| 2006-11-08 16:16:22 | BUILDING PLAN REVIEW | | | PERMIT: 06061268 | | | ADD: 2201 45TH STREET | | | CONT: BATTEN & SHAW | | | TEL: (561)292-2400 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) THE TITLE PAGE AND "E" SHEETS HAVE RUBBER STAMP | | | SIGNATURES . | | | MICHAEL R. BISHOP P. E. | | | JAMES C. SEABURYIII P. E. | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | THE ARCHITECTURAL SHEETS APPEAR TO BE CODE COMPLIANT. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-08 |
Time |
14:27 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-08-08 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06061268 | | | ADD: 2201 45TH STREET | | | CONT: BATTEN & SHAW | | | TEL: (561)292-2400 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD | | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | EXISTING BUILDING CODE LEVEL OF | | | ALTERATION? LEVEL I, II OR III? | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | 4) ENTERPRISE ELECTRIC LLC, CONTRACTORS | | | & ENGINEERS: | | | 61G15-23.002 P. E.- CERTIFICATE OF AUTHORIZATION.IF | | | PRACTICING THROUGH A | | | DULY AUTHORIZED ENGINEERING BUSINESS, | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME AND LICENSE NUMBER, AS WELL AS, | | | THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION | | | NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-01-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-01 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-01 |
Time |
12:13 |
Sent To |
PC |
|
| Notes |
| 2008-01-01 12:47:07 | REV AND SELECTIVE COORIDNATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-03 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-03 |
Time |
08:02 |
Sent To |
PC |
|
| Notes |
| 2007-12-03 08:19:05 | | | | | | | | | | | | | ** DENIED ** | | | | | | 1) NOTE: PLEASE KNOW AS REQUIRED PER FLORIDA STATUTES | | | 471.025 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002 | | | ALL SIGNATURES MUST BE ORIGINAL. MAY NOT USE A *RUBBER | | | STAMP*. | | | THIS COMMENT WAS SPECIFICALLY MADE ON A PREVIOUS REVIEW | | | TO THIS SAME ENGINEER. | | | THIS OFFICE WILL BE LEFT WITH NO CHOICE TO TURN PLANS | | | OVER TO THE FLORIDA BOARD OF ENGINEERS AND PROSECUTING | | | ATTORNEY FOR THE BOARD. THIS IS A SECOND AND FINAL | | | NOTICE. | | | | | | 2) NOTE: PLEASE SEE FBC 108.3 AS THE SCOPE OF WORK HAS | | | INCREASED, PLEASE INCREASE VALUE FOR APPLIED VALUE. | | | | | | *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-02-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-19 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-19 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2007-02-19 09:22:16 | ** PRODUCT DATA SUBMITTED DID NOT CONTAIN AN LISTINGS | | | FROM A NRTL(NATIONALLY RECOGNIZED TESTING LABORATORY). | | | FOUND PRODUCT ONLINE AND FOUND EQUIPMENT TO BE UL | | | LISTED. THIS IS TO BE VERIFIED IN FIELD THAT ALL | | | EQUIPMENT INSTALLED SHALL CORREALTE AND CONTAIN A | | | LISTING FROM A NRTL. | | | | | | ** VALUE FOR SCOPE OF WORK WAS INCREASED TO $228,988.00 | | | AND CONTRACTOR WILL OWE $1919.07 BEFORE PERMIT CAN BE | | | ISSUED. | | | | | | | | | ELECTRICAL PLANS AND DATA SHEETS SUBMITTED STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-10-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-15 |
Time |
19:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-15 |
Time |
19:31 |
Sent To |
|
|
| Notes |
| 2006-10-15 19:55:50 | ******** UNSAT 2ND REVIEW ******* | | | | | | ** PLEASE NOTE(S) FROM PREVIOUS WHICH ARE STILL IN NEED | | | OF ADDRESSING AND SOME NEW NOTES DUE TO PLANS | | | SUBMITTED. | | | NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW | | | WITH NEW NOTES ADDED TO LOWER PORTION. | | | | | | 1) NOTE: OK. VERIFIED. | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: NO, PLEASE SEE PLANS DO NOT SEEM TO INDICATE | | | ALL ELECTRICAL IN ROOM, LTS ETC. PLEASE SEEMIN SIZE | | | OF LOADS FOR CIRCUITS. | | | PLEASE SEE NEC 645 FOR ALL REQUIREMENTS. PLEASE ALSO | | | SEE NFPA-75 FOR ANY CONSTRUCTION METHODS ALONG WIHT | | | MECHNICAL WHERE APPLICABLE). | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE COMPLETE PLANS AND PLANS | | | SEE NFPA-70 645 AND NFPA-75 FOR | | | REQUIREMENTS IN "IT" RMS. | | | PLEASE PROVIDE COMPLETED INFORMATION FOR | | | REVIEW. | | | | | | 4) NOTE:NO, NONE SUBMITTED FOR REVIEW. | | | 110.3, 90.7 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT ALL MANUFACTURES | | | SPECS/CUT SHEETS FOR NEW EQUIPMENT BEING INSTALLED. | | | 110.3, 90.7 | | | | | | 5) NOTE:NO, NO ADJUSTMENT WAS MADE. PLEASE KNOW, IF | | | ONE IS NOT ADJUSTED TO SCOPEOF WORK , ONE WILL BE | | | ASSESSED AS REQUIRED UDENR THE FBC AND MARSHALL'S & | | | SWIFT GUIDE AS ADOPTED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE VALUE SHALL INCLUDE | | | ALL LABOR AND MATERIRALS, EVEN IF ANY | | | EQUIPMENT IS OWNER SUPPLIED. PLEASE | | | KNOW, THE VALUE MAY BE ADJUSTED BY THIS | | | OFFICE PER MARSHAL'S/ SWIFT GUIDE. | | | FBC 108.3 ADMIN SECT. | | | | | | | | | ** NEW NOTE ** | | | | | | | | | 6) NOTE: PLEASE SEE FAC 61G15-23.002 AND FLORIDA | | | STATUES 471.025, AS ALL SIGNATURES BY THE DESIGN | | | PROFESSIONALS SHALL BE ORIGINAL. "RUBBER STAMPS" AND/OR | | | "PHOTO-COPIED" SIGNATURES WITH A RAISED SEAL DOES NOT | | | MAKE THE PLANS/ DOCUMNETS VALID. PLEASE KNOW, AS PLANS | | | SUBMITTED DO NOT CONTAIN ORIGINAL SIGNATURE(S) FROM | | | MORE THAN ONE DESIGNER INCLUDING COVER SHEET , ONE SET | | | OF PLANS ARE BEING RETAINED BY THIS OFFICE AT THIS | | | TIME. PLEASE CONTACT THE FLORIDA BOARD OF PROFESSIONAL | | | ENGINEERS OF THERE ARE ANY QUESTIONS, OR THIS OFFICE. | | | PLANS MAY BE PROCESSED TO THE BOARD. | | | PLEASE ADDRESS. | | | | | | 7) NOTE: PLEASE ALSO SEE FS553.80(2)(B) WITH REPSECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE ON PLANS. THIS IS | | | ONLY A NOTICE GIVEN AT THIS TIME. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-07 |
Time |
21:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-07 |
Time |
21:52 |
Sent To |
|
|
| Notes |
| 2006-07-07 00:00:00 | ******** UNSAT ******* | | | | | | 1) NOTE: PLEASE SEE MISSSING LICENSE | | | INFORMATION REQUIRED ON TITLE BLOSCK FOR ENGINEERING | | | FIRM AS REQUIRED UNDER FAC 6115-23.002, FS 471.023 | | | MISSING CERITIFICATE OF AUTHORIZATION #. | | | | | | 2) NOTE: PLEASE SEE SOME SHEETS DID NOT | | | SEEM TO PRINT CLEAR WITH ALL | | | INFORMATION. | | | PLEASE SEE FBC ADMIN SECT 106.1.3 | | | | | | 3) NOTE: PLEASE COMPLETE PLANS AND PLANS | | | SEE NFPA-70 645 AND NFPA-75 FOR | | | REQUIREMENTS IN "IT" RMS. | | | PLEASE PROVIDE COMPLETED INFORMATION FOR | | | REVIEW. | | | | | | 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES | | | SPECS/CUT SHEETS FOR NEW EQUIPMENT BEING INSTALLED. | | | 110.3 | | | | | | 5) NOTE: PLEASE SEE VALUE SHALL INCLUDE | | | ALL LABOR AND MATERIRALS, EVEN IF ANY | | | EQUIPMENT IS OWNER SUPPLIED. PLEASE | | | KNOW, THE VALUE MAY BE ADJUSTED BY THIS | | | OFFICE PER MARSHAL'S/ SWIFT GUIDE. | | | FBC 108.3 ADMIN SECT. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-23 |
Time |
19:30 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-23 |
Time |
19:30 |
Sent To |
|
|
| Notes |
| 2007-02-23 19:32:40 | *****APPROVED***** | | | | | | SHEETS E1.0 AND E3.0 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-12-19 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-19 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-19 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2006-12-19 17:00:46 | ******APPROVED***** | | | | | | | | | TO BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-07-11 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-07-11 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. EXISTING SMOKE DETECTORS SHALL BE A | | | MINIMUM OF AT LEAST THREE FEET TO AIR | | | CONDITIONER DIFFUSERS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-12-31 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-12-31 |
Time |
11:52 |
Sent To |
E |
|
| Notes |
| 2007-12-31 11:52:43 | TO DEWEY PALMER'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-11-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-27 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-27 |
Time |
11:26 |
Sent To |
E |
|
| Notes |
| 2007-11-27 11:27:24 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-08 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-08 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2007-02-19 07:53:31 | TO COMM BOARDSPACE #60. | | 2007-02-08 10:56:58 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-27 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-27 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2006-10-12 17:44:40 | TO "COMM" BD#20 | | 2006-09-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-08 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2006-06-22 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2006-07-05 00:00:00 | TO "COMM" BD#26 | | 2006-06-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-02-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-21 |
Time |
08:40 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-02-21 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2007-02-21 08:41:13 | PLANS RESUBMITTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-17 |
Time |
09:57 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-17 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-31 |
Time |
14:39 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2006-07-31 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2006-07-31 00:00:00 | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE | | | CORRECT. | | | | | | 2) SEE PLAN PAGE A1.1 PROPOSED REFLECTED | | | CEILING PLAN SUPPLY AIR GRILLS ARE | | | SHOWING AS RETURN GRILLS, AND RETURN | | | GRILL AS A SUPPLY GRILL, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|