| 2006-07-03 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PLAN REVIEW: |
| | |
| | 1. PER FBC-2004, CHAPTER 1, SECTION 106 |
| | CONSTRUCTION DOCUMENTS: ISOMETRIC |
| | DRAWINGS IN PENCIL ARE UNACCEPTABLE. |
| | PLEASE PRINT NAME ABOVE THE SIGNATURE |
| | AND DATE DRAWING |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (NOTE: THIS INCLUDES THE |
| | EXISTING1-1/4" LINE INDICATED ON THE |
| | DRAWING) |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).(NOTE: THIS INCLUDES THE BTU'S |
| | OF THE EXISTING SYSTEM) |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | (NOTE: THIS INCLUDES THE EXISTING |
| | SYSTEM, LONGEST LENGTH METHOD USED IN |
| | SIZING SYSTEM) |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | PLEASE INDICATE PRESSURE ON THE DRAWING. |
| | 6. PER FBC-2004 FUEL GAS, SEC. 403.4.1: |
| | IRON PIPE SHALL NOT BE USED PLEASE |
| | CHANGE TO STEEL OR GALVANIZED. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. PLEASE SEE CORRECTED DRAWING IN |
| | RED INK FOR REFERENCE FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |