Plan Review Details - Permit 06061268
Plan Review Stops For Permit 06061268
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-09 Cont ID  
Sent By jwitmer Date 2007-03-09 Time 08:13 Rev Time 0.55
Received By jwitmer Date 2007-03-09 Time 08:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-08 Cont ID  
Sent By jwitmer Date 2006-11-08 Time 16:00 Rev Time 1.77
Received By jwitmer Date 2006-11-08 Time 16:00 Sent To  
Notes
2006-11-08 16:16:22BUILDING PLAN REVIEW
 PERMIT: 06061268
 ADD: 2201 45TH STREET
 CONT: BATTEN & SHAW
 TEL: (561)292-2400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) THE TITLE PAGE AND "E" SHEETS HAVE RUBBER STAMP
 SIGNATURES .
 MICHAEL R. BISHOP P. E.
 JAMES C. SEABURYIII P. E.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 THE ARCHITECTURAL SHEETS APPEAR TO BE CODE COMPLIANT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By jwitmer Date 2006-08-08 Time 14:27 Rev Time 2.22
Received By jwitmer Date 2006-08-08 Time 14:26 Sent To  
Notes
2006-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061268
 ADD: 2201 45TH STREET
 CONT: BATTEN & SHAW
 TEL: (561)292-2400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 EXISTING BUILDING CODE LEVEL OF
 ALTERATION? LEVEL I, II OR III?
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) ENTERPRISE ELECTRIC LLC, CONTRACTORS
 & ENGINEERS:
 61G15-23.002 P. E.- CERTIFICATE OF AUTHORIZATION.IF
 PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-01 Cont ID  
Sent By dpalmer Date 2008-01-01 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2008-01-01 Time 12:13 Sent To PC
Notes
2008-01-01 12:47:07REV AND SELECTIVE COORIDNATION.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 08:02 Sent To PC
Notes
2007-12-03 08:19:05 
  
  
  
 ** DENIED **
  
 1) NOTE: PLEASE KNOW AS REQUIRED PER FLORIDA STATUTES
 471.025 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002
 ALL SIGNATURES MUST BE ORIGINAL. MAY NOT USE A *RUBBER
 STAMP*.
 THIS COMMENT WAS SPECIFICALLY MADE ON A PREVIOUS REVIEW
 TO THIS SAME ENGINEER.
 THIS OFFICE WILL BE LEFT WITH NO CHOICE TO TURN PLANS
 OVER TO THE FLORIDA BOARD OF ENGINEERS AND PROSECUTING
 ATTORNEY FOR THE BOARD. THIS IS A SECOND AND FINAL
 NOTICE.
  
 2) NOTE: PLEASE SEE FBC 108.3 AS THE SCOPE OF WORK HAS
 INCREASED, PLEASE INCREASE VALUE FOR APPLIED VALUE.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-19 Cont ID  
Sent By dpalmer Date 2007-02-19 Time 09:19 Rev Time 0.00
Received By dpalmer Date 2007-02-19 Time 08:35 Sent To  
Notes
2007-02-19 09:22:16** PRODUCT DATA SUBMITTED DID NOT CONTAIN AN LISTINGS
 FROM A NRTL(NATIONALLY RECOGNIZED TESTING LABORATORY).
 FOUND PRODUCT ONLINE AND FOUND EQUIPMENT TO BE UL
 LISTED. THIS IS TO BE VERIFIED IN FIELD THAT ALL
 EQUIPMENT INSTALLED SHALL CORREALTE AND CONTAIN A
 LISTING FROM A NRTL.
  
 ** VALUE FOR SCOPE OF WORK WAS INCREASED TO $228,988.00
 AND CONTRACTOR WILL OWE $1919.07 BEFORE PERMIT CAN BE
 ISSUED.
  
  
 ELECTRICAL PLANS AND DATA SHEETS SUBMITTED STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 19:31 Sent To  
Notes
2006-10-15 19:55:50******** UNSAT 2ND REVIEW *******
  
 ** PLEASE NOTE(S) FROM PREVIOUS WHICH ARE STILL IN NEED
 OF ADDRESSING AND SOME NEW NOTES DUE TO PLANS
 SUBMITTED.
 NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW
 WITH NEW NOTES ADDED TO LOWER PORTION.
  
 1) NOTE: OK. VERIFIED.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE PLANS DO NOT SEEM TO INDICATE
 ALL ELECTRICAL IN ROOM, LTS ETC. PLEASE SEEMIN SIZE
 OF LOADS FOR CIRCUITS.
 PLEASE SEE NEC 645 FOR ALL REQUIREMENTS. PLEASE ALSO
 SEE NFPA-75 FOR ANY CONSTRUCTION METHODS ALONG WIHT
 MECHNICAL WHERE APPLICABLE).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PLANS AND PLANS
 SEE NFPA-70 645 AND NFPA-75 FOR
 REQUIREMENTS IN "IT" RMS.
 PLEASE PROVIDE COMPLETED INFORMATION FOR
 REVIEW.
  
 4) NOTE:NO, NONE SUBMITTED FOR REVIEW.
 110.3, 90.7
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR NEW EQUIPMENT BEING INSTALLED.
 110.3, 90.7
  
 5) NOTE:NO, NO ADJUSTMENT WAS MADE. PLEASE KNOW, IF
 ONE IS NOT ADJUSTED TO SCOPEOF WORK , ONE WILL BE
 ASSESSED AS REQUIRED UDENR THE FBC AND MARSHALL'S &
 SWIFT GUIDE AS ADOPTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE SHALL INCLUDE
 ALL LABOR AND MATERIRALS, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED. PLEASE
 KNOW, THE VALUE MAY BE ADJUSTED BY THIS
 OFFICE PER MARSHAL'S/ SWIFT GUIDE.
 FBC 108.3 ADMIN SECT.
  
  
 ** NEW NOTE **
  
  
 6) NOTE: PLEASE SEE FAC 61G15-23.002 AND FLORIDA
 STATUES 471.025, AS ALL SIGNATURES BY THE DESIGN
 PROFESSIONALS SHALL BE ORIGINAL. "RUBBER STAMPS" AND/OR
 "PHOTO-COPIED" SIGNATURES WITH A RAISED SEAL DOES NOT
 MAKE THE PLANS/ DOCUMNETS VALID. PLEASE KNOW, AS PLANS
 SUBMITTED DO NOT CONTAIN ORIGINAL SIGNATURE(S) FROM
 MORE THAN ONE DESIGNER INCLUDING COVER SHEET , ONE SET
 OF PLANS ARE BEING RETAINED BY THIS OFFICE AT THIS
 TIME. PLEASE CONTACT THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS OF THERE ARE ANY QUESTIONS, OR THIS OFFICE.
 PLANS MAY BE PROCESSED TO THE BOARD.
 PLEASE ADDRESS.
  
 7) NOTE: PLEASE ALSO SEE FS553.80(2)(B) WITH REPSECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE ON PLANS. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 21:57 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 21:52 Sent To  
Notes
2006-07-07 00:00:00******** UNSAT *******
  
 1) NOTE: PLEASE SEE MISSSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOSCK FOR ENGINEERING
 FIRM AS REQUIRED UNDER FAC 6115-23.002, FS 471.023
 MISSING CERITIFICATE OF AUTHORIZATION #.
  
 2) NOTE: PLEASE SEE SOME SHEETS DID NOT
 SEEM TO PRINT CLEAR WITH ALL
 INFORMATION.
 PLEASE SEE FBC ADMIN SECT 106.1.3
  
 3) NOTE: PLEASE COMPLETE PLANS AND PLANS
 SEE NFPA-70 645 AND NFPA-75 FOR
 REQUIREMENTS IN "IT" RMS.
 PLEASE PROVIDE COMPLETED INFORMATION FOR
 REVIEW.
  
 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR NEW EQUIPMENT BEING INSTALLED.
 110.3
  
 5) NOTE: PLEASE SEE VALUE SHALL INCLUDE
 ALL LABOR AND MATERIRALS, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED. PLEASE
 KNOW, THE VALUE MAY BE ADJUSTED BY THIS
 OFFICE PER MARSHAL'S/ SWIFT GUIDE.
 FBC 108.3 ADMIN SECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 19:30 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 19:30 Sent To  
Notes
2007-02-23 19:32:40*****APPROVED*****
  
 SHEETS E1.0 AND E3.0 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-19 Cont ID  
Sent By mawillia Date 2006-12-19 Time 16:59 Rev Time 0.00
Received By mawillia Date 2006-12-19 Time 16:58 Sent To  
Notes
2006-12-19 17:00:46******APPROVED*****
  
  
 TO BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 09:32 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 09:22 Sent To  
Notes
2006-07-11 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. EXISTING SMOKE DETECTORS SHALL BE A
 MINIMUM OF AT LEAST THREE FEET TO AIR
 CONDITIONER DIFFUSERS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-31 Cont ID  
Sent By spalmer Date 2007-12-31 Time 11:52 Rev Time 0.00
Received By spalmer Date 2007-12-31 Time 11:52 Sent To E
Notes
2007-12-31 11:52:43TO DEWEY PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 11:27 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 11:26 Sent To E
Notes
2007-11-27 11:27:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 10:56 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 10:56 Sent To  
Notes
2007-02-19 07:53:31TO COMM BOARDSPACE #60.
2007-02-08 10:56:58WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 13:58 Sent To  
Notes
2006-10-12 17:44:40TO "COMM" BD#20
2006-09-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By jwitmer Date 2006-08-08 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2006-06-22 Time 15:22 Sent To  
Notes
2006-07-05 00:00:00TO "COMM" BD#26
2006-06-22 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 08:40 Rev Time 0.20
Received By tgordon Date 2007-02-21 Time 08:40 Sent To  
Notes
2007-02-21 08:41:13PLANS RESUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-17 Cont ID  
Sent By tgordon Date 2006-10-17 Time 09:57 Rev Time 0.30
Received By tgordon Date 2006-10-17 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By tgordon Date 2006-07-31 Time 14:39 Rev Time 0.35
Received By tgordon Date 2006-07-31 Time 14:39 Sent To  
Notes
2006-07-31 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE
 CORRECT.
  
 2) SEE PLAN PAGE A1.1 PROPOSED REFLECTED
 CEILING PLAN SUPPLY AIR GRILLS ARE
 SHOWING AS RETURN GRILLS, AND RETURN
 GRILL AS A SUPPLY GRILL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  