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-07 |
Time |
09:18 |
Sent To |
E |
|
| Notes |
| 2006-07-07 00:00:00 | TO "GEN-RES" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-18 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-06-26 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2006-06-26 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-11 |
Time |
09:14 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-07-11 |
Time |
09:14 |
Sent To |
P |
|
| Notes |
| 2006-07-11 00:00:00 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE | | | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | PROVIDE MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AT THE JOBSITE FOR THE | | | FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-05 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-05 |
Time |
12:50 |
Sent To |
I |
|
| Notes |
|
|