Plan Review Details - Permit 06061280
Plan Review Stops For Permit 06061280
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-28 Cont ID  
Sent By dpalmer Date 2006-06-28 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2006-06-28 Time 11:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 18:33 Sent To PC
Notes
2006-06-27 00:00:00 
 ** UNSAT **
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE PROVIDE A MAIN
 DISCONNECT OUTSIDE WITH OCP TO MEET
 230.70.
  
 3) NOTE: PLEASE INCLUDE CWP AS PART OF
 THE GE SYSTEM.250.50
  
 4) NOTE: PLEASE INCLUDE THE # OF SEC'S
 AND FEEDERS ON RISER.
  
 5) NOTE: PLEASE INDICATE OF THE PANEL
 INSIDE WILL BE MLO, OR MCB?
  
 6) NOTE: PLEASE ALSO SHOW OR NOTE
 LOCATION OF PANEL IN KITCHEN AS PANEL
 WILL BE REQUIRED TO MEET 110.26, 408.7
 EVEN IF AN EXISTING LOCATION.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-27 Time   Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 13:50 Sent To  
Notes
2006-06-23 00:00:00TO "E" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved