Plan Review Details - Permit 06061338
Plan Review Stops For Permit 06061338
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2006-11-07 Cont ID  
Sent By lursu Date 2006-11-07 Time 08:47 Rev Time 0.00
Received By lursu Date 2006-11-07 Time 08:47 Sent To  
Notes
2006-11-07 08:47:51PERMIT ASSIGNE DTO THE CORRECT UNIT : 800

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By lursu Date 2006-06-29 Time 10:16 Rev Time 0.00
Received By lursu Date 2006-06-29 Time 10:16 Sent To  
Notes
2006-06-29 00:00:00EXT #0010 WAS CREATED FOR UNIT 702 UNDER
 THE MAIN PCN = 74434317050010042

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-11-26 Cont ID  
Sent By mjacobs Date 2007-11-26 Time 15:59 Rev Time 0.00
Received By mjacobs Date 2007-11-26 Time 15:16 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-04-04 Cont ID  
Sent By mjacobs Date 2007-04-04 Time 10:19 Rev Time 0.00
Received By mjacobs Date 2007-04-04 Time 09:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-03-31 Cont ID  
Sent By mjacobs Date 2007-03-31 Time 06:43 Rev Time 0.00
Received By mjacobs Date 2007-03-31 Time 05:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-03-19 Cont ID  
Sent By mjacobs Date 2007-03-19 Time 14:42 Rev Time 0.00
Received By mjacobs Date 2007-03-19 Time 11:53 Sent To  
Notes
2007-03-19 14:39:23BUILDING PLAN REVIEW
 PERMIT: 06061338
 ADD: 1401 FORUM PLACE #800
 CONT:AZ BUILDERS INC.
 TEL: (305)986-7035
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 4TH
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FBC 106.1SUBMIT TWO COMPLETE SETS OF DRAWINGS FOR
 PLAN REVIEW.ONLY ONE NEW COMPLETE SET WAS SUBMITTED
 WITH WITH THE OLD SETS.
  
 NOTE: THEISSUES FROM THE PREVIOUS REVIEW WERE
 ADDRESSED, HOWEVER, WE NEED TWO COMPLETE SETS OF PLANS
 FOR REVIEW AND BEFORE A PERMIT CAN BE ISSUED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-02-22 Cont ID  
Sent By mjacobs Date 2007-02-22 Time 10:54 Rev Time 0.00
Received By mjacobs Date 2007-02-22 Time 05:59 Sent To  
Notes
2007-02-22 10:45:22BUILDING PLAN REVIEW
 PERMIT: 06061338
 ADD: 1401 FORUM PL.#800
 CONT:AZ BUILDERS, INC.
 TEL: (561)986-7035
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 4TH
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISION OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. THE DEMOLITION PLAN SHEET A-2
 DOES NOT SHOW A CORRIDOR BETWEEN STAIR #1 AND #2.
 HOWEVER, SHEET A-4 SHOWS AN EXISTING CORRIDOR WITH THE
 WALLS EXISTING.
  
 3)DOOR 'M' ON SHEET A-4 WAS CHANGED TO COMPLY WITH
 SEC. 11-4.13.6, HOWEVER SEE SHEETS A-5 / E-1/ E-2 /
 AC-1 / F-1 WHERE THE SWING OF DOOR 'M' SWINGS IN THE
 OPPOSITE DIRECTION. THE FLOOR LAYOUT ON THESE PAGES
 SHALL MATCH EACH OTHER.
  
 4)F.S.481.221(2)ALL FINAL CONSTRUCTION DOCUMENTS
 AND INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS,
 PLANS, SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY
 THE REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC
 RECORD AND SHALL BEAR THE SIGNATURE AND SEAL OF THE
 REGISTERED ARCHITECT WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE 'DATE' ON WHICH THEY WERE SEALED. THE
 SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE OF THE
 AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. SEE
 SHEETS A-3 AND A-4. WHICH ARE NOT DATED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-08 Cont ID  
Sent By mjacobs Date 2006-12-08 Time 10:00 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 18:09 Sent To  
Notes
2006-12-08 09:53:01BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) SHEET A-3 FBC. 11-4.13.6.MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE 11-25. THE
 MINIMUM CLERANCE ON THE PULL SIDE IS 18 INCHES AND 12
 INCHES ON THE PUSH SIDE. AGAIN SEE FIG. 25 IN CH. 11.
  
 3)AS REQUESTED PREVIOUSLY, SUBMIT A DETAIL ELEVATION
 DRAWING OF THE RECEPTION COUNTER SHOWING HOW IT WILL
 MEET THE REQUIREMENTS OF 11-7 (2) WHICH STATES; "OTHER
 COUNTERS THAT MAY "NOT" HAVE CASH REGISTER BUT AT WHICH
 GOODS OR SERVICES ARE SOLD OR DISTRIBUTED, EITHER ETC.
 THE COUNTER SHALL MEET ONE OF THE REQUIREMENTS OF THIS
 SECTION.
  
 4)AGAIN, THE ENGINEERING INFORMATIONFOR THE
 RREMOVAL OF THE STAIRS REQUIRES AN INDEX SHEET
 REFERENCING ALL TO OTHER PAGES OF THE REPORT OR EACH
 SHEET SHALL HAVE THE ORIGINAL SEAL,SIGNATURE AND DATE
 OF THE ENGINEER, PHOTO COPIES ARE NOT ACCEPTABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-14 Cont ID  
Sent By mjacobs Date 2006-08-14 Time 17:19 Rev Time 0.00
Received By mjacobs Date 2006-08-11 Time 16:47 Sent To  
Notes
2006-08-11 00:00:00 
  
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) 61G15-23.002 SEAL, SIGNATURE AND DATE
 SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, REPORTS, FINAL
 BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER'S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID
 REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND
 SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS,
 SPECIFICATIONS,REPORTS, OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE
 SIGNATURE OF THE PROFESSIONAL ENGINEER.
 (2) EACH SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE
 PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET.
 (SEE SHEET A-3)
  
 3) OK.
  
 4) OK. PER SHEET P-4
  
 5) OK.
  
 6) OK.
  
 7) 11-7.2 SALES AND SERVICE COUNTERS ,
 TELLER WINDOWS, INFORMATION COUNTERS.
 (2) AT TICKETING COUNTERS , TELLER
 STATIONS IN A BANK, REGISTRATION
 COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS , AND OTHER
 COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES
 ARE SOLD OR DISTRIBUTED, EITHER:
 (I) A PORTION OF THE MAIN COUNTER WHICH
 IS A MINIMUM OF 36 INCHES (915 MM) IN
 LENGTH SHALL BE PROVIDED WITH A MAXIMUM
 HEIGHT OF 36 INCHES (915 MM);OR
 (II) AN AUXILIARY COUNTER WITH A
 MIXIMUM HEIGHT OF 36" IN CLOSE PROXIMITY
 TO THE MAIN COUNTER SHALL BE
 PROVIDED.SUBMIT A DETAIL ELEVATION
 DRAWING OF THE RECEPTION COUNTER SHOWING
 HOW THE ACCESSIBILITY REQUIREMENTS WILL
 BE MET. ALL BUSINESS AND SHALL MEET THE
 REQUIREMENTS OFSECTION 11-7.
 SUBMIT A DETAIL ELEVATION DRAWING OF THE
 RECEPTION COUNTER SHOWING HOW THE
 COUNTER WILL MEET THE ACCESSIBILITY
 REQUIREMENTS WITHOUT GOING INTO THE WORK
 AREA OF THE RECEPTIONIST.
  
 8)2004 EXISTING BUILDING CODE 605.2 THE
 MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
 EXCEPTIONS:
 1. WHERE THE WORK AREA AND THE MEANS OF
 EGRESS SERVING IT COMPLIES WITH THE
 FLORIDA FIRE PREVENTION CODE .
 2. MEANS OF EGRESS CONFORMING TO THE
 REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING AND THE FLORIDA FIRE
 PREVENTION CODE UNDER WHICH THE BUILDING
 WAS CONSTRUCTED SHALL BE CONSIDERED
 COMPLIANT MEANS OF EGRESS IF, IN THE
 OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO
 LIFE. {EXIT
 STAIRWAYS,CHUTES,JANITORCLOSETS, GUEST
 ROOMS, SERVICE ROOMS, ETC., SHALL NOT
 OPEN INTO THE ELEVATOR LOBBY.[1982
 STANDARD BUILDING CODE SEC.506.6 (1)}
 NOTE: THE MECH.ROOM AND BOTH EXIT
 STAIRWAYS OPEN INTO THE ELEVATOR LOBBY.
 NOTE: THIS BUILDING WAS CONSTRUCTED
 DURING THE 1982 BUILDING CODE PERIOD.
  
 9) OK.
  
 10) OK.
  
 11) THE ENGINEERING INFORMATION FOR THE
 REMOVAL OF THE STAIRS REQUIRES AN INDEX
 SHEET REFERING TO PAGES INCLUDED IN THE
 PACKAGE, OR EACH SHEET SHALL HAVE THE
 ORIGINAL SEAL, SIGNATURE AND DATE OF THE
 ENGINEER. PHOTO COPIES ARE NOT
 ACCEPTABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By mjacobs Date 2006-07-11 Time 13:51 Rev Time 0.00
Received By mjacobs Date 2006-07-10 Time 07:22 Sent To PC
Notes
2006-07-10 00:00:00 
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) 61G15-23.002 SEAL, SIGNATURE AND DATE
 SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, REPORTS, FINAL
 BID DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER'S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID
 REGISTRANT AND BEING FILED FOR
 PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS
 PROVIDED HEREIN SHALL BE ENTERED ON SAID
 PLANS, SPECIFICATIONS,
 REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER.
 (2) EACH SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE
 PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET.
  
 3) NFPA 99C5.1.3.3.2
 DESIGN AND CONSTRUCTION. LOCATIONS FOR
 CENTRAL SUPPLY SYSTEMS AND THE STORAGE
 OF POSITIVE PRESSURE GASES SHALL MEET
 THE FOLLOWING REQUIREMENTS:
 (1)BE CONSTRUCTED WITH ACCESS TO
 MOVE CYLINDERS, EQUIPMENT, AND SO FORTH,
 IN AND OUT OF THE LOCATION ON HAND
 TRUCKS COMPLYING WITH 9.5.3.1.1
 (2)BE SECURED WITH LOCKABLE DOORS OR
 GATES OR OTHERWISE SECURED
 (3)IF OUTDOORS, BE PROVIDED WITH AN
 ENCLOSURE (WALL OR FENCING) CONSTRUCTED
 OF NONCOMBUSTIBLE MATERIALS
 (4)IF INDOORS, BE CONSTRUCTED AND
 USE INTERIOR FINISHES OF NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE MATERIALS SUCH
 THAT ALL WALLS, FLOORS, CEILINGS AND
 DOORS ARE OF A MINIMUM 1-HOUR FIRE
 RESISTANCE RATING
  
 4) CONSTRUCTION. CARTS AND HAND TRUCKS
 FOR CYLINDERS AND CONTAINERS SHALL BE
 APPROPRIATE CONSTRUCTED FOR THE INTENDED
 PURPOSE, BE SELF-SUPPORTING, AND BE
 PROVIDED WITH 9.5.3.1.1 CHAINS OR STAYS
 TO RETAIN CYLINDERS OR CONTAINERS
  
 5) A.5.1.3.3.2 ELECTRIC WIRING AND
 EQUIPMENT IN STORAGE ROOMS FOR OXYGEN
 AND NITROUS OXIDE ARE NOT REQUIRED TO BE
 EXPLOSION PROOF.
  
 6) A.5.1.3.4 SEE FIGURE A.5.1.3.4. A
 FOUR-VALVE BYPASS ARRANGEMENT IS
 ILLUSTRATED. THREE-WAY VALVES ARE
 PERMITTED IN LIEU OF THE FOUR VALVES
 SHOWN.
  
 7) 11-7.2 SALES AND SERVICE COUNTERS ,
 TELLER WINDOWS, INFORMATION COUNTERS.
 (2) AT TICKETING COUNTERS , TELLER
 STATIONS IN A BANK, REGISTRATION
 COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS , AND OTHER
 COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES
 ARE SOLD OR DISTRIBUTED, EITHER:
 (I) A PORTION OF THE MAIN COUNTER WHICH
 IS A MINIMUM OF 36 INCHES (915 MM) IN
 LENGTH SHALL BE PROVIDED WITH A MAXIMUM
 HEIGHT OF 36 INCHES (915 MM);
  
 8)2004 EXISTING BUILDING CODE 605.2 THE
 MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
 EXCEPTIONS:
 1. WHERE THE WORK AREA AND THE MEANS OF
 EGRESS SERVING IT COMPLIES WITH THE
 FLORIDA FIRE PREVENTION CODE .
 2. MEANS OF EGRESS CONFORMING TO THE
 REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING AND THE FLORIDA FIRE
 PREVENTION CODE UNDER WHICH THE BUILDING
 WAS CONSTRUCTED SHALL BE CONSIDERED
 COMPLIANT MEANS OF EGRESS IF, IN THE
 OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO
 LIFE. {EXIT
 STAIRWAYS,CHUTES,JANITORCLOSETS, GUEST
 ROOMS, SERVICE ROOMS, ETC., SHALL NOT
 OPEN INTO THE ELEVATOR LOBBY.1982
 STANDARD BUILDING CODE SEC.506.6 (1)}
  
 9)11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS . MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIGURE 11-25 . THE FLOOR OR GROUND AREA
 WITHIN THE REQUIRED CLEARANCES SHALL BE
 LEVEL AND CLEAR. SEE SHEET A-3 WHERE
 CABINETS ARE INCROUCHING ON THE MINIMUM
 OF 18" ON THE PULL-SIDE OF THE DOORS.
  
 10) SEE FBC SEC.435.3/435.4 AND 435.5
 FOR THE REQUIREMENTS OF RADIATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-09-22 Cont ID  
Sent By btrobaug Date 2007-11-26 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2007-09-22 Time 14:25 Sent To PC
Notes
2007-09-22 14:35:54**REVISED SHEET E1,2,3.
  
 OTHER WORK FOR BASE BUILDING PREVIOUSLY SUBMITTED WILL
 BE UNDER SEPARATE PERMITS.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-08-13 Cont ID  
Sent By dpalmer Date 2007-08-13 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2007-08-13 Time 12:41 Sent To PC
Notes
2007-08-13 12:42:03** REVISION DENIED **
  
  
  
 1) NOTE: PLEASE SEE NEW SHEETS E 1-3 WHICH ARE NOW
 INDICATING SUBSTANTIAL REVISIONS TO THE BUILDING
 ELECTRICAL SERVICE RISER.
 AS THIS SCOPE OF WORK WAS NOT INCLUDED AND IS NOT PART
 OF THE BASE TENANT BUILD OUT, PLEASE SUBMIT THIS SCOPE
 OF WORK UNDER SEPARATE ELECTRICAL PERMIT FOR REVIEW.
 THIS RISER WAS NOT REVIEWED FOR CODE COMPLIANCE.
 FBC 106.1, 106.1.2
  
 2) NOTE: PLEASE SEE THE REVISED E-1 FOR TENANT BUILD
 OUT NEEDS TO INCLUDE ALL CIRCUITING FOR ALL THE NEW
 RECEPTACLES ETC SHOWN. THERE ARE A SUBSTANTIAL AMOUNT
 OF RECEPTACLES WHICH HAVE BEEN ADDED TO CIRCUITS.
 PLEASE SUBMIT REVISED PANEL SCHEDULES ALONG WITH
 REVISED LOAD CALCULATIONS FOR INCREASED LOADS.
 408.4, 220.12, 220.14 ETC.
  
 3) NOTE: PLEASE KNOW AS OF THIS REVIEW THE LOW VOLTAGE
 PERMIT FOR PHONE/DATA HAS BEEN PLACED ON HOLD AS FEES
 ARE OWED FOR INCREASED VALUE. THE VALUE AS STATED ON
 PERMIT APPLICATION DOES NOT ACCURATELY REFLECT THE
 SCOPE OF WORK OF LV CABLING ON PLANS.
 SPOKE TO CONTRACTOR/QUALIFIER AND HE WILL PAY THE FEES
 OWED.
 FBC 108.3
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-03-26 Cont ID  
Sent By dpalmer Date 2007-03-26 Time 19:38 Rev Time 0.00
Received By dpalmer Date 2007-03-26 Time 19:38 Sent To  
Notes
2007-03-26 19:38:40TWO NEW SETS SUBMITTED, STAMPED BOTH NEW SETS. OK.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 14:55 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 14:27 Sent To  
Notes
2007-03-10 15:03:24** UNSAT 6TH REVIEW **
  
 1) NOTE: PLEASE SEE ROOM CL AS THE DOOR WAY/COUNTER FOR
 ACCESS DOES NOT CORRELATE WITH ARCHITECTURAL SHEETS.
  
 2) NOTE: PLEASE SEE ONLY ONE SET OF NEW PLANS/SHEETS
 WERE SUBMITTED. PLEASE KNOW THAT A PHONE CALL WAS
 PLACED TO CONTRACTOR TO INFORM THEM THAT ONLY ONE SET
 OF NEW PLANS WAS SUBMITTED.
 PLEASE KNOW AT THIS TIME PLANS CAN NOT BE STAMPED AND
 PASSED.
  
 ** PLEASE KNOW NOTE #1 CAN BE REDLINED TO BE CORRECTED
 BEFORE ROUGH IF ALL OF THE OTHER COMMENTS FROM OTHER
 TRADES ARE OK AND WHEN TWO SETS OF PLANS ARE
 SUBMITTED.
 PLUMBING REVIEWER CALLED CONTRACTOR AND INFORMED HIM
 THAT ONLY ONE NEW SET WAS SUBMITTED ALONG WITH THE TWO
 OLD SETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE/REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-02-23 Cont ID  
Sent By dpalmer Date 2007-02-23 Time 10:45 Rev Time 0.00
Received By dpalmer Date 2007-02-23 Time 10:45 Sent To  
Notes
2007-02-23 11:37:05*** UNSAT ***
  
 1) NOTE: PLANS WHICH WERE PREVIOUSLY PASSED HAVE NOW
 BEEN "VOIDED". PLEASE CORRELATE ALL FLOOR LAYOUTS AND
 DOORWAY LAYOUTS. PLEASE SEE THE ELECTRICAL SHEETS DO
 NOT WITH ARCHITECTURAL, AND EVEN THE SAME ELECTRICAL
 SHEETS DO NOT MATCH. THIS WAS BROUGHT TO THIS REVIEWERS
 ATTENTION AND ANY STAMPED ELECTRICAL SHEETS AS
 ELECTRICAL COMPLIANCE WAS OK, HAVE NOW BEEN "VOIDED".
 PLEASE SEE SHEET E-3 IS OK, AS IT DOES NOT CONTAIN ANY
 FLOOR/DOOR LAYOUTS ETC.
 PLEASE SEE THE F-1 SHEET HAS NOW ALSO BEEN VOIDED AS
 THEY DOE NOT CORRELATE WITH THE ARCHITECTURAL.
  
  
 PLEASE BE SURE COORDINATION IS DONE FOR ALL TRADES AND
 FOR ALL SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICESDEPARTMENT
 CITY OF WEST PALM BEACH.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2007-02-18 Time 16:16 Sent To  
Notes
2007-02-18 16:16:59PASSED, AND STAMPED ELECTRICAL SHEETS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-20 Cont ID  
Sent By dpalmer Date 2006-11-20 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2006-11-20 Time 18:50 Sent To  
Notes
2006-11-20 19:59:13****** UNSAT 3RD REVIEW *******
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE NO RESPONSE LETTERS WERE SUBMITTED IN
 SETS.
  
  
 1) NOTE:NO, PLEASE SEE NO COMPLIANCE WITH FBC CHAPTER
 13 HAS BEEN ADDRESSED. PLEASE SEE THIS IS A TENANT
 BUILD OUT IN A BUILDING GREATER THAN 5000 SQ FT. THIS
 IS NOT FOR THE REST OF THE BUILDING; IT IS FOR THIS
 TENANT SPACE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1,
 TABLES 415.2.C.1, OR 415.2.B.1.
 NO ENERGY CALCULATIONS, NO PERFORMANCE CALCULATIONS,
 LIGHTING CONTROLS ETC.
 PLEASE SEE THE 2004 FBC. THIS IS NOT UNDER THE 2001
 FBC.
  
  
 ** PREVIOUS REVIEW NOTES FROM REVIEW ONE AND TWO. **
 PLEASE SEE PLANS ARE NOTED AS MEETING THE NEW FLORIDA
 ENERGY CODE; HOWEVER NO ITEMS COULD BE LOCATED ON PLANS
 TO VERIFY THIS.
 PLEASE SEE 2004 FBC
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1.
 PLEASE SEE EXCEPTIONS FOR MEDICAL AREAS FOR PROCEDURES
 ETC.
  
 PLEASE PROVIDE THE TIME OF DAY SCHEDULING, DEVICES,
 DEVICE LOCATIONS, OVER-RIDES AND LOCATIONS. PLEASE
 SPECIFY THE AMOUNT OF TIME (MAX) ON DEVICE(S) USED FOR
 OVER RIDES IN SPACES ETC.
 **PLEASE KNOW THE DEVICE(S) CAN BE LISTED ON THE
 ELECTRICAL DEVICE LEGEND AND NOTED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE SECTION #2/PANEL "B" IS SHOWN AS
 100A'S ON SCHEDULE AND 225A ON RISER. THIS WAS IN
 PREVIOUS REVIEWS HOWEVER PART OF THE CHANGES WERE DONE
 WITH WHITE-OUT ON PLANS. PLEASE KNOW, UNDER NO
 CIRCUMSTANCES MAY WHITE OUT BE PLACED ON PLANS,
 ESPECIALLY PLANS SIGNED, DATED AND SEALED BY AN
 ARCHITECT OR ENGINEER.
  
 3) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH
 "INITIALS", IF INDEED THIS IS THE LEGAL SIGNATURE OF
 THE ENGINEER OF RECORD, PLEASE SUBMIT A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION.
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE. PLEASE BE SURE THE LETTER IS PROPERLY
 NOTARIZED AS REQUIRED PER FLORIDA STATUTES 117.05.
  
 4) NOTE: PLEASE KNOW A 4X FEE HAS NOW BEEN ASSESSED FOR
 THIS SAID PLAN REVIEW AS REQUIRED UNDER THE FS AS
 NOTED. )PLEASE SEE PREVIOUS NOTES GAVE A NOTICE TO
 FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW AT THIS TIME A FEE OF $7,200.00 WILL BE DUE
 BEFORE PLANS CAN BE RESUBMITTED FOR REVIEW. MAY NOT
 SUBMIT UNTIL THIS FEE IS PAID, THIS IS REQUIRED PER THE
 FLORIDA STATUTES AS NOTED. THIS FEE IS NOT TO THE
 CONTRACTOR OR OWNER.
 PLEASE KNOW AT THIS TIME ONE SET OF EACH SUBMITTED
 ELECTRICAL PLANS ARE BEING RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-10 Cont ID  
Sent By dpalmer Date 2006-08-10 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 10:08 Sent To  
Notes
2006-08-10 00:00:00****** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTE BELOW ARE TAKEN DIRECTLY
 FROM THE PREVIOUS REVIEW.
 PLEASE SEE NEW NOTES BELOW ADDED TO THE
 BOTTOM.
  
 1) NOTE: OK, HOWEVER PLEASE SEE NEW
 ENGINEER WHICH IS SIGNED AND SEALED ON
 PLANS IS REQUIRED TO HAVE TITLE BLOCKS
 ON SAID PLANS WITH ALL INFORMATION AS
 SET-FORTH UNDER FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002, FS 471.025.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY SERVICE AS SHOWN
 AS SOME ITEMS ARE SHOWN AS EXISTING AND
 SOME OTHER ITEMS DO NOT INDICATE BEING
 EXISTING. IT IS BEING TAKEN THAT THESE
 ITEMS ARE NEW.
 PLEASE SEE NEW SYSTEMS INVOLVING
 277/480V SYSTEMS SHALL BE SIGNED, DATED
 AND SEALED BY A PE.
 471.003 (2)(H).
  
 2) NOTE: NO, PLEASE SEE AS PLANS SHOWS
 THESE ARE STILL BEING TAPPED CONDUCTORS
 EXCEEDING PERMITTED LENGTHS PER 240.21.
 PLEASE REVISE RISER FOR CODE COMPLIANCE.
 (SUGG: ONE FEEDER TO PANEL W/FEED THRU
 LUGS>) THIS IS ONLY NOTED AS THERE ARE
 MANY SCENERIOS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOWS A GUTTER
 IN THE LOAD SIDE OF THE TRANSFORMER
 WHICH VIOLATES THE NEC 240.21. THIS IS
 SHOWING TAPPED CONDUCTORS BEING FED FROM
 OTHER TAPPED CONDUCTORS. THIS IS NOT
 PERMITTED , AND IF THIS IS EXISTING,
 THIS WILL BE REQUIRED TO BE CORRECTED.
 PLEASE KNOW, THE TAPPED CONDUCTORS ON
 THE SEC SIDE OF THE TRANSFORMER SHALL
 TERMINATE IN A SINGLE MEANS OF OCP WHEN
 USING THE 10FTRULE ETC.
 PLEASE ADJUST RISER.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: NO, PLEASE SEE THE TENANT BUILD
 OUT SPACE IS IN A BUIDLING WHICH IS
 LARGER THAN 5000 SQFT AND WILL REQUIRE
 CONTROLS IN THIS BUILD OUT SPACE. THIS
 COMMENT WAS NOT FOR UPDATING THE REST OF
 THE BUILDING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS ARE NOTED AS
 MEETING THE NEW FLORIDA ENERGY CODE,
 HOWEVER NO ITEMS COULD BE LOCATED ON
 PLANS TO VERIFY THIS.
 PLEASE SEE 2004 FBC
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1.
 PLEASE SEE EXCEPTIONS FOR MEDICAL AREAS
 FOR PROCEDURES ETC.
  
 PLEASE PROVIDE THE TIME OF DAY
 SCHEDULING, DEVICES, DEVICE LOCATIONS,
 OVER-RIDES AND LOCATIONS. PLEASE SPECIFY
 THE AMOUNT OF TIME(MAX) ON DEVICE(S)
 USED FOR OVER RIDES IN SPACES ETC.
 **PLEASE KNOW THE DEVICE(S) CAN BE
 LISTED ON THE ELECTRICAL DEVICE LEGEND
 AND NOTED ACCORDINGLY.
  
 8) NOTE: OK, HOWEVER THIS NOTE WILL
 REMAIN AS NEW EQUIPMENT AND LOCATIONS
 WILL MOST LIKELY CHANGE DUE TO ONE OF
 THE ABOVE COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY LOCATIONS OF ALL
 ELECTRICAL EQUIPMENT, AS PANELS ARE
 SHOWN ON PLANS, HOWEVER NOT CLEAR WHERE TRANSFORMER AND
 TWO OTHER DISCONNECTS
 ARE ??
 215.5,110.26, ETC
  
 9) NOTE: OK.
  
 ***NEW NOTES **
  
 10) NOTE: PLEASE SEE THE ADDRESSING
 REVIEWER HAS ADDED AND EXTENSION AND NEW
 SUITE # OF 702 FOR THIS SPACE. PLEASE
 ADJUST ADDRESS ON TITLE BLOCKS.
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO THE DEISGN PROFESSIONALS
 AND REPEAT COMMENTS.
  
 ** IMPORTANT**
 WHEN AND BEFORE RESUBMITTING PLANS ONCE
 ALL REVIEWS ARE DONE. PLEASE COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT ANY OF THE NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONLY ONE COPY OF THE
 OLD/REMOVED VOIDED SHEETS FOR REFERENCE
 ONLY. THESE WILL BE SEPARATE FROM NEW
 SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-28 Cont ID  
Sent By dpalmer Date 2006-06-28 Time 20:32 Rev Time 0.00
Received By dpalmer Date 2006-06-28 Time 19:06 Sent To  
Notes
2006-06-28 00:00:00****** UNSAT *******
  
 1) NOTE: PLEASE CLARIFY SERVICE AS SHOWN
 AS SOME ITEMS ARE SHOWN AS EXISTING AND
 SOME OTHER ITEMS DO NOT INDICATE BEING
 EXISTING. IT IS BEING TAKEN THAT THESE
 ITEMS ARE NEW.
 PLEASE SEE NEW SYSTEMS INVOLVING
 277/480V SYSTEMS SHALL BE SIGNED, DATED
 AND SEALED BY A PE.
 471.003 (2)(H).
  
 2) NOTE: PLEASE SEE RISER SHOWS A GUTTER
 IN THE LOAD SIDE OF THE TRANSFORMER
 WHICH VIOLATES THE NEC 240.21. THIS IS
 SHOWING TAPPED CONDUCTORS BEING FED FROM
 OTHER TAPPED CONDUCTORS. THIS IS NOT
 PERMITTED , AND IF THIS IS EXISTING,
 THIS WILL BE REQUIRED TO BE CORRECTED.
 PLEASE KNOW, THE TAPPED CONDUCTORS ON
 THE SEC SIDE OF THE TRANSFORMER SHALL
 TERMINATE IN A SINGLE MEANS OF OCP WHEN
 USING THE 10FTRULE ETC.
 PLEASE ADJUST RISER.
  
 3) NOTE: PLEASE INCLUDE ALL EQUIPMENT
 GROUNDING CONDUCTORS AS REQUIRED.
 250.110,250.24B , 250.122
  
 4) NOTE: PLEASE INDICATE THE GROUNDING
 ATTACHEMENT FOR THE TRANSFORMER.
 250.66,250.30, 250.50
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6) NOTE: PLEASE SEE THAT ALL CURRENT
 CODES AS FOLLOWS SHALL BE STATED ON
 PLANS/DESIGN.
 NFPA-70,2002, NFPA-101 2003, NFPA-72
 2002.
  
 7) NOTE: PLEASE SEE PLANS ARE NOTED AS
 MEETING THE NEW FLORIDA ENERGY CODE,
 HOWEVER NO ITEMS COULD BE LOCATED ON
 PLANS TO VERIFY THIS.
 PLEASE SEE 2004 FBC
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1.
 PLEASE SEE EXCEPTIONS FOR MEDICAL AREAS
 FOR PROCEDURES ETC.
  
 PLEASE PROVIDE THE TIME OF DAY
 SCHEDULING, DEVICES, DEVICE LOCATIONS,
 OVER-RIDES AND LOCATIONS. PLEASE SPECIFY
 THE AMOUNT OF TIME(MAX) ON DEVICE(S)
 USED FOR OVER RIDES IN SPACES ETC.
 **PLEASE KNOW THE DEVICE(S) CAN BE
 LISTED ON THE ELECTRICAL DEVICE LEGEND
 AND NOTED ACCORDINGLY.
  
 8) NOTE: PLEASE CLARIFY LOCATIONS OF ALL
 ELECTRICAL EQUIPMENT, AS PANELS ARE
 SHOWN ON PLANS, HOWEVER NOT CLEAR WHERE
 TRANSFORMER AND TWO OTHER DISCONNECTS
 ARE ??
 215.5,110.26, ETC
  
 9) NOTE: PLEASE CLARIFY TITLE BLOCKS ON
 PLANS, AS PLANS INDICATE THE FIRM,
 ARCHITECT ALONG WITH THE SAME FIRM AND
 ARCHITECTS LICENSE NUMBER AND CA #,
 HOWEVER PLEASE SEE TITLE BLOCKS ALSO
 INCLUDE WHAT APPEAR TO BE A NAME OF
 ANOTHER "ARCHITECTURAL FIRM". THESE ARE
 STATED AS "ALIEN ARCHITECTURE"??
 PLEASE CLARIFY, AS THIS DOES NOT SEEM TO
 PART OF THE TITLE BLOCK FOR SAID FIRM
 LISTED??
 FAC 61G1-16.004, FS 481.219
  
 ** IMPORTANT**
 WHEN AND BEFORE RESUBMITTING PLANS ONCE
 ALL REVIEWS ARE DONE. PLEASE COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT ANY OF THE NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONLY ONE COPY OF THE
 OLD/REMOVED VOIDED SHEETS FOR REFERENCE
 ONLY. THESE WILL BE SEPARATE FROM NEW
 SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-04-03 Cont ID  
Sent By mawillia Date 2007-04-03 Time 15:14 Rev Time 0.00
Received By mawillia Date 2007-04-03 Time 14:42 Sent To B
Notes
2007-04-03 15:10:05*****APPROVED*****
  
  
 SHEET F-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-03-23 Cont ID  
Sent By mwennerg Date 2007-03-23 Time 13:46 Rev Time 0.00
Received By mwennerg Date 2007-03-23 Time 13:46 Sent To  
Notes
2007-03-23 13:48:43***DENIED***
  
 1) PLEASE NOTE THAT ONLY (1) COMPLETE SET OF PLANS WERE
 SUBMITTED FOR REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-06 Cont ID  
Sent By mawillia Date 2006-12-06 Time 11:49 Rev Time 0.00
Received By mawillia Date 2006-12-06 Time 11:49 Sent To  
Notes
2006-12-06 11:56:38*****APPROVED*****
  
  
 SHEET F-1 STAMPED AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By mwennerg Date 2006-08-24 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2006-08-24 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By mwennerg Date 2006-07-03 Time 10:50 Rev Time 0.00
Received By mwennerg Date 2006-07-03 Time 10:50 Sent To  
Notes
2006-07-03 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT ANY ELEVATION CHANGE
 IN EXCESS OF 1/4" SHALL COMPLY WITH NFPA
 101, 2003 EDITION SEC. 7.1.6.2.
  
 2) PRESSURIZED GAS CYLINDERS SHALL BE
 SECURED BY APPROVED MEANS. PLEASE SEE
 LARGER CYLINDERS TO BE SECURED WITH
 CHAINS.
  
 3) FLORIDA FIRE PREVENTION CODE TO
 COMPLY WITH 2004 EDITION.
  
 4) PLEASE SEE MECHANICAL PROVISO. IN
 ADDITION TO FAN SHUTDOWN, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM WHEN TIED INTO A FIRE ALARM
 SYSTEM.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 09:19 Rev Time 0.00
Received By btrobaug Date 2007-11-19 Time 09:19 Sent To B
Notes
2007-11-26 13:27:16TO MYRON, ARCHITECTURAL SHEET./WRT.
2007-11-19 09:19:47TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-21 Cont ID  
Sent By adarroug Date 2007-09-21 Time 16:20 Rev Time 0.00
Received By adarroug Date 2007-09-21 Time 16:20 Sent To E
Notes
2007-09-21 16:20:25TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 18:04 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 18:04 Sent To E
Notes
2007-08-06 18:04:30TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 10:05 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 10:05 Sent To M
Notes
2007-08-02 10:06:05TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-26 Cont ID  
Sent By mmiller Date 2007-03-26 Time 18:35 Rev Time 0.00
Received By mmiller Date 2007-03-26 Time 18:35 Sent To  
Notes
2007-03-26 18:36:00SENT TO BOB # 16 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 10:53 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 10:53 Sent To  
Notes
2007-03-10 10:56:38TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 11:53 Sent To  
Notes
2007-02-16 11:53:41TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 17:00 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 17:00 Sent To  
Notes
2006-11-20 16:35:24TO "BOB"#15
2006-11-08 17:01:03WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-24 Cont ID  
Sent By adarroug Date 2006-07-24 Time 13:48 Rev Time 0.00
Received By adarroug Date 2006-07-24 Time 13:48 Sent To  
Notes
2006-08-09 00:00:00TO "BOB"#4
2006-07-24 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-12 Time   Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 11:46 Sent To  
Notes
2006-06-27 00:00:00TO "BOB"#3
2006-06-26 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-08-07 Cont ID  
Sent By tgordon Date 2007-08-07 Time 15:43 Rev Time 0.30
Received By tgordon Date 2007-08-07 Time 15:43 Sent To  
Notes
2007-08-07 15:43:49REVISION TO MECH. PLANS PAGE AC-1.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 16:01 Rev Time 0.30
Received By tgordon Date 2007-03-27 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-03-13 Cont ID  
Sent By tgordon Date 2007-03-13 Time 11:35 Rev Time 0.30
Received By tgordon Date 2007-03-13 Time 11:35 Sent To  
Notes
2007-03-13 11:41:51*** DENIED ***
 1) PLANS PAGE A-4 SHOWS THE WALLS FOR THE CORRIDOR,
 MAIN LAB AND PORCELAIN ROOM TO BE ONE HOUR FIRE RATED
 (WALL SYMBOL LEGEND), SEE PAGE AC-1 ALL THE A/C DUCTS
 THAT PENETRATE THE FIRE RATED WALLS NEED TO COMPLY WITH
 2004 FBC/M 607, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-23 Cont ID  
Sent By tgordon Date 2007-02-23 Time 08:37 Rev Time 0.30
Received By tgordon Date 2007-02-23 Time 08:37 Sent To  
Notes
2007-02-23 09:00:36*** DENIED ***
 1) PLANS PAGE A-4 SHOWS THE WALLS FOR THE MAIN LAB AND
 PORCELAIN ROOM TO BE ONE HOUR FIRE RATED, SEE PAGE AC-1
 ALL THE A/C DUCTS THAT PENETRATE THE FIRE RATED WALLS
 NEED TO COMPLY WITH 2004 FBC/M 607, PLEASE CORRECT.
  
 2) SEE PAGE AC-1 MECHANICAL ROOM THE 62X12 SUPPLY AIR
 DUCT PENETRATING THE FIRE RATED WALL WILL NEED A FIRE
 DAMPER, SEE 2004 FBC/M 607.5.1,PLEASE CORRECT.
  
 3) SEE PAGES A-3 AND A-4 (ARCHITECT'S SEAL) THE
 ARCHITECT NEED TO PUT THE DATE WHEN HE SIGNED AND
 SEALED THE PLANS, SEE FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-22 Cont ID  
Sent By tgordon Date 2006-11-22 Time 13:56 Rev Time 0.30
Received By tgordon Date 2006-11-22 Time 13:56 Sent To  
Notes
2006-11-22 13:59:22*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #3 REGARDING ENGINEER'S
 SIGNATURE, PLEASE RESPOND.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
2006-11-20 20:02:44NEW SHEETS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By tgordon Date 2006-06-28 Time 16:38 Rev Time 0.45
Received By tgordon Date 2006-06-28 Time 16:38 Sent To  
Notes
2006-06-28 00:00:00*** PROVISO ***
 1) SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop MEDGAS MEDICAL GAS
Rev No 6 Status P Date 2007-03-31 Cont ID  
Sent By jleech Date 2007-03-31 Time 08:55 Rev Time 0.00
Received By jleech Date 2007-03-31 Time 08:55 Sent To  
Notes
2007-03-31 08:58:36COPY OFINSTALLERS LICENSE REQUIRED WITH APPLICATION

Review Stop MEDGAS MEDICAL GAS
Rev No 5 Status F Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 14:06 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 14:06 Sent To  
Notes
2007-03-10 14:07:17ONLY ONE SET OF PLANS. PLUMBING OK WILL PASS WHEN
 SECOND SET SUBMITED.

Review Stop MEDGAS MEDICAL GAS
Rev No 4 Status F Date 2007-02-28 Cont ID  
Sent By jleech Date 2007-02-28 Time 07:09 Rev Time 0.00
Received By jleech Date 2007-02-28 Time 07:09 Sent To  
Notes
2007-02-28 07:15:42DENIED;
 1. SHEET A-2 DEMO PAGE IS MISSING FROM ONE SET OF
 PLANS.
 2. ALL PAGES ARE TO BE SIGNED AND DATED.
 MED-GAS OK BUT CANNOT BE STAMPED AND SIGNED
 AT THIS TIME.
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status F Date 2006-11-21 Cont ID  
Sent By jleech Date 2006-11-21 Time 13:57 Rev Time 0.00
Received By jleech Date 2006-11-21 Time 13:57 Sent To  
Notes
2006-11-21 14:02:02DENIED;
  
 THE MED-GAS PAGES ARE REQUIRED TO BE SEALED BY A
 REGISTERED ENGINEER SEE FBC-2004 CHAPTER 1
 ADMINISTRATION WEST PALM BEACH
 AMENDMENTS.
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2006-08-26 Cont ID  
Sent By jleech Date 2006-08-26 Time 06:54 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 06:54 Sent To  
Notes
2006-08-26 00:00:00DENIED;
 1. PAGE P-4 NOT SEALED OR SIGNED.
 2. PAGE A-3 (OXYGEN CLOSET) REMOVE THE
 NOTATION FOR NITROUS OXIDE. (N2O)
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2006-06-30 Cont ID  
Sent By jleech Date 2006-06-30 Time 08:30 Rev Time 0.00
Received By jleech Date 2006-06-30 Time 08:30 Sent To  
Notes
2006-06-30 00:00:00DENIED;
 1.ADD TO NOTES; OXYGEN, COMPRESSED AIR ,
 AND VACUUM PIPING TO BE INSTALLED BY A
 CERTIFIED MED-GAS CONTRACTOR. SEPARATE
 PERMIT REQUIRED.
 2.PAGE P-3 OXYGEN PIPING DIAGRAM; SHOW
 PIPE SIZE, MATERIAL, AND HOW JOINTS ARE
 TO BE DONE. ALSO SHOW ALL SHUTOFF VALVES
 AND ALARMS REQUIRED.
 3.SHOW DETAIL OR LIST EQUIPMENT TO BE
 USED TO SECURE OXYGENT TANKS.
 4.LEVEL 3 VACUUM; SHOW CHECK VALVE
 REQUIRED SEC. 5.3.3.6.3.2(1) AND A NOTE
 REQUIRING A DEEP SEAL TRAP SEC.
 5.3.3.6.3.2(2).
 5 ADD TO PLANS, EXHAUST FROM VACUUM
 SYSTEM TO BE SCREENED SEC. 5.3.3.6.4.6.
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-03-31 Cont ID  
Sent By jleech Date 2007-03-31 Time 08:59 Rev Time 0.00
Received By jleech Date 2007-03-31 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 14:03 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 14:03 Sent To  
Notes
2007-03-10 14:05:38ONLY ONE SET OF PLANS SUBMITED. MED-GAS OK NEED 2ND SET
 BEFORE APPROVAL.

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-02-28 Cont ID  
Sent By jleech Date 2007-02-28 Time 07:16 Rev Time 0.00
Received By jleech Date 2007-02-28 Time 07:16 Sent To  
Notes
2007-02-28 07:22:18DENIED;
 1.DEMO PAGE MISSING FROM ONE SET OF PLANS.
 2.ALL PAGES TO BE SIGNED AND DATED.
 PLUMBING PLAN REVIEW OK BUT CAN NOT BE STAMPED AND
 SIGNED AT THIS TIME.
 ONE SET OF PLANS HAS BEEN RETAINED BY THIS
 OFFICE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-11-21 Cont ID  
Sent By jleech Date 2006-11-21 Time 13:10 Rev Time 0.00
Received By jleech Date 2006-11-21 Time 13:10 Sent To  
Notes
2006-11-21 13:55:22DENIED;
 FBC-2004 , CHAPTER 1, ADMINISTRATION; SECTION
 105.3.1.2(5). THE PLUMBING AND MED-GAS PLANS ARE
 REQUIRED TO BE SEALED BY A REGISERED
 ENGINEER.
 PAGE P-1 SANITARY DESIGN NOTE,SECTION 7.14.4.2,THE
 REGISTERED DESIGN PROFESSIONAL SHALL INDICATE ON THE
 PERMIT APPLICATION
 THAT THE PLUMBING SYSTEM IS AN ALTERNATIVE ENGINEER
 DESIGN. NOT LISTED ON PERMIT APP. 714.4.3NO TECHNICAL
 DATA SUBMITED TO SUBSTANTIATE THE PROPOSED ALTERATIVE
 ENGINEER DESIGN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-26 Cont ID  
Sent By jleech Date 2006-08-26 Time 06:54 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 06:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By jleech Date 2006-06-30 Time 08:22 Rev Time 0.00
Received By jleech Date 2006-06-30 Time 08:22 Sent To PC
Notes
2006-06-30 00:00:00DENIED;
 1. PAGE P-4 WATER HEATER DETAIL; HEATER
 PAN WITH DRAIN REQUIRED FBC-2004
 PLUMBING SEC. 504.7, AND 504.7.1 AND 2.
 THERMAL EXPANTION CONTROL REQUIRED SEC.
 607.3
 2.PAGE P-5 NOTE 33; "CAST IRON IS
 REQUIRED IN THIS STRUCTURE" SHOULD
 VACUUM SYSTEM LINES BE COPPER?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695