Plan Review Details - Permit 06061436
Plan Review Stops For Permit 06061436
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-07 Cont ID  
Sent By lursu Date 2006-07-07 Time 10:46 Rev Time 0.00
Received By lursu Date 2006-07-07 Time 09:17 Sent To  
Notes
2006-07-07 00:00:00A COPY OF APPL. GIVEN TO LILI
 SITE ADDRESS 6707 PAMELA LN WAS EXISTING
 IN PAPA ; CP HAS BEEN UPDATED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By alange Date 2006-08-14 Time 09:17 Rev Time 0.00
Received By alange Date 2006-08-14 Time 09:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By alange Date 2006-07-18 Time 08:40 Rev Time 0.50
Received By alange Date 2006-07-18 Time 08:40 Sent To  
Notes
2006-07-18 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-11 Cont ID  
Sent By btrobaug Date 2006-08-11 Time 13:24 Rev Time 0.50
Received By btrobaug Date 2006-08-11 Time 13:09 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-07 Cont ID  
Sent By btrobaug Date 2006-07-07 Time 17:53 Rev Time 0.50
Received By btrobaug Date 2006-07-07 Time 17:42 Sent To P
Notes
2006-07-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS
 SPECIFICATIONS/RECOMMENDATION, REGARDING
 CLEARANCES.
  
 2} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED.
  
 4} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. DOES THE ATS OR THE NEW PANEL
 CONTAIN MAIN OCP?
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-08-11 Cont ID  
Sent By mperson Date 2006-08-11 Time 14:23 Rev Time 0.45
Received By mperson Date 2006-08-11 Time 14:23 Sent To B
Notes
2006-08-11 00:00:00REFERENCE: GAS PERMIT #06061438

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By mperson Date 2006-07-11 Time 15:43 Rev Time 0.45
Received By mperson Date 2006-07-11 Time 15:43 Sent To B
Notes
2006-07-11 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE THIS ON THE DRAWING.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). PLEASE INDICATE THE GENERATOR
 BTU LOAD ON DRAWING.
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. PLEASE
 PROVIDE MANUFACTURE SHEETS FOR THE 1ST
 AND 2ND STAGE REGULATORS AND INDICATE
 THEIR LOCATION ON THE ISOMETRIC DRAWING.
 4. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H). PLEASE INDICATE ON THE
 SURVEY AND ISOMETRIC DRAWING THE PROPANE
 TANK SIZE AND IF THE TANK IS ABOVE OR
 BELOW GROUND.
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 17:21 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 17:21 Sent To E
Notes
2006-08-02 00:00:00SENT "BT DESK"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 09:18 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 09:18 Sent To E
Notes
2006-07-07 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-18 Cont ID  
Sent By alange Date 2006-07-18 Time 08:46 Rev Time 0.00
Received By alange Date 2006-06-26 Time 14:29 Sent To  
Notes
2006-06-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 09:14 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 09:14 Sent To P
Notes
2006-07-11 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-05 Cont ID  
Sent By mmclean Date 2006-07-05 Time 12:50 Rev Time 0.00
Received By mmclean Date 2006-07-05 Time 12:50 Sent To I
Notes
***NONE***