Plan Review Details - Permit 06061421
Plan Review Stops For Permit 06061421
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-14 Cont ID  
Sent By alange Date 2006-07-14 Time 10:31 Rev Time 0.33
Received By alange Date 2006-07-14 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-05 Cont ID  
Sent By btrobaug Date 2007-04-05 Time 08:34 Rev Time 0.75
Received By btrobaug Date 2007-04-05 Time 07:34 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-07 Cont ID  
Sent By btrobaug Date 2007-03-07 Time 07:17 Rev Time 0.33
Received By btrobaug Date 2007-03-07 Time 06:58 Sent To PC
Notes
2007-03-07 07:17:54 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. THE CALCULATIONS
 SUBMITTED EXCEED THE GENERATOR OUTPUT, SEE 702.5 2005
 NEC.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMMENDED. 215.5 NEC
  
 3} THE RISER SHOWS A 25 KW GENERATOR, THE SPEC'S FOR A
 20 KW WERE SUBMITTED, PLEASE CORRELATE.
  
 4} PLEASE HI-LITE THE TRANSFER SWITCH INTENDED FOR
 INSTALLATION ON THE SPEC SHEET SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-05 Cont ID  
Sent By btrobaug Date 2007-01-05 Time 17:28 Rev Time 0.33
Received By btrobaug Date 2007-01-05 Time 17:22 Sent To G
Notes
2007-01-05 17:27:54 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON A SITE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION,
 REGARDING CLEARANCES.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-07 Cont ID  
Sent By btrobaug Date 2006-07-07 Time 07:50 Rev Time 0.50
Received By btrobaug Date 2006-07-07 Time 07:26 Sent To P
Notes
2006-07-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON A SITE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 2} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING GROUPED PER 230.72, SEE THAT
 ALLARTICLES FROM 225.31 THROUGH 225.39,
 ARE COMPLIED WITH.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION,
 REGARDING CLEARANCES.
  
 4} HOW IS THE ATS PROTECTED?
  
 5} THE ATS IS POSITIONED AS PART OF THE
 SERVICE EQUIPMENT PER THE RISER DIAGRAM.
 PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-08-07 Cont ID  
Sent By mperson Date 2007-08-07 Time 13:56 Rev Time 0.33
Received By mperson Date 2007-08-07 Time 13:56 Sent To PC
Notes
2007-08-07 14:02:56REVISION: CHANGE LOCATION OF GENERATOR STUBOUT AND
 LONGES RUN CHANGED. REFERENCE GAS PERMIT #06070423.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By mperson Date 2006-07-07 Time 14:34 Rev Time 0.15
Received By mperson Date 2006-07-07 Time 14:34 Sent To M
Notes
2006-07-07 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 09:00 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 09:00 Sent To E
Notes
2007-03-29 09:01:02TO BT'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 11:31 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 11:31 Sent To E
Notes
2007-02-27 11:31:49TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-14 Cont ID  
Sent By adarroug Date 2006-11-14 Time 14:52 Rev Time 0.00
Received By adarroug Date 2006-11-14 Time 14:52 Sent To E
Notes
2006-11-14 14:52:58TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-05 Cont ID  
Sent By adarroug Date 2006-07-05 Time 11:20 Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 11:20 Sent To E
Notes
2006-07-05 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-14 Cont ID  
Sent By alange Date 2006-07-14 Time 10:31 Rev Time 0.00
Received By alange Date 2006-06-26 Time 16:22 Sent To  
Notes
2006-06-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 11:07 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 11:07 Sent To B
Notes
2006-07-11 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-02 Cont ID  
Sent By mmclean Date 2006-07-02 Time 17:47 Rev Time 0.00
Received By mmclean Date 2006-07-02 Time 17:47 Sent To I
Notes
2006-07-02 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 9FT FROM REAR PROPERTY LINE
 AND 1FT FROM THE SIDE SETBACK.


Account Summary | Usage Policy | Privacy Policy