| 2006-07-11 00:00:00 | DENIED |
| | |
| | 1) FAC 61G15 REQUIRES THE ENGINEER TO |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE |
| | NUMBER ON EACH SHEET OF PLANS. |
| | |
| | 2) THE CODE EDITION LISTED ON SHEET 7 IS |
| | INCORRECT. PLEASE UPDATE TO 2004 FBC. |
| | |
| | 3) THE DESIGN PARAMETER INFORMATION ON |
| | SHEET 7 IS INCORRECT. |
| | - THE IMPORTANCE FACTOR FOR THESE |
| | STRUCTURES IS .77 |
| | - THE BUILDING CATEGORY IS OPEN. |
| | - THE INTERNAL PRESSURE COEFFICENT FOR |
| | OPEN STRUCTURES IS 0.00. |
| | PLEASE SEE ASCE7-02. |
| | |
| | 4) ON SHEET THERE ARE GENERAL AND |
| | STRUCTURAL NOTES THAT DO NOT APPLY TO |
| | THIS PROJECT. PLEASE REMOVE THOSE THAT |
| | DO NOT APPLY. PLANS ARE REQUIRED TO BE |
| | SPECIFIC TO THE WORK PROPOSED. SEE FBC |
| | 106.1.1 (CITY AMENDMENTS). |
| | |
| | 5)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT PRODUCT APPROVALS FOR THE SIMPSON |
| | CONNECTORS. |
| | |
| | 6) FBC 106.3.3 (CITY AMENDMENTS)REQUIRES |
| | THE PRODUCTS THAT ARE REGULATED BY DCA |
| | RULE 9B-72 TO BE REVIEWED AND APPROVED |
| | IN WRITING BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL. |
| | |
| | 7) SPECIFY THE UNIFORM LIVE LOAD FOR THE |
| | WALKWAYS AND ELEVATED PLAT FORMS. FBC |
| | TABLE 1607.1 REQUIRES A MINIMUM OF |
| | 60 PSF. |
| | |
| | 8) FBC 11-4.8.4 LANDINGS. |
| | RAMPS SHALL HAVE LEVEL LANDINGS AT |
| | BOTTOM AND TOP OF EACH RAMP AND EACH |
| | RAMP RUN. LANDINGS SHALL HAVE THE |
| | FOLLOWING FEATURES: |
| | 2)ALL LANDINGS ON RAMPS SHALL BE |
| | NOT LESS THAN 60 INCHES (1524 MM) CLEAR, |
| | AND THE BOTTOM OF EACH RAMP SHALL HAVE |
| | NOT LESS THAN 72 INCHES (1829 MM) OF |
| | STRAIGHT AND LEVEL CLEARANCE. |
| | |
| | 9) FBC 11-4.9.2 TREADS AND RISERS. |
| | ON ANY GIVEN FLIGHT OF STAIRS, ALL STEPS |
| | SHALL HAVE UNIFORM RISER HEIGHTS AND |
| | UNIFORM TREAD WIDTHS. STAIR TREADS SHALL |
| | BE NO LESS THAN 11 INCHES (280 MM) WIDE, |
| | MEASURED FROM RISER TO RISER. SEE SHEET |
| | 16R. |
| | |
| | 10) FBC 1009.3 STAIR TREADS AND RISERS. |
| | STAIR RISER HEIGHTS SHALL BE 7 INCHES |
| | (178 MM) MAXIMUM AND 4 INCHES (102 MM) |
| | MINIMUM. STAIR TREAD DEPTHS SHALL BE 11 |
| | INCHES (279 MM) MINIMUM. THE RISER |
| | HEIGHT SHALL BE MEASURED VERTICALLY |
| | BETWEEN THE LEADING EDGES OF ADJACENT |
| | TREADS. THE GREATEST RISER HEIGHT WITHIN |
| | ANY FLIGHT OF STAIRS SHALL NOT EXCEED |
| | THE SMALLEST BY MORE THAN 0.375 INCH |
| | (9.5 MM). SEE SHEET 16R. |
| | |
| | 11) FBC11-4.9.4 HANDRAILS. |
| | STAIRWAYS SHALL HAVE HANDRAILS AT BOTH |
| | SIDES OF ALL STAIRS. HANDRAILS SHALL |
| | COMPLY WITH SECTION 11-4.26 AND SHALL |
| | HAVE THE FOLLOWING FEATURES: |
| | |
| | (2)IF HANDRAILS ARE NOT |
| | CONTINUOUS, THEY SHALL EXTEND AT LEAST |
| | 12 INCHES (305 MM) BEYOND THE TOP RISER |
| | AND AT LEAST 12 INCHES (305 MM) PLUS THE |
| | WIDTH OF ONE TREAD BEYOND THE BOTTOM |
| | RISER. AT THE TOP, THE EXTENSION SHALL |
| | BE PARALLEL WITH THE FLOOR OR GROUND |
| | SURFACE. AT THE BOTTOM, THE HANDRAIL |
| | SHALL CONTINUE TO SLOPE FOR A DISTANCE |
| | OF THE WIDTH OF ONE TREAD FROM THE |
| | BOTTOM RISER; THE REMAINDER OF THE |
| | EXTENSION SHALL BE HORIZONTAL [SEE |
| | FIGURE 11-19 (C) AND FIGURE 11-19 (D)]. |
| | HANDRAIL EXTENSIONS SHALL COMPLY WITH |
| | SECTION 11-4.4 . |
| | |
| | (3)THE CLEAR SPACE BETWEEN |
| | HANDRAILS AND WALL SHALL BE 1? INCHES |
| | (38 MM). |
| | |
| | (6)ENDS OF HANDRAILS SHALL BE |
| | EITHER ROUNDED OR RETURNED SMOOTHLY TO |
| | FLOOR, WALL OR POST. |
| | |
| | 12) 11-4.1.2 ACCESSIBLE SITE AND |
| | EXTERIOR FACILITIES: NEW CONSTRUCTION. |
| | THIS EDITION OF THE CODE DOES NOT APPLY |
| | TO BUILDINGS, STRUCTURES, OR FACILITIES |
| | WHICH WERE EITHER UNDER CONSTRUCTION OR |
| | UNDER CONTRACT FOR CONSTRUCTION ON |
| | OCTOBER 1, 1997. |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | STRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE AND BELOW THE OCCUPIABLE |
| | GRADE LEVEL, REGARDLESS OF WHETHER THE |
| | CODE REQUIRES AN ELEVATOR TO BE |
| | INSTALLED IN SUCH BUILDING, STRUCTURE OR |
| | FACILITY, EXCEPT: (1) ELEVATOR PITS, |
| | ELEVATOR PENTHOUSES, MECHANICAL ROOMS, |
| | PIPING OR EQUIPMENT CATWALKS, AND |
| | AUTOMOBILE LUBRICATION AND MAINTENANCE |
| | PITS AND PLATFORMS; (2) UNOCCUPIABLE |
| | SPACES, SUCH AS ROOMS, ENCLOSED SPACES, |
| | AND STORAGE SPACES THAT ARE NOT DESIGNED |
| | FOR HUMAN OCCUPANCY, FOR PUBLIC |
| | ACCOMMODATIONS, OR FOR WORK AREAS; AND |
| | (3) OCCUPIABLE SPACES AND ROOMS THAT ARE |
| | NOT OPEN TO THE PUBLIC AND THAT HOUSE NO |
| | MORE THAN FIVE PERSONS INCLUDING, BUT |
| | NOT LIMITED TO, EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. HOWEVER AS |
| | PROVIDED IN SECTION 553.509, FLORIDA |
| | STATUTES, BUILDINGS, STRUCTURES, AND |
| | FACILITIES MUST, AT A MINIMUM, COMPLY |
| | WITH THE REQUIREMENTS OF THE ADAAG. |
| | THEREFORE, FACILITIES SUBJECT TO THE |
| | ADAAG MAY BE REQUIRED TO PROVIDE |
| | VERTICAL ACCESS TO AREAS OTHERWISE |
| | EXEMPT UNDER SECTION 11-4.1.3 (5) OF |
| | THIS CODE. VERTICAL ACCESSIBILITY IS |
| | REQUIRED FROM THE BOARDWALK TO THE CANOE |
| | LANDING PLATFORM OR DOCK. THIS IS A |
| | FLORIDA SPECIFIC REQUIREMENT AND THE |
| | APPLICANT HAS THE OPTION OF APPLYING TO |
| | THE FLORIDA BUILDING COMMISSION FOR A |
| | WAIVER. |
| | 553.512 MODIFICATIONS AND WAIVERS; |
| | ADVISORY COUNCIL. THE FLORIDA BUILDING |
| | COMMISSION SHALL PROVIDE BY REGULATION |
| | CRITERIA FOR GRANTING INDIVIDUAL |
| | MODIFICATIONS OF, OR EXCEPTIONS FROM, |
| | THE LITERAL REQUIREMENTS OF THIS PART |
| | UPON A DETERMINATION OF UNNECESSARY, |
| | UNREASONABLE, OR EXTREME HARDSHIP, |
| | PROVIDED SUCH WAIVERS SHALL NOT VIOLATE |
| | FEDERAL ACCESSIBILITY LAWS AND |
| | REGULATIONS AND SHALL BE REVIEWED BY THE |
| | ACCESSIBILITY ADVISORY COUNCIL. (SEE |
| | SECTION 553.512, FLORIDA STATUTES). |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |