Plan Review Details - Permit 06061252
Plan Review Stops For Permit 06061252
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-05-31 Cont ID  
Sent By mjacobs Date 2007-05-31 Time 15:14 Rev Time 0.00
Received By mjacobs Date 2007-05-31 Time 15:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-05-07 Cont ID  
Sent By mjacobs Date 2007-05-07 Time 11:23 Rev Time 0.00
Received By mjacobs Date 2007-05-07 Time 10:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-02 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 18:53 Rev Time 0.00
Received By mjacobs Date 2007-02-02 Time 16:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-29 Cont ID  
Sent By mjacobs Date 2006-12-29 Time 11:21 Rev Time 0.00
Received By mjacobs Date 2006-12-26 Time 16:09 Sent To PC
Notes
2006-12-28 11:38:59BUILDING PLAN REVIEW
 PERMIT:06061252
 ADD:223 MONCEAUX RD
 CONT: GEORGE GRAMMER
 TEL: (561)832-1772
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)OK
  
 2)OK
  
 3)OK.
  
 4)FBC. 1609.1.4 (1) GLAZED OPENINGS LOCATED WITHIN 30
 FEET OF GRADE SHALL MEET THEREQUIREMENTS OF THE
 "LARGE" MISSILE TEST.THE ROLL-UP SHUTTER AND THE
 SH-800 SINGLE HUNG WINDOW PRODUCT APPROVALS SUBMITTED
 ARE FOR OPENINGS LOCATED MORE THAN 30 FEET ABOVE
 GRADE.
  
  
 5) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6)OK.
  
 7)OK.
  
 8)OK.
  
 9)OK.
  
 10) OK
  
 11) OK.
  
 12) OK,
  
 13) OK.
  
 14) OK.
  
 15) OK.
  
 16) OK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-20 Cont ID  
Sent By mjacobs Date 2006-11-20 Time 17:43 Rev Time 0.00
Received By mjacobs Date 2006-11-20 Time 07:31 Sent To PC
Notes
2006-11-20 08:08:24 
 BUILDING PLAN REVIEW
 PERMIT: 06061252
 ADD: 223 MONCEAUX RD
 CONT: OWNER BUILDER
 TEL: (561)832-1772
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)THE NEW SETS OF PLANS NEED TO RE-STAMP BY PALM
 BEACH COUNTY IMPACT FEES DEPT.
  
 2)RADON FEES ARE DUE PER FAC.10D-91IN THE AMOUNT OF
 $12.24
  
 3)OK.
  
 4)THE PRODUCT APPROVALS SUBMITTED FOR THE ROOL-UP
 SHUTTERS AND SINGLE HUNG WINDOWS ARE IN-COMPLETE. THEY
 ARE MISSING THE NOA REPORTS. MISSING FORM THE PACKAGE
 IS REPORTS FOR MULLIONS/ROOFING/GARAGE DOOR / WOOD
 CONNECTORS (A SCHEDULE WITH WOOD CONNECTORS,
 ATTATCHMENTS AND FL# IS ADEQUATE) ONCE AGAIN TWO COPIES
 OF EACH IS REQUIRED FOR PLAN REVIEW.
  
  
 5) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6)OK.
  
 7)OK.
  
 8)OK.
  
 9)OK.
  
 10) WHAT IS THE SIZE OF THE NEW WINDOW @ ROOM #103?
 SUBMIT A DOOR AND WINDOW SCHEDULE INDICATING THE
 DIMENTION OF EACH DOOR AND WINDOW. THIS INFORMATION
 WILL HELP SPEED UP THE PLAN REVIEW PROCESS.
  
 11) OK.
  
 12) OK, BUT WHERE IS THE PRODUCT APPROVAL FOR THE
 SHINGLES.
  
 13) OK.
  
 14) OK.
  
 15) OK.
  
 16) OK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By amorse Date 2006-07-19 Time 13:11 Rev Time 1.50
Received By amorse Date 2006-07-19 Time 13:11 Sent To PC
Notes
2006-07-19 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENCE NUMBER
 ON EACH SHEET THAT BEARS THEIR SEAL PER
 61G15-23.002(2)
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 APPROVALS REQUIRED FOR LINTELS IF USED,
 DOORS, WINDOWS, MULLIONS, ROOFING,
 GARAGE DOORS, STORM SHUTTERS IF IMPACT
 RATED WINDOWS AND DOORS NOT USED AND
 WOOD CONNECTORS (A SCHEDULE WITH WOOD
 CONNECTORS, ATTACHMENTS AND FL# IS
 ADEQUATE)
  
 5) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAS BEEN REVIEWED AND APPROVED BY
 DESIGNER OF RECORD
  
 7) PROVIDE WALL SECTION FROM FOUNDATION
 THROUGH ROOF WITH DETAILS SHOWING
 ROOFING, INSULATION TYPE AND VALUE, WOOD
 CONNECTORS,ETC, PER 106.3.5.4(6) FBC*
  
 8) SHOW,IDENTIFY ACCESSABLE BATHROOM PER
 106.3.5.4(7) AND R322.1.1 FBC
  
 9) PROVIDE SMOKE DETECTORS IN COMPLIANCE
 WITH 904.1 AND 904.2 OF THE 2004
 EXISTING BLDG CODE (SEC. 9, ADDITIONS)
  
 10) PLEASE BE SURE THAT THE NEW WINDOW
 IN BEDROOM #103 MEETS THE EMERGENCY
 EGGRESS REQUIREMENTS OF R310.1 FBC
  
 11) PROVIDE ATTIC ACCESS FOR EACH
 ENCLOSED ROOF AREA PER R807.1 FBC
  
 12) PROVIDE TYPE OF ROOF COVERING
  
 13) PROVIDE LOCATION OF NEW GAS HOT
 WATER HEATER
  
 14) PROVIDE LINTEL OR POURED DOWN DETAIL
 FOR DOORS AND WINDOWS. IF LINTELS
 PROVIDE LINTEL SCHEDULE
  
 15) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 16) PROVIDE A COMPLETED AND NOTORIZED
 OWNER/BUILDER DISCLOSURE STATEMENT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-31 Cont ID  
Sent By dpalmer Date 2007-01-31 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2007-01-31 Time 14:17 Sent To B
Notes
2007-01-31 14:39:17*
2007-01-31 14:35:44GENERATOR SUBMITTALS IN PACKAGE ARE TO BE GIVEN BACK TO
 OWNER AS THE GEN SCOPE OF WORK IS EXISTING.
 THE GENERATOR/ATS IS TO HAVE CONTACTS FOR LOAD SHEDDING
 OF THE HEAT STRIP ON THE AHU AS THE GEN IS NOT RATED
 FOR LOAD OF HEAT ALSO. THIS NOTE WAS HIGH-LIGHTED ON
 PLANS.
  
 PLANS STAMPED AND ROUTED TO BUILDING

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-25 Cont ID  
Sent By dpalmer Date 2006-12-25 Time 09:32 Rev Time 0.00
Received By dpalmer Date 2006-12-24 Time 19:08 Sent To M
Notes
2006-12-25 09:34:59*** UNSET 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE COMMENTS FROM BOTH PREVIOUS
 REVIEWS WHICH STILL ARE IN NEED OF ADDRESSING. PLEASE
 SEE SOME ARE FROM THE FIRST REVIEW AND SOME ARE FROM
 THE SECOND REVIEW AS THE ELECTRICAL RISER HAD
 COMPLETELY CHANGED FROM THE INITIAL REVIEW.
  
 ** PLEASE KNOW THAT THIS REVIEW WILL ALSO BRING NEW
 COMMENTS AS RISER AND SOME INFORMATION HAS CHANGED ONCE
 AGAIN FROM THE PREVIOUS TWO SETS OF PLANS SUBMITTED FOR
 REVIEW. THESE COMMENTS ARE BEING NOTED BACK TO PREVIOUS
 REVIEW IN MOST CASES.
  
 ** PLEASE SEE NOTE BELOW WHICH REFERENCE BACK TO THE
 TWO PREVIOUS REVIEWS AND THE NUMERICAL IDENTIFICATION
 OF EACH NOTE WHICH HAS BEEN REPEATED FORM THE FIRST AND
 SECOND REVIEW. SOME ONLY REFERENCE TO NOTES FROM THE
 SECOND REVIEW AS THE SECOND REVIEW CONTAINED NUMEROUS
 NEW NOTES BASED ON THE CHANGES MADE TO PLANS.
  
 1) NOTE: PLEASE SEE SOME AREAS OF PLANS WHICH ARE
 MISSING RECEPTACLES PER 210.52. THESE WERE REDLINED ON
 BOTH SETS OF THE PREVIOUS SUBMITTED PLANS FOR
 LOCATIONS, HOWEVER NOT ALL OF THOSE REDLINED AREAS WERE
 DONE.
 PLEASE SEE THE 2FT, 6FT, AND 12FT RULE.
 PREVIOUS REVIEW(S)
  
 2) NOTE: PLEASE SEE NOTE #10 FROM THE PREVIOUS TWO
 REVIEWS WHICH SEEMED TO BE ADDRESS BY THE ADDITION OF
 THE SA /SMOKE ALARM DEVICES, HOWEVER SEE SYMBOL LEGEND
 FOR THESE ADDED DEVICES WHICH INDICATES THESE AS WALL
 MOUNTED CLOSET FIXTURES?
 PLEASE CORRELATE SYMBOL LEGEND WITH THE ACTUAL DEVICE
 BEING INSTALLED.
 PREVIOUS REVIEW(S) NOTE #10
  
 3) NOTE: PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON
 PLANS FOR ALL ROOMS.
 FBC 106.1.2. (ON ELECTRICAL SHEETS)
 PREVIOUS REVIEW(S) NOTE #11
  
 4) NOTE: PLEASE SEE CLOSET LIGHTS EVEN AS SHOWN MOUNTED
 ABOVE CLOSET DOORS DO NOT SEEM TO MEET 410.8. PLEASE
 SEE THIS SECTION 410.8 D(1) AS INCANDESCENT FIXTURES
 REQUIRE A GREATER CLEARANCE THAN FLUORESCENT. PLEASE
 SEE SYMBOL LEGEND FOR THIS TYPE OF FIXTURE SHOWS
 INCANDESCENT AND PER SCALE ON PLANS AND THE FIXTURE
 BEING MOUNTED OFF THE WALL WOULD PLACE THESE WITH IN
 12" OF SHELVING.
 PLEASE ALSO SEE SYMBOL LEGEND AND FIXTURE SCHEDULE NEED
 TO CORRELATE. PLEASE SEE THE SAME SYMBOL AS BEING SHOWN
 AS A WALL MOUNTED FIXTURE IS ALSO SHOWN AS CEILING
 MOUNTED.
 PREVIOUS REVIEW(S) NOTE #12
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS FOR SERVICE STILL
 DO NOT INDICATE THE DEDICATED JACUZZI CIRCUIT.
 PLEASE SEE THE LOAD ON PANEL SCHEDULE DOES NOT
 CORRELATE WITH THE KVA SHOWN ON PANEL SCHEDULE.
 PREVIOUS REVIEW(S) NOTE #13
  
 6) NOTE: PLEASE SEE MISSING EITHER EXISTING OR NEW COLD
 WATER PIPE AS PART OF THE GROUNDING ELECTRODE SYSTEM.
 THESE PLANS NOW INDICATE ALL AS EXISTING EXCEPT FOR A
 NEW NOTE FOR THE REQUIRED FOOTER STEEL AND A NEW DETAIL
 FOR STRUCTURAL STEEL COLUMNS.
 (MISSING CWP). 250.50
 PREVIOUS REVIEW(S) NOTE #14
  
 7) NOTE: PLEASE SEE CORRELATE OF THE A/C SYSTEMS IS
 STILL NOT DONE. PLEASE SEE WHAT IS BEING SHOWN IN LOAD
 CALCULATIONS AND THE LOADS ON PANEL SCHEDULES ARE
 DIFFERENT. PLEASE SEE 424.3B FOR MINIMUM SIZING OF THE
 OVER CURRENT PROTECTION DEVICES. PLEASE CORRELATE
 PANELS AS ONE SHOWS 5600 AS EXISTING AND LOAD
 CALCULATIONS INDICATE 11,200 AS EXISTING FOR THE SAME
 UNIT. PLANS SHOW 5KW, PLANS ALSO SHOW THREE CONDENSING
 UNITS?
 PLEASE SEE LOADS FOR THE NEW ARE ALSO NOT BEING DONE ON
 EMERGENCY SUB PANEL CORRECTLY. PLEASE SEE OTHER
 COMMENTS FOR THIS.
 PREVIOUS REVIEW(S) NOTE #16 AND NOTE #36
 FBC 106.1.2 ADMIN SECTION. PLEASE CORRELATE ALL.
  
 8) NOTE: PLEASE SEE 220.31B FOR REQUIRED LOAD
 CALCULATIONS. PLEASE SEE THERE ARE STILL SEVERAL ITEMS
 NOT INCLUDED ON THE MAIN HOUSE LOAD SUMMARY WHICH ARE
 SHOWN ON PANEL SCHEDULES.
 PLEASE SEE MISSING DINING ROOM, JACUZZI, CORRECT A/C
 (?), DISHWASHER, DISPOSAL ETC.
 PLEASE KNOW IT IS REQUIRED TO CONTAIN THE LOAD
 CALCULATIONS FOR EACH PANEL AND THEN THOSE LOADS SHALL
 CORRELATE WITH THE MAIN PANEL SCHEDULE FOR EACH
 INDIVIDUAL LOAD ON EACH PANEL. THE MAIN LOAD SUMMARY
 SHALL INCLUDE ALL LOADS WITH THE PERMITTED DE-RATINGS
 AS PERMITTED PER THE CODE SECTION ABOVE AS GIVEN.
 PLEASE SEE LOADS ON PANELS SHOWN IN KVA DO NOT
 CORRELATE WITH WHAT APPEARS TO BE AMPERAGES?
 PLEASE SEE THE 2002 NEC.
 PREVIOUS REVIEW(S) NOTE #17 AND NOTE #20, #36, #37,
 #40
  
 9) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 WITH
 RESPECT TO DINING ROOM CIRCUIT. PLEASE SEE LOAD
 CALCULATIONS NOTE ABOVE WHICH MENTIONS THIS AS ONE OF
 THE CIRCUITS NOT LISTED.
 PREVIOUS REVIEW(S) NOTE # 19
  
 10) NOTE: PLEASE IDENTIFY ALL SERVICE EQUIPMENT FOR
 WHICH IS EXISTING AND WHICH IS NEW. THE EM PANEL IS NOW
 THE ONLY PANEL WHICH IS DARKENED AS BEING NEW, HOWEVER
 PLEASE SEE AS ATTACHED PLANS AND PERMIT FOR GENERATOR
 PERMIT INDICATES THIS PANEL ALREADY DONE UNDER A
 SEPARATE PERMIT.
 PLEASE IDENTIFY NEW AND EXISTING.
 FBC 106.1.2 ADMIN SECTION.
 PREVIOUS REVIEW(S) NOTE #23 AND #24
  
 11) NOTE: PLEASE SEE MISSING THE CIRCUITING AND ARC
 FAULT PROTECTION INDICATION FOR THE SMOKE ALARMS AS
 REQUIRED PER 210.12.
 PREVIOUS REVIEW(S) NOTE #26 AND #38
  
 12) NOTE: PLEASE KNOW UNTIL A CORRECTED LOAD
 CALCULATION CAN BE SUBMITTED FOR REVIEW, THE SIZE OF
 THE SERVICE, SERVICE ENTRANCE CONDUCTORS, GROUNDING
 ELECTRODE AND OTHER ITEMS CAN NOT BE DONE AT THIS
 TIME.
 PREVIOUS REVIEW NOTE(S). #28, 29, 30, 31, 34ETC.
  
 13) NOTE: PLEASE SEE AHU AND OVER CURRENT PROTECTION IS
 STILL BEING SHOWN IN CLOSET FOR AHU WHICH IS NOT
 PERMITTED.
 PREVIOUS REVIEW NOTE #33
  
 14) NOTE: PLEASE SEE PREVIOUS NOTES ABOVE AND NOTE #35,
 # 37 FROM PREVIOUS REVIEW WHICH REQUESTED FOR
 CORRELATION OF THE EXISTING GENERATOR PERMIT AND PLANS
 WITH THE PLANS CURRENTLY BEING SUBMITTED. PLEASE SEE
 THE LOAD ON THE EMERGENCY PANEL FAR EXCEEDS THAT OF THE
 RATING OF THE GENERATOR. PLEASE SEE AS THE GENERATOR
 RATED LOAD UNDER PROPANE AND NATURAL GAS ARE TWO
 RATINGS. PLEASE SEE THAT IN EITHER CASE, THE LOAD ON
 THE GENERATOR EXCEEDS RATING OF UNIT. PLEASE SEE THE
 CALCULATIONS SUBMITTED UNDER THE GENERATOR PERMIT DOES
 NOT CONTAIN ALL THE LOADS NOW SHOWN ON THIS EM PANEL
 SCHEDULE.
 PLEASE PROVIDE DETAILED LOAD SHEDDING DETAILS FOR SOME
 LOADS WHICH MAY BE REMOVED BY MEANS OF CONTROL DEVICES,
 AND/ OR DELETE LOADS.
 702.5, 220.31
 PLEASE SEE THE CONDUCTORS FROM THE GENERATOR ON THESE
 PLANS DO NOT CORRELATE WITH THE CONDUCTORS ON GENERATOR
 PLANS. THIS UNIT IS NOT RATED FOR 100A'S.
 PLEASE SEE COMMENTS ABOVE WITH RESPECT TO CORRELATION
 OF LOAD CALCULATIONS.
 PLEASE SEE PREVIOUS REVIEW NOTE #35
 ** PLEASE KNOW ON A SIDE NOTE, ALL PLANS, PERMIT AND SO
 FORTH FROM WHAT SHOULD REMAIN ON JOBSITE WAS SUBMITTED
 WITH THIS PERMIT APPLICATION PACKAGE. PLEASE DO NOT
 SUBMIT, AS THESE SHOULD REMAIN IN THE POSSESSION OF THE
 OWNER ON THE PROPERTY AT ALL TIMES. WE CONTAIN RECORDS
 OF THESE AS THIS IS HOW I CAME UP WITH THE COMMENTS FOR
 THE GENERATOR PLANS AND LOADS NOT MATCHING.
  
 15) NOTE: PLEASE SEE ON THE PREVIOUS REVIEW NOTE #42, A
 NOTICE WAS GIVEN TO THE DESIGN PROFESSIONAL WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE WITH
 RESPECT TO FLORIDA STATUTES 553.80(2)(B).
 PLEASE KNOW BASED ON THIS THE THIRD REVIEW WITH SEVERAL
 COMMENTS STILL BEING NOTED FOR THE SAME CODES
 COMPLIANCE ISSUES, THIS OFFICE HAS NOW ASSESSED A 4X
 TIMES FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT
 FEE. THIS FEE OF $2,400.00 IS ASSESSED TO THE DESIGNER
 OF RECORD AND IS NOT THE RESPONSIBILITY OF THE
 OWNER/CONTRACTOR.
 PLEASE KNOW ONE SET OF ELECTRICAL PLANS WILL BE
 RETAINED ONCE AGAIN FOR FILE CREATED.
 PLEASE ALSO KNOW TO DATE NO CONTACT HAS BEEN MADE TO
 THIS REVIEWER FOR ANY QUESTIONS OR COMMENTS REGARDING
 THE TWO PREVIOUS REVIEWS.
 PLEASE KNOW THIS FEE WILL BE REQUIRED TO BE PAID BEFORE
 PLANS CAN BE RESUBMITTED AS REQUIRED UNDER THE FS AS
 NOTED.
  
 16) NOTE: PLEASE SEE AS NOTED AT THE END OF PREVIOUS
 REVIEWS AND ** WITH ** IMPORTANT*, REQUESTED ALL
 OLD/VOIDED SHEETS TO BE REMOVED FROM SETS AND ONLY TO
 INSERT NEW REVISED SHEETS INTO TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 THE ONLY SHEET WHICH SHOULD BE KEPT AND PLACED ON THE
 COVE OF EACH SET FOR REFERENCE SHOULD BE THE SHEET
 CONTAINING THE STAMP FROM PALM BEACH COUNTY FOR IMPACT
 FEES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
2006-12-25 08:07:532006-12-25 08:07:53
 IN PROGRESS
2006-12-24 20:02:382006-12-24 20:02:38
 TO CONTINUE, REVIEW STOPPED. NOTES TO FOLLOW ONCE
 REVIEW IS COMPLETED ON 12/25.
2006-12-24 19:14:04IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-03 Cont ID  
Sent By dpalmer Date 2006-11-03 Time 11:19 Rev Time 0.00
Received By dpalmer Date 2006-11-02 Time 19:15 Sent To M
Notes
2006-11-03 11:19:19********* UNSAT 2ND REVIEW***********
  
  
 ** PLEASE SEE MANY COMMENTS FROM PREVIOUS REVIEW WHICH
 STILL NEED TO BE ADDRESSED AND MANY NEW COMMENTS DUE TO
 COMPLETE CHANGE IN ELECTRICAL RISER DIAGRAM, PANEL
 SCHEDULES AND PLANS SUBMITTED.
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND WHETHER OR NOT THEY WERE ADDRESSED.
 PLEASE SEE COMPLETELY NEW COMMENTS ADDED TO THE BOTTOM
 OF THE REVIEW.
  
 1) NOTE: NO, SAME NOTE, PLEASE SEE ONCE AGAIN REDLINED
 AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING RECEPTS PER 210.52. 2',6' ,12' RULE
 ALL WALL SPACES FOR NEW AREAS AND NEW CONVERTED AREAS
 WHICH USED TO BE THE KITCHEN.
  
 2) NOTE:NO, PLEASE ALSO SEE COMMENTS WITH RESPECT
 CIRCUITING AS SHOWN ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING EITHER EXISTING OR NEW DINING RM
 DEDICATED CIRCUIT REQUIRED. PLEASE SEE 210.52B1,
 210.11C1, 220.16 ON ONE OR MORE OF THE SM APPL
 CIRCUITS.
 ** PLEASE SEE THE DINING ROOM MAY NOT BE CIRCUITED TO
 THE GARAGE AS NOTED ON PANEL SCHEDULE. (THIS WOULD BE
 OK, ONLY FOR LIGHTING CIR).
  
 3) NOTE: NO, PLEASE STILL SEE MOST HAVE BEEN ADDED
 HOWEVER NOT ALL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING GFI RECEPT SPACING ALONG MANY AREAS
 OF THE KITCHEN COUNTER SPACES.
 210.52C1
  
 4) NOTE:OK, NOW SHOWN, HOWEVER SEE NEW COMMENTS WITH
 RESPECT TO THE LOCATION(S) NOT MEETING CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LOCATION OF NEW AHU FOR ADDITION.
 PLEASE SHOW LOCATION AND PLEASE ALSO SEE 440.11 FOR
 MISSING DISCONNECTS FOR BOTH THE AHU AND CU.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE SEE THIS IS THE SAME COMMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING NEW OR EXISTING REAR RECEPT PER
 210.52E (GFI PER 210.8A)
  
 7) NOTE:NO, SAME NOTE.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING GFI RECEPT FOR NEW BATH RM OFF THE
 GARAGE.
 210.52D, 210.11C3
  
 8) NOTE:OK, HOWEVER GFI DESIGNATION IS NOT CLEAR?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY NEW OR EXISTING GARAGE GFI.
 210.52G, 210.8A
  
 9) NOTE:NO, PLEASE SEE NOTE ABOVE FOR MISSING.
  
 ** PREVIOUS REVIEW NOTE A**
 PLEASE SEE MISSING REQUIRED DEDICATED BATH(S) RM
 CIRCUITS(S). 210.52D,210.11C3.
  
 10) NOTE:NO, PLEASE SEE SA DEVICES ARE REQUIRED
 WITHIN 12" OFTHE HIGHEST POINT ON A FLAT CEILING.
 PLEASE SEE MASTER BEDRM. AN EXACT ARCHITECTURAL REVIEW
 OF THETRAY CEILING DETAIL WAS NOT DONE, HOWEVER
 PLEASE BE SURE THIS SA IS EITHER MOVED IN FIELD OR
 NOTED ON PLANS TO MEET 11.8.3 NFPA-72 2002.
 PLEASE SEE NEW NOTE FOR CIRCUITING AND AFCI.
  
 ** PREVIOUS REVIEW NOTE:PLEASE SEE MISSING SMOKE ALARM
 REQUIRED IN NEW AND EXISTING DWELLING PER NFPA-72
 11.5.1.1,11.8.3
 PLEASE SEE THESE SHALL ALL BE HARDWIRED INLINE AND ARC
 FAULT PROTECTED PER
 210.12B
 PLEASE SEE SA IN MASTER BEDRM SHALL BE INSTALLED WITHIN
 3' OF THE HIGHEST POINT OF THE SLOPED CEILING OR 12" OF
 THE FLAT CEILING AREA IF A TRAY/FLAT AREA.
  
 11) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS ON
 PLANS.
 106.1.2 FBC ADMIN SECT.
  
 12) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MIN CLEARANCES DO NOT SEEM TO BE MET FOR
 NEW CLOSET LTS PER 410.8
  
 13) NOTE: OK, HOWEVER SEE COMMENT WITH RESPECT TOP LOAD
 CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS APPEAR TO SHOW A "JACUZZI/SPA TUB" YET
 PANEL SCHEDULE AND LOAD CALCULATIONS DO NOT INDICATE
 EITHER??
 PLEASE ALSO INDICATE THE REQUIRED GFI PROTECTION.
 680.71, 106.1.2 FBC ADMIN SECT.
  
 14) NOTE:NO, PLEASE SEE SYSTEM IS NOT SHOWN AT ALL.
 PLEASE ALSO SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.50, AS THE NEW FOOTER STEEL IS REQUIRED
 TO PART OF THE GROUNDING ELECTRODE SYSTEM.
  
 15) NOTE: NO, PLEASE SEE NEW COMMENTS AS A COMPLETELY
 NEW SERVICE RISER IS NOW SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER INDICATES "CURRENT SERVICE", THIS IS
 TAKEN AS EXISTING SERVICE, YET THE PANEL SCHEDULE IS
 NOTED AS BEING THE "PROPOSED" PANEL?
 IS THIS EXISTING OR NEW?
 PLEASE CLARIFY.
  
 16) NOTE:NO, PLEASE SEE MIN OCP FOR AHU(S) NOT
 CORRECT. PLEASE SEE PREVIOUS REVIEWNOTE AND PLEASE
 SEE NEW NOTES FOR OTHER COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER ONLY SEEMS TO BE SHOWING ONE A/C
 SYSTEM?
 PLEASE ALSO SEE THE FOLLOWING COMMENTS.
 PLEASE SEE NOTE ON PANEL SCHEDULE MENTIONS 1-5KW AND
 1-10KW, HOWEVER PANEL SCHEDULE SHOWS 10KW UNITS.
 PANEL ALSO SHOWS "4-SPACES"??
 PLEASE CLARIFY THIS. PLEASE SEPARATE THESE OF THE
 "4-SPACES" IS FOR TWO SEPARATE A/C AHU'S.
 PLEASE ALSO SEE THAT THE OCP FOR THE AHU'S SHALL BE
 SIZED AT A MIN OF 125%.
 PLEASE SEE AHU'S ARE SHOWN W/ 40A OCP.
 PLEASE SEE 424.3B, 240.4, 310.16, 440.11 ETC.
  
 17) NOTE:NO, NOT DONE. PLEASE SEE CALCULATIONS
 SUBMITTED ARE NOT CODE COMPLIANT.
 THERE ARE FAR TOO MANY INDIVIDUAL ITEMS TO BE MENTIONED
 IN DETAIL FOR COMPLIANCE. PLEASE SEE 220.31B.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.31B, 220.21 FOR MIN LOAD CALCULATIONS
 FOR SERVICE.
 PLEASE ALSO SEE MIN LOADS FOR A/C SYSTEM SHALL BE
 SHOWN. PLEASE SEE THE LARGER OF THE TWO LOADS SHALL BE
 INDICATED IN LOADS CALCS. LOADS SHOWN DO NOT CORRELATE
 WITH EITHER THE NOTE FOR ONE 5KW AND ONE-10KW OR THE
 TWO 10KW UNITS AS NOTED ON PANEL SCHEDULE.
 PLEASE ADJUST AND REVISE CALCULATIONS.
  
 18) NOTE: NO, SAME NOTE **
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LOAD CALCULATIONS MENTIONS 2-RANGES, YET
 PLANS DO NOT CORRELATE WITH THIS?
 PLEASE SEE PLANS INDICATE ONE RANGE AND AN "OVEN"?
 PLEASE SEE PANEL SCHEDULE DOES NOT SHOW OVEN.
 PLEASE VERIFY ALL KW LOADS, OCP AND CIRCUITS.
 408.4, 240.4, 310.16 ETC
  
 19) NOTE: NO, PLEASE SEE MINIMUM OF "2" ARE REQUIRED.
 PLEASE ALSO SEE COMMENTS WITH RESPECT DINING RM
 CIRCUIT(S) FROM PREVIOUS REVIEW. OK, FOR SM APPL ONLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52B1, 210.11C1, 220.16A FOR MIN 1500VA
 FOR SM APPL CIRCUITS.
 (PLANS SHOW 1400).
  
 20) NOTE: NO, SEE OTHER NOTES FOR LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE DEDICATED DISHWASHER IS SHOWN ON LOAD
 CALCS, YET NOT ON PANEL SCHEDULE.
 PLEASE SEE DISPOSAL(S) ON PANEL SCHEDULE, HOWEVER NOT
 IN LOAD CALCS.?
 PLEASE SEE OTHER WHICH ARE NOT LISTED.
 PLEASE BE SURE TO GO THROUGH ALL CIRCUITS ON THE HOUSE
 PANEL NEW AND EXISTING, LIST IN LOAD CALCULATIONS, AND
 SHOW ON PANEL SCHEDULE AND ADJUST LOAD CALCULATIONS
 ACCORDINGLY.
 215.5, 220.31B, ETC.
  
 21) NOTE: OK, HOWEVER AS PANEL SCHEDULE(S) ARE NOT
 COMPLETE ATE THIS TIME, PLEASE BE SURE TO THE SAME WHEN
 OTHER ITEMS ARE ADDED TO PANEL SCHEDULE(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL SCHEDULE SHALL INDICATE ALL CONDUCTOR
 SIZES PER 310.16, 240.4, 215.5, 408.4 ETC
 FBC 106.1.2, ADMIN SECT
  
 22) NOTE: OK. SEE NEW NOTES.
  
 23) NOTE: ? SEE NEW NOTES AS A COMPLETELY NEW RISER WAS
 SUBMITTED AND THIS PREVIOUS NOTE WOULD NO LONGER APPLY.
 NO CONDUCTORS ARE SHOWN?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOWS AN "EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO THE MAIN?? IT IS NOTED THAT
 THIS IS EXISTING; HOWEVER THE #8 SHOULD NOT BE LOCATED
 IN THIS SEGMENT OF THE SEC'S. PLEASE SEE 250.6,
 240.24B, AS THIS CREATES "OBJECTIONABLE CURRENT" BY
 PARALLELING THE NEUTRAL.
 PLEASE KNOW, "IF" THIS CONDUCTOR IS INSTALLED, EVEN IF
 EXISTING, THIS MUST BE REMOVED.
 PLEASE BE SURE THIS IS THERE AS NOTED ON RISER BEFORE
 REVISING AND RESUBMITTING PLANS.
  
 24) NOTE: NO/ OK, PLEASE SEE THE SERVICE IS NOW SHOWN
 HOWEVER IT IS NO LONGER SHOWN AS EXISTING AND PLEASE
 SEE COMPLETE SET OF NEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE LOCATION OF THE EXISTING SERVICE.
 215.5, 240.24B, 408.7 ETC
  
 25) NOTE:NO, SAME NOTE .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 680.22B1 FOR MIN CLEARANCES FOR LIGHTING
 FIXTURES FROM POOL. PLEASE SEE LTS ETC AS SHOWN DO NOT
 MEET THE MIN DISTANCES REQUIRED FOR THE NEW ADDITION.
 PLEASE SEE SCONCES SHOWN ARE EVEN CLOSER WHICH WILL
 ALSO NOT BE PERMITTED.
  
 26) NOTE: OK/ NO, PLEASE SEE NOT ALL ARE SHOWN, HOWEVER
 SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE LIST ALL THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS PER 2002
 NEC 210.12B
  
  
 ***** NEW NOTES 2ND REVIEW **********
  
 27) NOTE: PLEASE SEE A COMPLETELY NEW RISER IS BEING
 SHOWN AND SUBMITTED. PLEASE SEE THIS SERVICE IS BEING
 SHOWN BUT NOT CLEAR WHAT, HOW OR WHERE THIS SERVICE IS
 MOUNTED AS NO BUILDING OR STRUCTURE IS SHOWN.
 PLEASE ALSO SEE LOCATION AS SHOWN PLACES SERVICE CLOSER
 THAN 3 FT FROM PROPERTY LINE WHICH WOULD NOT GIVE THE
 PERMITTED CLEARANCES PER 110.26
  
 28) NOTE: PLEASE COMPLETE RISER WITH ALL SEC?S, FROM
 METER TO MAIN.
 310.15B6, 310.16, 240.4 , 230,42 ETC.
  
 29) NOTE: PLEASE SEE RISER MENTIONS TO SEE PANEL
 SCHEDULE FOR GROUNDING ELECTRODE CONDUCTOR, HOWEVER
 THIS WAS NOT LOCATED. PLEASE SEE SERVICE IS NOW BEING
 SHOWN AS 300A'S, AND NO NEW GEC IS SHOWN.
  
 30) NOTE: PLEASE ALSO SEE 310.15B6, 250.66 FOR SIZING
 OF THE NEW GEC, MIN PER 250.66 WOULD BE #2.
  
 31) NOTE: PLEASE SEE FEEDERS FROM MAIN TO PANEL "LA" ,
 AND OCP F.24B, 250.110,OR NEW PANEL. PLEASE INDICATE
 THE CORRECT SIZE FOR THE EQUIPMENT GROUNDING CONDUCTOR
 WHICH IS BASED ON THE OCP AND PER 250.122.
 250
  
 32) NOTE: PLEASE CORRELATE RISER AND PANEL LA, AS ONE
 SHOWS MCB AND THE OTHER MLO.
 FBC ADMIN SECT 106.1.2
  
 33) NOTE: PLEASE SEE NOW THAT AHU'S ARE ALL SHOWN
 PLEASE SEE 424.3B (AS PREVIOUSLY NOTED ), HOWEVER MOST
 IMPORTANT, PLEASE SEE 240.24D AND 110.26 AS THIS SHALL
 NOT BE LOCATED ON CLOTHES CLOSET AS SHOWN.
  
 34) NOTE: PLEASE SUBMIT AND COORDINATE AIC RATINGS FOR
 ALL SERVICE EQUIPMENT.
 110.9, 240.12.
 SHOWN FOR SOME, HOWEVER NOT ALL.
  
 35) NOTE: PLEASE SEE THIS PLAN IS NOW SHOWING A
 GENERATOR WHICH WAS NOT ON PREVIOUS PLANS. PLEASE ALSO
 KNOW THE EXISTING PERMIT/PLANS FOR THE INSTALLATION OF
 A GENERATOR DOES NOT CORRELATE WITH THESE PLANS
 SUBMITTED. THEGEN/ ATS/ RISER/ SITE / PRIMEMOVER ETC
 ARE ALL DIFFERENT ON THE GEN PERMIT.
  
 PLEASE KNOW AS SHOWN ON THIS RISER THIS IS NOT
 PERMITTED.
 PLEASE SUBMIT ALL OF THE MANUFACTURES SPECS AND CUT
 SHEETS ON THE EQUIPMENT NOW BEING PROPOSED ON THIS
 RISER WHICH DOES NOT CORRELATE WITH GEN PERMIT.
 UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS TIME.
 225.31, 90.7, 110.3.
 PLEASE COMPLETE AND CORRELATE RISER AS SHOWN. PLEASE
 KNOW, IF INDEED SERVICE IS BEING INCREASED A COMPLETE
 REVISION TO THE GEN PERMIT WILL BE REQUIRED.
 FBC ADMIN SECT 106.1.2, NEC 2002.
  
 36) NOTE: PLEASE SEE WITH THE NEW CALCULATIONS AS SHOWN
 FOR AHU, PLEASE CORRELATE THE 11KW, 10KW, AND AMPERAGE
 AS SHOWN.
 PLEASE SEE HOW COULD 10KW AND 5KW MAKE 11.2KVA? PLEASE
 SEE ALSO PERVIOUSNOTES FOR OCP ETC.
 220.31B, 220.21, 424 ETC THERE ARE MANY ARTICLES WHICH
 COULD BE REFERENCED, HOWEVER PLEASE CORRELATE.
  
 37)NOTE: PLEASE CORRELATE LOAD ON EM PANEL AS SHOWN
 AS 8.5A'S WHERE KW RATING AND LOAD IS SUBSTANTIALLY
 HIGHER.
 215.5, 220 ETC.
  
 38) NOTE: PLEASE SEE MISSING CIRCUITING FOR SA'S (
 SMOKE ALARMS). PLEASE ALSO SEE 210.12B FOR REQUIRED
 PROTECTION.
  
 39) NOTE: PLEASE SEE NEC 210.11C2, 220.16 FOR MIN VA
 FOR LAUNDRY AND WASHERCIRCUIT.
  
 40) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS A "A" AND "C"
 PHASE YET THIS IS AND SHOULD BE "A" AND "B" PHASE.
 PLEASE ALSO SEE THE AMPERAGE'S AS SHOWN ON PANEL
 SCHEDULE(S) DO NOT SEEM TO CORRELATE WITH THE KVA/ KW
 LOADS AS SHOWN??
 UNABLE TO VERIFY MANY ITEMS.
 215.5,220.31B,310.16,240.4 ETC
  
 41) NOTE: PLEASE SEE 220.3B (4) RECESSED LUMINAIRES
 (LIGHTING FIXTURES). AN OUTLET SUPPLYING RECESSED
 LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE COMPUTED
 BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE
 EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S)
 [FIXTURE(S)] IS RATED.
 PLEASE LIST ON THE FIXTURE SCHEDULE THE FIXTURE AND THE
 MAX WATTAGE PER FIXTURE AS SHOWN.
 PLEASE ADJUST AND INCLUDE INTO THE LOAD CALCULATIONS.
 THESE ARE NOT PART OF THE GEN LTS, AS THEY EXCEED THE
 NORMAL AMOUNT FOR GEN LTS.
  
 42) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 THE DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE KNOWONE COPY OF EACH OF THE ELECTRICALPLANS
 ARE BEING RETAINED AT THIS TIME.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
  
  
 ** PLEASE KNOW DUE TO THE EXTENT OF COMMENTS; PLEASE BE
 SURE TO SEE ONE REDLINED SET AS MANY OF THE ABOVE ITEMS
 WERE "REDLINED". THIS IS IN NO WAY ALL POSSIBLE
 LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
  
 561-805-6717
 [email protected]
  
2006-11-02 19:15:51IN ELEC FROM ZON ON 11/2

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-05 Cont ID  
Sent By dpalmer Date 2006-07-05 Time 18:44 Rev Time 0.00
Received By dpalmer Date 2006-07-05 Time 17:20 Sent To M
Notes
2006-07-05 00:00:00********* UNSAT ***********
  
  
 ** PLEASE SEE COMMENTS FROM ZONING
 REVIEW WHICH WILL AFFECT ELECTRICAL
 PLANS AND DESIGN.
  
 1) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. 2',6'12' RULE ALL WALL SPACES
 FOR NEW AREAS AND NEW CONVERTED AREAS
 WHICH USED TO BE THE KITCHEN.
  
 2) NOTE: PLEASE SEE MISSING EITHER
 EXISTING OR NEW DINING RM DEDICATE
 CIRCUIT REQUIRED. PLEASE SEE 210.52B1,210.11C1,220.16
 ON ONE OR MORE
 OF THE SM APPL CIRCUITS.
 ** PLEASE SEE THE DINING ROOM MAY NOT BE
 CIRCUITED TO THE GARAGE AS NOTED ON
 PANEL SCHEDULE. (THIS WOULD BE OK,ONLY
 FOR LIGHTING CIR).
  
 3) NOTE: PLEASE SEE MISSING GFI RECEPT
 SPACING ALONG MANY AREAS OF THE KITCHEN
 COUNTER SPACES.
 210.52C1
  
 4) NOTE: PLEASE SEE MISSING LOCATION OF
 NEW AHUFOR ADDITION. PLEASE SHOW
 LOCATION AND PLEASE ALSO SEE 440.11 FOR
 MISSING DISCONNECTS FOR BOTH THE AHU AND
 CU.
  
 5) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR CU.
 210.63, 210.8A
  
 6) NOTE: PLEASE SEE MISSING NEW OR
 EXISTING REAR RECEPT PER 210.52E (GFI
 PER 210.8A)
  
 7) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR NEW BATH RM OFF THE GARAGE.
 210.52D,210.11C3
  
 8) NOTE: PLEASE CLARIFY NEW OR EXISTING
 GARAGE GFI.
 210.52G, 210.8A
  
 9) NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) RM CIRCUITS(S). 210.52D,210.11C3.
  
 10) NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS REQUIRED IN NEW AND EXISTING
 DWELLING PER NFPA-72 11.5.1.1,11.8.3
 PLEASE SEE THESE SHALL ALL BE HARDWIRED
 INLINE AND ARC FAULT PROTECTED PER
 210.12B
 PLEASE SEE SD IN MASTER BEDRM SHALL BE
 INSTALLED WITHIN 3' OF THE HIGHEST POINT
 OF THE SLOPED CEILING OR 12" OF THE FLAT
 CEILING AREA IF A TRAY/FLAT AREA.
  
 11) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 106.1.2 FBC ADMIN SECT.
  
 12) NOTE: PLEASE SEE MIN CLEARANCES DO
 NOT SEEM TO BE MET FOR NEW CLOSET LTS.
 PER 410.8
  
 13) NOTE: PLEASE SEE PLANS APPEAR TO
 SHOW A "JACUZZI/SPA TUB" YET PANEL
 SCHEDULE AND LOAD CALCULATIONS DO NOT
 INDICATE EITHER??
 PLEASE ALSO INDICATE THE REQUIRED GFI
 PROTECTION.
 680.71, 106.1.2 FBC ADMIN SECT.
  
 14) NOTE: PLEASE SEE 250.50, AS THE NEW
 FOOTER STEEL IS REQUIRED TO PART OF THE
 GROUNDING ELECTRODE SYSTEM.
  
 15) NOTE: PLEASE SEE RISER INDICATES
 "CURRENT SERVICE", THIS IS TAKEN AS
 EXISTING SERVICE, YET THE PANEL SCHEDULE
 IS NOTED AS BEING THE "PROPOSED" PANEL?
 IS THIS EXISTING OR NEW?
 PLEASE CLARIFY.
  
 16) NOTE: PLEASE SEE RISER ONLY SEEMS TO
 BE SHOWING ONE A/C SYSTEM?
 PLEASE ALSO SEE THE FOLLOWING COMMENTS.
 PLEASE SEE NOTE ON PANEL SCHEDULE
 MENTIONS 1-5KW AND 1-10KW, HOWEVER PANEL
 SCHEDULE SHOWS 10KW UNITS.
 PANEL ALSO SHOWS "4-SPACES"??
 PLEASE CLARIFY THIS. PLEASE SEPARATE
 THESE OF THE "4-SPACES" IS FOR TWO
 SEPARATE A/C AHU'S.
 PLEASE ALSO SEE THAT THE OCP FOR THE
 AHU'S SHALL BE SIZED AT A MIN OF 125%.
 PLEASE SEE AHU'S ARE SHOWN W/ 40A OCP.
 PLEASE SEE 424.3B,240.4,310.16,440.11
 ETC
  
 17) NOTE: PLEASE SEE 220.31B, 220.21 FOR
 MIN LOAD CALCULATIONS FOR SERVICE.
 PLEASE ALSO SEE MIN LOADS FOR A/C SYSTEM
 SHALL BE SHOWN. PLEASE SEE THE LARGER OF
 THE TWO LOADS SHALL BE INDICATED IN
 LOADS CALCS. LOADS SHOWN DO NOT
 CORRELATE WITH EITHER THE NOTE FOR ONE
 5KW AND ONE-10KW OR THE TWO 10KW UNITS
 AS NOTED ON PANEL SCHEDULE.
 PLEASE ADJUST AND REVISE CALCULATIONS.
  
 18) NOTE: PLEASE SEE LOAD CALCULATIONS
 MENTIONS 2-RANGES, YET PLANS DO NOT
 CORRELATE WITH THIS?
 PLEASE SEE PLANS INDICATE ONE RANGE AND
 AN "OVEN"? PLEASE SEE PANEL SCHEDULE
 DOES NOT SHOW OVEN.
 PLEASE VERIFY ALL KW LOADS, OCP AND
 CIRCUITS.
 408.4,240.4,310.16 ETC
  
 19) NOTE: PLEASE SEE
 210.52B1,210.11C1,220.16A FOR MIN 1500VA
 FOR SM APPL CIRCUITS. (PLANS SHOW 1400).
  
 20) NOTE: PLEASE SEE DEDICATED
 DISHWASHER IS SHOWN ON LOAD CALCS, YET
 NOT ON PANEL SCHEDULE.
 PLEASE SEE DISPOSAL(S) ON PANEL
 SCHEDULE, HOWEVER NOT IN LOAD CALCS.?
 PLEASE SEE OTHER WHICH ARE NOT LISTED.
 PLEASE BE SURE TO GO THROUGH ALL
 CIRCUITS ON THE HOUSE PANEL NEW AND
 EXISTING, LIST IN LOAD CALCS, SHOW ON
 PANEL SCHEDULE AND ADJUST LOAD
 CALCULATIONS ACCORDINGLY.
 215.5,220.31B,ETC.
  
 21) NOTE: PLEASE SEE PANEL SCHEDULE
 SHALL INDICATE ALL CONDUCTOR SIZES PER
 310.16,240.4,215.5,408.4 ETC
 FBC 106.1.2, ADMIN SECT
  
 22) NOTE: PLEASE CLARIFY "4-SPACES SHOWN
 FOR THE 2-POLE 60A BREAKER FOR THE POOL
 SUB PANEL??
 106.1.2
  
 23) NOTE: PLEASE SEE RISER SHOWS AN
 "EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO THE MAIN?? IT IS NOTED THAT
 THIS IS EXISTING, HOWEVER THE #8 SHOULD
 NOT BE LOCATED IN THIS SEGMENT OF THE
 SEC'S. PLEASE SEE 250.6,240.24B, AS THIS
 CREATES "OBJECTIONABLE CURRENT" BY
 PARALLELING THE NEUTRAL.
 PLEASE KNOW, "IF" THIS CONDUCOTOR IS
 INSTALLED , EVEN IF EXISTING, THIS MUST
 BE REMOVED.
 PLEASE BE SURE THIS IS THERE AS NOTED ON
 RISER BEFORE REVISING AND RESUBMITTING
 PLANS.
  
 24) NOTE: PLEASE SHOW THE LOCATION OF
 THE EXISTING SERVICE.
 215.5,240.24B,408.7 ETC
  
 25) NOTE: PLEASE SEE 680.22B1 FOR MIN
 CLEARANCES FOR LIGHTING FIXTURES FROM
 POOL. PLEASE SEE LTS ETC AS SHOWN DO NOT
 MEET THE MIN DISTANCES REQUIRED FOR THE
 NEW ADDITION.
 PLEASE SEE SCONCES SHOWN ARE EVEN CLOSER
 WHICH WILL ALSO NOT BE PERMITTED.
  
 26) NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS PER 2002
 NEC 210.12B
  
  
 ** PLEASE KNOW DUE TO THE EXTENT OF
 COMMENTS, PLEASE BE SURE TO SEE ONE
 REDLINED SET AS MANY OF THE ABOVE ITEMS
 WERE "REDLINED". THIS IS IN NO WAY ALL
 POSSIBLE LOCATIONS.
  
 **IMPORTANT**
 AFTER ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS AND BEFORE
 RESUBMITTING PLANS. PLEASE BE SURE TO
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO AVOID ANY
 DELAYS IN THE PROCESSING OF PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 14:49 Rev Time 0.00
Received By shill Date 2008-01-25 Time 14:49 Sent To M
Notes
2008-01-25 14:49:31TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 09:20 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 09:20 Sent To B
Notes
2007-05-18 09:20:57TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 10:05 Rev Time 0.00
Received By shill Date 2007-05-03 Time 10:05 Sent To B
Notes
2007-05-03 10:05:23TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 10:07 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 10:07 Sent To E
Notes
2007-01-31 10:07:52TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 14:38 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 14:38 Sent To E
Notes
2006-12-22 14:38:53TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 18:53 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 18:53 Sent To ENG
Notes
2006-11-01 18:53:38TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 11:08 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 11:08 Sent To Z
Notes
2006-10-24 11:09:05TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-05 Cont ID  
Sent By adarroug Date 2006-07-05 Time 10:15 Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 10:15 Sent To E
Notes
2006-07-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-19 Time   Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 14:06 Sent To  
Notes
2006-06-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-28 Cont ID  
Sent By tgordon Date 2008-01-28 Time 09:00 Rev Time 0.30
Received By tgordon Date 2008-01-28 Time 09:00 Sent To Z
Notes
2008-01-28 09:01:11REVISION TO MECH. PLAN PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-26 Cont ID  
Sent By tgordon Date 2006-12-26 Time 08:50 Rev Time 0.30
Received By tgordon Date 2006-12-26 Time 08:50 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-03 Cont ID  
Sent By tgordon Date 2006-11-03 Time 14:22 Rev Time 0.30
Received By tgordon Date 2006-11-03 Time 14:22 Sent To P
Notes
2006-11-03 14:35:00*** DENIED ***
 1) THE ARCHITECT NEED TO PUT THE DATE WHEN HE SIGNED
 THE PLANS, PER FAC 61G-16.003.
  
 2) MANUAL J CALCULATIONS WILL NEED TO BE FOR THE WHOLE
 HOUSE, AS THE NEW A/C SYSTEM IS SERVICING HALF OF THE
 EXISTING HOUSE THAT WAS SERVICED BY THE EXISTING A/C
 SYSTEM, AND NOW THE EXISTING A/C SYSTEM MAY BE OVER
 SIZED FOR JUST TWO ROOMS. ALSO PLEASE SUBMIT ALL
 INFORMATION ON THE EXISTING A/C SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-06 Cont ID  
Sent By tgordon Date 2006-07-06 Time 10:24 Rev Time 0.45
Received By tgordon Date 2006-07-06 Time 10:24 Sent To P
Notes
2006-07-06 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE AN ARCHITECT'S
 SEAL ON THEM AND REQUIRE HIS NAME AND
 INFORMATION IN THE TITLE BLOCK, PER FAC
 61G1-16.004 .
  
 2) PLEASE SUBMITMANUAL J CALCULATIONS,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 4) BATHROOM EXHAUST FANS NEED TO BE 50
 CFM'S INTERMITTENT OR 20 CFM'S
 CONTINUOUS, PER 2004 FBC/M 403.3 PLEASE
 CORRECT.
  
 5) SHOW LOCATION OF CLOTHES DRYER VENT
 ON MECHANICAL PLANS, PLEASE OBSERVE
 CLOTHES DRYER VENT TERMINATION MUST BE A
 MIN. OF 4 FT. FROM A/C CONDENSER UNIT,
 PER 2004 FBC/M 501.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-11-18 Cont ID  
Sent By jleech Date 2006-11-18 Time 14:23 Rev Time 0.00
Received By jleech Date 2006-11-18 Time 14:23 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-13 Cont ID  
Sent By jleech Date 2006-07-13 Time 13:13 Rev Time 0.00
Received By jleech Date 2006-07-13 Time 13:12 Sent To B
Notes
2006-07-13 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER IS REQUIRED
 TO DISCHARGE DOWN STREAM OF THE BATHROOM
 GROUP. FBC-2004 PLUMBING SEC. 909.1.
 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 IS REQUIRED TO BE 3" SEC. 406.3. SHOW
 CLEANOUT ON WASHER STACK AT 48" ABOVE
 FINISH FLOOR.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-28 Cont ID  
Sent By choops Date 2008-01-28 Time 09:21 Rev Time 0.00
Received By choops Date 2008-01-28 Time 09:21 Sent To PC
Notes
2008-01-28 09:23:09***APPROVED - REVISION - CHANGED A/C LOCATION - SHEET
 M-1***
  
 PROVISO:A/C EQUIPMENT MUST BE A MINIMUM OF 4' TO THE
 WEST SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-31 Cont ID  
Sent By mmclean Date 2006-10-31 Time 16:07 Rev Time 0.00
Received By mmclean Date 2006-10-31 Time 16:07 Sent To I
Notes
2006-10-31 16:08:38PROVISO: THE SIDE SETBACK MUST MEET THE REQUIRED 15FT
 TOTAL.
  
 NOTE: ANY FENCE/GATE/WALL MUST HAVE A SEPARATE PERMIT
 WITH EASEMENT APPROVAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By mmclean Date 2006-07-03 Time 16:14 Rev Time 0.00
Received By mmclean Date 2006-07-03 Time 16:14 Sent To I
Notes
2006-07-03 00:00:00DENIED,
 1. THE PROPOSED GARAGE MUST SIT 25FT IN
 THE FRONT SETBACK AS REQUIRED IN SEC
 94-74(3)A.
 2. THE SITEPLAN SHOWS THE FRONT SETBACK
 AT 20FT.
  
 NOTE:
 THE PROPOSED A/C UNIT MUST BE 6FT FROM
 THE SIDE SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved