Plan Review Details - Permit 06061341
Plan Review Stops For Permit 06061341
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-04 Cont ID  
Sent By mawillia Date 2006-08-04 Time 10:21 Rev Time 0.00
Received By mawillia Date 2006-08-04 Time 10:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By mwennerg Date 2006-07-21 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2006-07-21 Time 13:39 Sent To  
Notes
2006-07-21 00:00:00***DENIED***
  
 PLEASE SEE MECHANICAL REVIEW COMMENT (1)
 REGARDING TITLE BLOCK REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 09:48 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 09:48 Sent To M
Notes
2006-08-01 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-24 Cont ID  
Sent By pkrauss Date 2006-07-24 Time 10:06 Rev Time 0.00
Received By pkrauss Date 2006-07-24 Time 10:06 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-21 Cont ID  
Sent By mwennerg Date 2006-07-21 Time 13:47 Rev Time 0.00
Received By mwennerg Date 2006-06-25 Time 17:44 Sent To  
Notes
2006-06-25 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 10:06 Rev Time 0.30
Received By tgordon Date 2006-08-04 Time 10:06 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-27 Cont ID  
Sent By tgordon Date 2006-07-27 Time 08:27 Rev Time 0.30
Received By tgordon Date 2006-07-27 Time 08:27 Sent To  
Notes
2006-07-27 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-26-06 NOTE
 #1. THE ENGINEER'S LICENSE NUMBER MUST
 APPEAR IN THE TITLE BLOCK OF EACH PAGE
 OF THE PLANS, PER FAC 61G15-23.002 .
  
 2) EXHAUST FAN IS 2250 CFM'S, SEE 2004
 FBC/M 507.13.2, WHICH WOULD REQUIRE
 3,600 CFM'S EXHAUST, PLEASE CORRECT.
  
 3) SHOW DETAIL OF HOW ANGLE IRON
 SUPPORTS ARE TO BE ANCHORED TO WALL AND
 WILL COMPLY WITH 2004 FBC/M 301.13 WIND
 RESISTANCE 140 MPH.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 10:52 Rev Time 0.30
Received By tgordon Date 2006-06-26 Time 10:52 Sent To FIRE
Notes
2006-06-26 00:00:00*** DENIED ***
 1) THE ENGINEER'S LICENSE NUMBER MUST
 APPEAR IN THE TITLE BLOCK OF EACH PAGE
 OF THE PLANS, PER FAC 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.