| 2006-06-28 00:00:00 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE PROVIDE LOAD ON EXISTING |
| | SERVICE W/ NEW LOAD ADDED. PLEASE SEE |
| | THAT ALL CONTINOUS LOADS BE SHOWN AT |
| | 125%, SHOWN FOR LT AND PUMP, HOWEVER |
| | THISIS ALSO REQUIRED FOR HEAT PUMP. |
| | 215.3,230.42,430.32,680.9,220.31, 215.5 |
| | |
| | 2) NOTE: PLEASE SEE NEW 1-1/2 HP PUMP IS |
| | SHOWN WITH THREE #8'S ON PLANS AND ON |
| | "PANEL SCHEDULE" PROVIDED BY THE |
| | ELECTRICAN. PLEASE SEE THE MAX OPC FOR |
| | 1/2 HP PUMP SHALL BE SIZED FROM NEC |
| | 430.31,32,430.148 |
| | PLEASE ALSO SEE 3-#8'S WILL NOT FIT INTO |
| | THIS PUMP, OR RATED FOR CONNECTION TO |
| | 30A OR 20A BRKR. |
| | PLEASE REVISE AND ADJUST CONDUCTOR SIZES |
| | ON PLANS AND SHEET ATTACHED TO PLANS. |
| | |
| | 3) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM EXISTING |
| | SERVICE TO NEW SUB/POOL PANEL. |
| | PLEASE SEE 3-#6'S AND 1-#10 IS BEING |
| | SHOWN IN A 3/4 INCH CONDUIT, YET THIS |
| | CONDUIT IS OVER FILLED BASED ON TABLES |
| | FOR CONDUIT FILL IN CHAPTER 9 |
| | 250.110,250.122,680.6, 680.25B |
| | |
| | *** IMPORTANT** |
| | 4) NOTE: PLEASE SEE ZONING NOTES, AND |
| | PLEASE SEE THAT IT IS KNOWN BY THIS |
| | OFFICE THAT THE EXISTING ELECTRICAL |
| | METER IS BEING MOVED, HOWEVER THE |
| | EXISTING ELECTRICAL SERVICE PANEL IS |
| | REMAINING WHERE IT IS AND DOES NOT MEET |
| | MIN CLEARENCE REQUIREMENTS PER NEC. 680. |
| | PLEASE KNOW, THE EXISTING ELECTRICAL |
| | PANEL MUST BE MOVED. |
| | |
| | ** PLEASE KNOW, EACH PLAN, PANEL |
| | SCHEDULE ETC SHALL BE SPECIFIC IN DESIGN |
| | TO EACH DWELLING/LOCATION AND POOL BEING |
| | DESIGNED. |
| | 106.1.1,1.6.1.2 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |