Plan Review Details - Permit 06061379
Plan Review Stops For Permit 06061379
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:26 Rev Time 0.50
Received By alange Date 2006-07-13 Time 08:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By btrobaug Date 2006-08-08 Time 12:42 Rev Time 0.50
Received By btrobaug Date 2006-08-08 Time 12:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-06 Cont ID  
Sent By btrobaug Date 2006-07-06 Time 11:51 Rev Time 1.00
Received By btrobaug Date 2006-07-06 Time 07:46 Sent To P
Notes
2006-07-06 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. INDICATE AIC FOR
 THE ATS.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 3} 110.3(B) INSTALLATION AND USE. LISTED
 OR LABELED EQUIPMENT SHALL BE INSTALLED
 AND USED IN ACCORDANCE WITH ANY
 INSTRUCTIONS INCLUDED IN THE LISTING OR
 LABELING. SUBMIT SPECIFICATIONS
 INDICATING CLEARANCES.
  
 4} THE TRANSFER SWITCH MAY NOT BE ON THE
 LOAD SIDE OF THE SERVICE, SEE 230.82.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By mperson Date 2006-07-07 Time 13:55 Rev Time 0.15
Received By mperson Date 2006-07-07 Time 13:55 Sent To M
Notes
2006-07-07 00:00:00NOTE: REFERENCE GAS PERMIT #06061387

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-06-23 Cont ID  
Sent By ssherman Date 2006-06-23 Time 15:08 Rev Time 0.00
Received By ssherman Date 2006-06-23 Time 15:08 Sent To  
Notes
2006-06-23 00:00:00HISTORICAL APPROVAL PER G JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 14:12 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 14:12 Sent To E
Notes
2006-08-01 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-05 Cont ID  
Sent By adarroug Date 2006-07-05 Time 13:31 Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 13:31 Sent To E
Notes
2006-07-05 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:27 Rev Time 0.00
Received By alange Date 2006-06-25 Time 17:36 Sent To  
Notes
2006-06-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 09:46 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 09:46 Sent To B
Notes
2006-07-11 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-02 Cont ID  
Sent By mmclean Date 2006-07-02 Time 16:32 Rev Time 0.00
Received By mmclean Date 2006-07-02 Time 16:32 Sent To I
Notes
2006-07-02 00:00:00NOTE: THE PROPOSED GENERATOR SHALL NOT
 BE CLOSER THAN 6 FT FROMSIDE PROPERTY
 LINE.