Plan Review Details - Permit 06061237
| Plan Review Stops For Permit 06061237 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-08-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-20 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-20 |
Time |
10:15 |
Sent To |
PC |
|
| Notes |
| 2006-08-20 00:00:00 | REDLINED 250.56 FOR 2-GRNDS RODS MIN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-08-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-06 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-06 |
Time |
13:14 |
Sent To |
PC |
|
| Notes |
| 2006-08-06 00:00:00 | *** UNSAT2ND REVIEW ****** | | | | | | ** PLEASE SEE SOME NOTE ARE NEW DUE TO | | | RISER BEING REVISED. | | | | | | 1) NOTE: PLEASE CLARIFY AND COMPLETE | | | RISER. | | | PLEASE SEE RISER SHOWS A 800A SERVICE, | | | HOWEVER SEC'S ARE ONLY SHOWN FOR A 400A | | | SERVICE. PREVIOUS RISER SUBMITTED 800A'S | | | 240.4,310.16 | | | | | | 2) NOTE: PLEASE SEE GROUNDING ELECTRODE | | | IS SHOWN ON THE EXISTING RISER AS #4 | | | WHICH IS WAY TOO SMALL PER TABLE IN | | | 250.66. PLEASE SEE "NEW" RISER DOES NOT | | | SHOW ANY GE SYSTEM. | | | 250.66 | | | | | | 3) NOTE: PLEASE SEE "EQUIPMENT GROUNDING | | | CONDUCTORS" ARE BEING SHOWN BEFORE THE | | | FIRST MEANS OF DISCONNECTS. | | | 250.6,250.24B | | | | | | 4) NOTE: PLEASE PROVIDE CONDUCTORS FROM | | | J-BOX TO THE MTS. | | | | | | 5) NOTE: PLEASE BE SURE THE PERSON | | | RESPONSIBLE FOR PLANSSHALL CONTAIN THE | | | PRINTED NAME AND SIGNATURE. | | | FBC 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-27 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-27 |
Time |
17:51 |
Sent To |
PC |
|
| Notes |
| 2006-06-27 00:00:00 | ******** UNSAT *********** | | | | | | 1) NOTE: PLEASE CLARIFY AND COMPLETE | | | RISER. | | | PLEASE SEE NEW J-BOX APPEARS TO BE | | | LOCATED IN GROUND, YET RISER SHOWS "EMT" | | | AS THE CONDUIT. | | | PLEASE PROVIDE PLANS WITH MIN 1/8" SCALE | | | AND PLEASE DRAW RISER AS AN ELEVATION. | | | | | | 2) NOTE: PLEASE CLARIFY OF THE 800A MAIN | | | FEED STHE GUTTER? | | | PLEASE COMPLETE ALL NEW CONDUCTORS BEING | | | INSTALLED IN GUTTER AND NEW MAN MTS'S. | | | 215.5,240.4,310.16 | | | PLEASE SEE BOTH MTS'S NEED SHOW THE OCP | | | IN EACH AS THE ONLY FEED COMEING FROM | | | GEN CONNECTION IS ONLY RATED AT 200A'S?? | | | | | | | | | 3) NOTE: PLEASE PROVIDE THE MANUFACTURES | | | SPECS/CUT SHEETS FOR BOTH MTS DEVICES. | | | NEED TO VERIFY THE REQUIREMENT FOR | | | 230.70,230.72,230.76,230.79 ETC. | | | 110.3, 215.5, | | | FBC 106.1.2 ADMIN SECT. | | | | | | | | | 4) NOTE: PLEASE BE SURE THE PERSON | | | RESPONSIBLE FOR PLANS/DESIGN PRINTS AND | | | SIGNS PLANS/DESIGN. | | | FBC ADMIN SECT 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-08-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-16 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-16 |
Time |
15:14 |
Sent To |
E |
|
| Notes |
| 2006-08-16 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-02 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-02 |
Time |
11:52 |
Sent To |
E |
|
| Notes |
| 2006-08-02 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-06-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-22 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | TO "E" BOX |
|
|
|