Plan Review Details - Permit 06061430
Plan Review Stops For Permit 06061430
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-28 Cont ID  
Sent By amorse Date 2006-09-28 Time 14:33 Rev Time 0.00
Received By amorse Date 2006-09-28 Time 14:33 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-11 Cont ID  
Sent By amorse Date 2006-09-11 Time 07:16 Rev Time 0.00
Received By amorse Date 2006-09-11 Time 07:16 Sent To PC
Notes
2006-09-11 00:00:00 
  
 DENIED
  
 3RD REVIEW: THE FOLLOWING ARE THE SAME
 COMMENTS FROM THE 2ND REVIEW OF WHICH
 NONE WERE ADDRESSED
  
 2) PROVIDE PRODUCT APPROVALS FOR NEW
 WINDOW IN BATHROOM, ENTRY DOOR IF
 REPLACED AND WOOD CONNECTORS/TIE DOWNS
 (SCHEDULE LISTING CONNECTORS, FASTENING
 AND FL# WOULD BE ADEQUATE)SEE ATTACHED
 SIMPSON TIE INDEX
  
 3) FLORIDA COVER PAGES FOR PGT FRENCH
 DOORS ARE FOR 2001 CODE CYCLE PLEASE
 UPDATE TO 2004
 ***************************************
 NEW COMMENTS
  
 1) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 2) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 ***NOTE PLEASE BE AWARE THERE ARE NO
 PLUMBING OR MECHANICAL DRAWINGS OR
 CONTRACTORS SIGNED ONAND THEIR ARE
 CHANGES IN THE BATHROOMS THAT WILL
 REQUIRE DRAWINGS AND SEPERATE PERMITS***
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-15 Cont ID  
Sent By amorse Date 2006-08-15 Time 15:27 Rev Time 0.00
Received By amorse Date 2006-08-15 Time 15:27 Sent To PC
Notes
2006-08-15 00:00:00 
  
 DENIED
  
 ****PREVIOUS REVIEW COMMENTS WERE NOT
 ADDRESSED****
  
 2) PROVIDE PRODUCT APPROVALS FOR NEW
 WINDOW IN BATHROOM, ENTRY DOOR IF
 REPLACED AND WOOD CONNECTORS/TIE DOWNS
 (SCHEDULE LISTING CONNECTORS, FASTENING
 AND FL# WOULD BE ADEQUATE)SEE ATTACHED
 SIMPSON TIE INDEX
  
 3) FLORIDA COVER PAGES FOR PGT FRENCH
 DOORS ARE FOR 2001 CODE CYCLE PLEASE
 UPDATE TO 2004
 ***************************************
 NEW COMMENTS
  
 1) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 2) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 ***NOTE PLEASE BE AWARE THERE ARE NO
 PLUMBING OR MECHANICAL DRAWINGS OR
 CONTRACTORS SIGNED ONAND THEIR ARE
 CHANGES IN THE BATHROOMS THAT WILL
 REQUIRE DRAWINGS AND SEPERATE PERMITS***
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By amorse Date 2006-07-19 Time 15:06 Rev Time 1.00
Received By amorse Date 2006-07-19 Time 15:06 Sent To PC
Notes
2006-07-19 00:00:00 
  
 DENIED
  
 1) PROVIDE INFILL DETAIL FOR BLOCK WALL
 AND WOOD FRAME WHERE WINDOWS AND DOORS
 ARE BE REMOVED
  
 2) PROVIDE PRODUCT APPROVALS FOR NEW
 WINDOW IN BATHROOM, ENTRY DOOR IF
 REPLACED AND WOOD CONNECTORS/TIE DOWNS(
 SCHEDULE LISTING CONNECTORS, FASTENING
 AND FL# WOULD BE ADEQUATE)
  
 3) FLORIDA COVER PAGES FOR PGT FRENCH
 DOORS ARE FOR 2001 CODE CYCLE PLEASE
 UPDATE TO 2004
  
 4) WORK TO BE PERFORMED IS A LEVEL 2
 ALTERATION IN THE 2004 EXISTING BLDG
 CODE AND ACCESSABILITY SHALL COMPLY WITH
 THE 2004 FBC, PROVIDE AN ACCESSABLE
 BATHROOM ON GRADE LEVEL WITH A MIN 29"
 CLEAR OPENING PER R322.1.1 FBC
  
 5) PLEASE NOTE THAT ZONING STATES THAT
 ANY WORK PERFORMED ON STAIRWAY OTHER
 THAN DECKING WOULD REQUIRE STAIR TO BE
 REMOVED DUE TO SETBACK INFRINGEMENT
  
 6) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-26 Cont ID  
Sent By dpalmer Date 2006-09-26 Time 12:03 Rev Time 0.00
Received By dpalmer Date 2006-09-26 Time 11:52 Sent To B
Notes
2006-09-26 00:00:00***** NOTES REDLINED**
  
 SD'S ARE BEING SHOWN ON TWO SEPARATE
 CIRCUITS, WHERE THEY ARE REQUIRED TO BE
 WIRED "INLINE" , WHICH WOULD BE ON THE
 SAME CIRCUIT AND ARC FAULT PROTECTED.
  
 ONLY ONE SET BLDG PLANS SUBMITTED,
 HOWEVER SUBMITTED TWO SEPARATE REVISED
 ELECTRICAL SHEETS NOT IN SETS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 12:42 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 12:11 Sent To B
Notes
2006-09-08 00:00:00******** UNSAT 3RD REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH SOME NEW COMMENTS DUE TO CHANGES IN
 PLANS.
 ** PLEASE SEE NOTE BELOW ARE TAKEN
 DRIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED AT THE BOTTOM OF NOTES.
  
  
 1) NOTE: NO, PLEASE SEE NOT OF THIS
 PREVIOUS NOTE WAS ADDRESSED. PLEASE SEE
 NUMEROUS ITEMS ON PANEL SCHEDULE WHICH
 IS NOT IN LOAD CALCULATIONS, PLEASE SEE
 NO LOAD CALCULATION WAS SUBMITTEF RO
 EXISTING LOAD AND NEW INCREASED LOAD ON
 EXISTING SERVICE.
 PLEASE CORRELATE AND ADJUST ALL.
  
 ** PREVIOUS REVIEW NOTE **
  
 PLEASE SUBMIT INFORMATION ON
 LOAD OF EXISTING SERVICE WITH NEW LOADS
 BEING ADDED.220.31B
 PLEASE SHOW AND INDICATE THE EXSTING
 FEEDERS AND OCP FROM THE EXISTING 300A
 PANEL.
 PLEASE CORRELATE PANEL SCHEDULE(S) AND
 RISER DIAGRAM. PLEASE SEE RISER SHOWS
 150A PANEL AND 150A MAIN, YET, PLEASE
 SEE PANEL SHOWS 200A MAIN ON A 150A BUS.
 PLEASE ALSO SEE EXISTING PANEL SCHEDULE.
 240.4,310.16, 215.5, ETC.
  
 2) NOTE: NO, PLEASE SEE NO SWITCH IS
 BEING INDICATED AT THE STAIRS LEADING TO
 FLR ABOVE AS PERVIOUSLY NOTED. PLEASE
 SEE A 4-WAY SWITCH IS BEING SHOWN,
 HOWEVER SWITCHING IS ONLY BEING SHOWN
 FROM TWO LOCATIONS, THER-FORE THIS
 WOULD BE TWO 3-WAYS SWITHCES.
  
 ** PREVIIOUS REVIEW NOTE **
 PLEASE SEE MEANS EGRESS LT
 CONTROL SHOULD BE IN THE IMMEDIATE AREA
 LEADING TO THE FLR ABOVE.
 210.70, LS 101 7.8
  
 3) NOTE: NO, PLEASE SEE THIS IS THE SAME
 ALSO. MAY NOT USE LANSCAPE LTS AS THEY
 ARE NOT ON PLANS SHOWING THE TYPE AND
 LOCATIONS OF FIXTURES. THE LANSCAPE LTS
 ARE NOT INCLUDE IN THE PLANS SUBMITTED.
 A CONTROL AS REQUIRED BY 210.70, LS101
 7.8 IS REQUIRED TO CONTROL A LT LOCATED
 IN THE AREA OF EGRESS. (PORCH, DOOR,
 SCONCE) ETC IN ORDER TO ILLUMINATE
 OUTSIDE THIS DOOR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING CONTROL
 EXITING FROM FIRST FLR TO OUTSIDE.
 MENTIONS "LANSCAPE LTS, HOWEVER PLEASE
 KNOW, THERE SHOULD BE A LT IN THE AREA
 TO LT UP EGRESS.
 210.70
  
 4) NOTE: OK, HOWEVER PLEASE SEE NOW TWO
 SD'S ARE BEING ADDED TO PLANS AT LOWER
 LEVEL IN THE SAME VICINITY WITH
 EACHOTHER?? PLEASE ALSO SEE CIRCUITING
 IS MISSING FOR THESE. PLEASE KNOW, THESE
 WOULD BE REQUIRED TO BE ON AN ARC FAULT
 PROTECTED CIRCUIT PER 210.12.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SD'S INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OR
 ADAPTABLE SLEEPING ROOMS.
 PLEASE SEE THE EXERCISE RM IS CONSIDERED
 AN ADAPTBALE SLEEPING RM. PLEASE SEE
 REDLINED PLANS.
 NFPA-72 11.5.1.1,11.8.3
  
 5) NOTE: OK, SEE NOTE ABOVE FOR SD'S.
  
 6) NOTE: OK.
  
 7) NOTE: NO, PLEASE SEE C-17 AS THIS IS
 AN AREA DETERMINED BY THE NEC IN
 210.52B1 REQUIRED TO BE ON ONE OR MORE
 OF THE SMALL APPLIANCE CIRCUITS OR
 DEDICATED DINING/BRKFAST AREA(S). PLEASE
 SEE THIS AREA REDLINED WOULD REQUIRED
 20A #12.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52B1 FOR DINING
 AREAS AND AREAS OF THE LIKE REQUIRING
 THOSE RECEPTS TO BE ON ONE OR MORE OF
 THE SMALL APPLIANCE CIRCUITS. THIS MAY
 BE MORE THAN THE TWO MIN.
 PLEASE SEE MISSING RECEPT(S) PER 210.52,
 REDLINED.
 PLEASE ALSO SEE REDLINED MISSING RECEPT
 ON 2' OR MORE OF WALL.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE:NO, PLEASE SEE ONLY ONE SHOWS
 THE CORRECT OCP. (2-POLE 30A OCP.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY THE OCP ETC FOR
 THE AHU #1, AS THE 2-POLE 45 SEEMS HIGH
 FOR A 5KW HEAT STRIP.
  
 ** NEW NOTE **
 14) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS FOR DESIGN PROFESSIONALS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 15) NOTE: PLEASE SEE THE FOLLOWING WAS
 NOT DONE. THIS MUST BE DONE OR PLANS MAY
 COME BACK FOR ONLY THIS COMMENT.
 THE PREVIOUS REVIEW REQUESTED THIS BE
 DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-15 Cont ID  
Sent By dpalmer Date 2006-08-15 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2006-08-15 Time 10:44 Sent To B
Notes
2006-08-15 00:00:00******** UNSAT ********
  
 1) NOTE: PLEASE SUBMIT INFORMATION ON
 LOAD OF EXISTING SERVICE WITH NEW LOADS
 BEING ADDED.220.31B
 PLEASE SHOW AND INDICATE THE EXSTING
 FEEDERS AND OCP FROM THE EXISTING 300A
 PANEL.
 PLEASE CORRELATE PANEL SCHEDULE(S) AND
 RISER DIAGRAM. PLEASE SEE RISER SHOWS
 150A PANEL AND 150A MAIN, YET, PLEASE
 SEE PANEL SHOWS 200A MAIN ON A 150A BUS.
 PLEASE ALSO SEE EXISTING PANEL SCHEDULE.
 240.4,310.16, 215.5, ETC.
  
 2) NOTE: PLEASE SEE MEANS EGRESS LT
 CONTROLL SHOUDL BE IN THE IMMEDIATE AREA
 LEADING TO THE FLR ABOVE.
 210.70, LS 101 7.8
  
 3) NOTE: PLEASE SEE MISSING CONTROL
 EXITING FROM FIRST FLR TO OUTSIDE.
 MENTIONS "LANSCAPE LTS, HOWEVER PLEASE
 KNOW, THERE SHOULD BE A LT IN THE AREA
 TO LT UP EGRESS.
 210.70
  
 4) NOTE: PLEASE SEE MISSING SD'S INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OR
 ADAPTABLE SLEEPING ROOMS.
 PLEASE SEE THE EXERCISE RM IS CONSIDERED
 AN ADAPTBALE SLEEPING RM. PLEASE SEE
 REDLINED PLANS.
 NFPA-72 11.5.1.1,11.8.3
  
 5) NOTE: PLEASE SEE CIRCUITING FOR ALL
 "OUTLETS" IN SLEEPING ROOMS OR ADAPTABLE
 SLEEPIGN RMS ARE REQUIED TO HAVE ARC
 FAULT PROTECTION. THIS WOULD BE THE
 UPSTAIRS BEDRM AND THE "EXCERCISE RM.
 PLEASE SEE 2002 NEC210.12B AS SD'S,
 LTS, FANS ETC ARE REQUIRED TO BE
 PROTECTED. PLEASE BE SURE TO ADJUST
 CIRCUTING ON PANEL SCHEDULE AND IDENTIFY
 EACH.
  
 6) NOTE: PLEASE SEE
 210.52B1,210.11C1,220.16 AS THESE
 REQUIRE A MIN OF TWO SAMLL APPLIANCE
 CIRCUITS. PLEASE SEE THE IS CONSIDERED A
 DWELLING AND A KITCHEN BY DEFINITION.
 PLEASE ADJUST PANEL SCHEDULE AND LOAD
 CALCS.
  
 7) NOTE: PLEASE SEE 210.52B1 FOR DINING
 AREAS AND AREAS OF THE LIKE REQUIRING
 THOSE RECEPTS TO BE ON ONE OR MORE OF
 THE SMALL APPLIANCE CIRCUITS. THIS MAY
 BE MORE THAN THE TWO MIN.
 PLEASE SEE MISSING RECEPT(S) PER 210.52,
 REDLINED.
 PLEASE ALSO SEE REDLINED MISSING RECEPT
 ON 2' OR MORE OF WALL.
  
 8) NOTE: PLEASE SEE RISER MENTIONS TO
 CONNECT THE GROUDING ELECTRODE CONDUCTOR
 TO THE EXSITING FOOTER STEEL. PLEASE
 KNOW IN AN EXISTING STRUCTURE OF THE
 AGE, THERE IS A GOOD CHANCE THERE IS NO
 FOOTER STEEL AND THERE WOULD BE MORE
 HARM DONE AFFECTING THE STRUCTURAL
 INTEGRITY OF THE EXSITING FOOTER TRYING
 TO FIND STEEL WHICH MAY NOT BE THERE.
 PLEASE KNOW, THIS MAY BE DONW, HOWEVER
 NOT REQUIRED IN EXISTING BUILDINGS.
 PLEASE REVISE RISER OR IF NOTE STAYS
 THEN THIS WILL BE REQUIRED.
  
 9) NOTE: PLEASE SEE THERE ARE TWO BATH
 #1 CIRCUITS. PLEASE SEE 210.52D,
 210.11C3 AS NO MORE THAN ONE BATHRM MAY
 BE FED.
  
 10) NOTE: PLEASE SEE FIRST FLR BATH, AS
 THERE IS A WALL LT AND RECEPTHOWEVER
 THIS IS NOT CIRCUITED NOR DOES IT SEEM
 IT BELONGN LOCATED THERE NEXT TO THE
 WATER CLOSET.
 PLEASE CLARIFY.
  
 11) NOTE: PLEASE SEE CIRCUITING FOR #14
 MENTIONS OUTSIDE , YET PLANS SHOW THIS
 BEING CIRCUITED INSIDE??
 PLEASE CORRELATE.
  
 12) NOTE: PLEASE SEE MISSING GFI
 RECEPT(S) FRONT AND REAR OF DWELLING AND
 PLEASE SEE MISSING GFI FOR CU.
 210.52E,210.63, 210.8A
  
 13) NOTE: PLEASE VERIFY THE OCP ETC FOR
 THE AHU #1, AS THE 2-POLE 45 SEEMS HIGH
 FOR A 5KW HEAT STRIP.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-05 Cont ID  
Sent By dpalmer Date 2006-07-05 Time 15:59 Rev Time 0.00
Received By dpalmer Date 2006-07-05 Time 15:59 Sent To M
Notes
2006-07-05 00:00:00*********** UNSAT ***********
  
 1) NOTE: PLEASE SEE NO ELECTRICAL
 PLANS/DETAILS SUBMITTED FOR REVIEW WHICH
 IS REQUIRED FOR NEW SCOPE OF WORK AND
 EXISTING TO REMAIN. COMPLIANCE FOR SCOPE
 NEEDS TO BE VERIFIED, SD'S, LTS,
 RECEPTS, ENERGY CALCULATIONS, DEDICATED
 CIRCUITS NEW AND EXISTING, SERVICE ETC
 ETC.
 215.5,FBC 106.1, 106.1.2,106.3.5.1.2 ETC
 ADMIN SECT
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 09:11 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 09:11 Sent To E
Notes
2006-09-19 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-28 Cont ID  
Sent By adarroug Date 2006-08-28 Time 14:44 Rev Time 0.00
Received By adarroug Date 2006-08-28 Time 14:44 Sent To E
Notes
2006-08-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 16:27 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 16:27 Sent To E
Notes
2006-08-12 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-09 Time 11:27 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 11:27 Sent To Z
Notes
2006-08-09 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-05 Cont ID  
Sent By adarroug Date 2006-07-05 Time 11:19 Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 11:19 Sent To E
Notes
2006-07-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-19 Time   Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 15:07 Sent To  
Notes
2006-06-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-07-05 Cont ID  
Sent By tgordon Date 2006-07-05 Time 16:49 Rev Time 0.15
Received By tgordon Date 2006-07-05 Time 16:49 Sent To P
Notes
2006-07-05 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 12:31 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 12:31 Sent To B
Notes
2006-07-08 00:00:00NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-12 Cont ID  
Sent By mmclean Date 2006-08-12 Time 09:12 Rev Time 0.00
Received By mmclean Date 2006-08-12 Time 09:12 Sent To I
Notes
2006-08-12 00:00:00NOTE: NO CHANGE IN THE FOOT-PRINT OF THE
 EXISTING STRUCTURE.ALL PROPOSED WORK
 IS INTERIOR OF STRUCTURE.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-02 Cont ID  
Sent By mmclean Date 2006-07-02 Time 17:49 Rev Time 0.00
Received By mmclean Date 2006-07-02 Time 17:49 Sent To I
Notes
2006-07-02 00:00:00NOTE: NO CHANGE IN THE FOOT-PRINT OF THE
 EXISTING STRUCTURE.ALL PROPOSED WORK
 IS INTERIOR OF STRUCTURE.