Plan Review Details - Permit 06061237
Plan Review Stops For Permit 06061237
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 10:28 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 10:15 Sent To PC
Notes
2006-08-20 00:00:00REDLINED 250.56 FOR 2-GRNDS RODS MIN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 13:27 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 13:14 Sent To PC
Notes
2006-08-06 00:00:00*** UNSAT2ND REVIEW ******
  
 ** PLEASE SEE SOME NOTE ARE NEW DUE TO
 RISER BEING REVISED.
  
 1) NOTE: PLEASE CLARIFY AND COMPLETE
 RISER.
 PLEASE SEE RISER SHOWS A 800A SERVICE,
 HOWEVER SEC'S ARE ONLY SHOWN FOR A 400A
 SERVICE. PREVIOUS RISER SUBMITTED 800A'S
 240.4,310.16
  
 2) NOTE: PLEASE SEE GROUNDING ELECTRODE
 IS SHOWN ON THE EXISTING RISER AS #4
 WHICH IS WAY TOO SMALL PER TABLE IN
 250.66. PLEASE SEE "NEW" RISER DOES NOT
 SHOW ANY GE SYSTEM.
 250.66
  
 3) NOTE: PLEASE SEE "EQUIPMENT GROUNDING
 CONDUCTORS" ARE BEING SHOWN BEFORE THE
 FIRST MEANS OF DISCONNECTS.
 250.6,250.24B
  
 4) NOTE: PLEASE PROVIDE CONDUCTORS FROM
 J-BOX TO THE MTS.
  
 5) NOTE: PLEASE BE SURE THE PERSON
 RESPONSIBLE FOR PLANSSHALL CONTAIN THE
 PRINTED NAME AND SIGNATURE.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 17:59 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 17:51 Sent To PC
Notes
2006-06-27 00:00:00******** UNSAT ***********
  
 1) NOTE: PLEASE CLARIFY AND COMPLETE
 RISER.
 PLEASE SEE NEW J-BOX APPEARS TO BE
 LOCATED IN GROUND, YET RISER SHOWS "EMT"
 AS THE CONDUIT.
 PLEASE PROVIDE PLANS WITH MIN 1/8" SCALE
 AND PLEASE DRAW RISER AS AN ELEVATION.
  
 2) NOTE: PLEASE CLARIFY OF THE 800A MAIN
 FEED STHE GUTTER?
 PLEASE COMPLETE ALL NEW CONDUCTORS BEING
 INSTALLED IN GUTTER AND NEW MAN MTS'S.
 215.5,240.4,310.16
 PLEASE SEE BOTH MTS'S NEED SHOW THE OCP
 IN EACH AS THE ONLY FEED COMEING FROM
 GEN CONNECTION IS ONLY RATED AT 200A'S??
  
  
 3) NOTE: PLEASE PROVIDE THE MANUFACTURES
 SPECS/CUT SHEETS FOR BOTH MTS DEVICES.
 NEED TO VERIFY THE REQUIREMENT FOR
 230.70,230.72,230.76,230.79 ETC.
 110.3, 215.5,
 FBC 106.1.2 ADMIN SECT.
  
  
 4) NOTE: PLEASE BE SURE THE PERSON
 RESPONSIBLE FOR PLANS/DESIGN PRINTS AND
 SIGNS PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 15:14 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 15:14 Sent To E
Notes
2006-08-16 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 11:52 Sent To E
Notes
2006-08-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-27 Time   Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 13:25 Sent To  
Notes
2006-06-22 00:00:00TO "E" BOX