Plan Review Details - Permit 06061271
Plan Review Stops For Permit 06061271
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-03 Cont ID  
Sent By dpalmer Date 2006-07-03 Time 17:28 Rev Time 0.00
Received By dpalmer Date 2006-07-03 Time 17:28 Sent To P
Notes
2006-07-03 00:00:00REDLINED **
  
  
 OVER HEAD TO UNDERGROUND, METER LOCATION
 MOVING , HOWEVER PLANS REDLINED AS THE
 FUTURE POOL IN FOR PERMIT SHALL MEET ALL
 MIN CLEARENCES FROM EXISTING PANEL, OR
 PANEL SHALL BE RELOCATED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 12:09 Sent To PC
Notes
2006-06-27 00:00:00** UNSAT **
  
 1) NOTE: PLEASE PROVIDE AN ELECTRICAL
 RISER DIAGRAM SHOWING THE NEW PROPOSED
 CONDUCTORS FROM METER TO EXISTING MAINS.
 PLEASE INCDICATE IF THE EXISTING MAIN IS
 LOCATED OUTSIDE AND THE SIZE FO THE
 EXISTING OCP AT MAIN.
 PLEASE INCLUDE THE NEW GROUNDING
 ELECTRODE SYSTEM ON RISER. 2-MIN GRND
 RODS, CWP,.
 215.5,250.50,310.16,240.4
  
  
 2) NOTE: PLEASE BE SURE THE RISER
 CONTAINS THE PRINTED NAME AND SIGNATURE
 OF THE PERSONRESPONSIBLE FOR
 PLAN/DESIGN.
 FBC 106.1.2 ADMIN SEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-27 Time   Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 15:20 Sent To  
Notes
2006-06-23 00:00:00TO "E" BOX