Plan Review Details - Permit 06061238
Plan Review Stops For Permit 06061238
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:34 Rev Time 0.50
Received By alange Date 2006-07-13 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By btrobaug Date 2006-08-14 Time 07:45 Rev Time 0.33
Received By btrobaug Date 2006-08-14 Time 07:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-05 Cont ID  
Sent By btrobaug Date 2006-07-05 Time 18:20 Rev Time 0.50
Received By btrobaug Date 2006-07-05 Time 17:45 Sent To P
Notes
2006-07-05 00:00:00 
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE COPE OF THIS PERMIT. FBC
 108.3.
  
 2} IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 3}702.5 CAPACITY AND RATING.AN
 OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. PROVIDE A LOAD
 CALCULATION SHOWING COMPLIANCE WITH THIS
 ARTICLE.
  
 4} 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
 NO APPLIANCES AND NO LAMPS, OTHER THAN
 THOSE SPECIFIED AS REQUIRED FOR
 EMERGENCY USE, SHALL BE SUPPLIED BY
 EMERGENCY LIGHTING CIRCUITS. PROVIDE A
 PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL.
  
 5} INDICATE HOW THE TRANSFER SWITCH IS
 FED FROM THE PANEL.THERE MUST BE A
 MAIN IN THIS PANEL OR OCP IN THE MAIN
 PANEL. SEE 230.72.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By mperson Date 2006-07-07 Time 10:56 Rev Time 0.15
Received By mperson Date 2006-07-07 Time 10:56 Sent To M
Notes
2006-07-07 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-09 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 09:45 Sent To E
Notes
2006-08-09 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 13:11 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 13:11 Sent To Z
Notes
2006-08-02 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 10:25 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 10:25 Sent To E
Notes
2006-06-27 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:34 Rev Time 0.00
Received By alange Date 2006-06-22 Time 13:28 Sent To  
Notes
2006-06-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By tgordon Date 2006-08-14 Time 08:05 Rev Time 0.20
Received By tgordon Date 2006-08-14 Time 08:05 Sent To  
Notes
2006-08-14 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 09:41 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 09:41 Sent To B
Notes
2006-07-11 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By mmclean Date 2006-08-08 Time 07:33 Rev Time 0.00
Received By mmclean Date 2006-08-08 Time 07:33 Sent To I
Notes
2006-08-08 00:00:00THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6FT FROMSIDE PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-25 Cont ID  
Sent By mmclean Date 2006-06-25 Time 16:36 Rev Time 0.00
Received By mmclean Date 2006-06-25 Time 16:36 Sent To I
Notes
2006-06-25 00:00:00DENIED,
 1. PLEASE PROVIDE TWO COPY OF THE HOA
 APPROVAL FOR THE PROPOSED GENERATOR.
 (HOA - HOME ASSOCIATION APPROVAL FOR
 IRON HORSE)
 2. PLEASE PROVIDE A COMPLETE COPY OF THE
 SURVEY (NOT BLOWN UP)THAT SHOWS THE
 COMPLETE PROPERTY WITH DIMENSION OF LOT
 WITH THE LOCATION OF PROPOSED GENERATOR.
  
 NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6FT FROMSIDE PROPERTY
 LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720