| Plan Review Stops For Permit 06061218 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2007-07-12 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2007-07-12 |
Time |
16:27 |
Sent To |
I |
|
| Notes |
| 2007-07-12 16:34:48 | PROJECT: 219 MARLBOROUGH | | | | | | REVIEW: SUBMITTAL FOR GENERATOR STAND | | | | | | | | | COMMENTS: | | | | | | 1) PLEASE PROVIDE A HOLD HARMLESS LETTER ACKNOWLEDGING | | | THAT THE REMAINING MANUFACTURER'S WARRANTY MAY BE | | | VOIDED DUE TO THE USE OF THE ENGINEERED STAND. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-28 |
Time |
14:55 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2006-08-28 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-08-15 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-15 |
Time |
09:02 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-08-15 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-13 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-13 |
Time |
08:44 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-07-13 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2006-07-13 00:00:00 | DENIED | | | | | | SHOW GENERATOR SLAB DETAIL AND METHOD OF | | | ATTACHMENT TO SLAB. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2007-03-30 |
Time |
10:06 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
2007-03-30 |
Time |
10:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-08-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-25 |
Time |
13:59 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-25 |
Time |
13:49 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-11 |
Time |
07:03 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-11 |
Time |
06:31 |
Sent To |
M |
|
| Notes |
| 2006-08-11 00:00:00 | | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE COST OF LABOR AND MATERIAL | | | FOR THE INSTALLATION OF ALL COMPONENTS | | | UNDER THE SCOPE OF THIS PERMIT. FBC | | | 108.3. NOTE: THE INCREASE MUST BE | | | DECLAIRED TO THE PERMIT CLERK, A RECIEPT | | | ISSUED AND PAYMENT MADE PRIOR TO | | | RESUBMITTING. | | | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, GENERATOR, | | | TRANSFER SWITCH, DISCONNECTS AND PANELS, | | | SO THAT COMPLIANCE WITH ARTICLES 225 AND | | | 230 CAN BE REVIEWED. | | | PLEASE USE A SITE PLAN, THE ONE | | | SUBMITTED IS NOT SUFFICIENT TO ACTUALLY | | | LOCATE THE EQUIPMENT ON THE PROPERTY. | | | | | | 3} 700.15 LOADS ON EMERGENCY BRANCH | | | CIRCUITS. | | | NO APPLIANCES AND NO LAMPS, OTHER THAN | | | THOSE SPECIFIED AS REQUIRED FOR | | | EMERGENCY USE, SHALL BE SUPPLIED BY | | | EMERGENCY LIGHTING CIRCUITS. PROVIDE A | | | PANEL SCHEDULE FOR THE | | | EMERGENCY/GENERATOR PANEL. APANEL | | | SCHEDULE WITH A LOAD CALCULATION FOR | | | THAT PANEL. | | | | | | 4} THERE MUST BE A DISCONNECT FROM THE | | | GENERATOR WHERE THE CONDUCTORS ENTER THE | | | BUILDING. IF ALL DISCONNECTS CANNOT BE | | | GROUPED PER 230.72, SEE THAT ALL | | | ARTICLES FROM 225.31 THROUGH 225.39, ARE | | | COMPLIED WITH. PLEASE LOCATE ON | | | RESUBMITTED SITE PLAN. | | | | | | 6} PROVIDE A RISER DIAGRAM WITH | | | CONDUCTOR AND CONDUIT SIZE AND TYPE, | | | GROUNDING DETAILS, LOAD CALCULATIONS, | | | PANEL SCHEDULES, SERVICE EQUIPMENT AND | | | PANEL LOCATIONS PER 106.3.5.4 FBC. IF | | | YOU ARE NOT SURE WHAT A "RISER DIAGRAM" | | | CONSISTS OF, PLEASE CONTACT AN | | | ELECTRICAL CONTRACTOR. | | | | | | PLEASE OBTAIN A SETBACK RECOMMENDATION | | | FROM THE MANUFACTURER AND SUBMIT SAME. | | | SOMETIMES THEIR RECOMMENDATION IS MORE | | | STRINGENT THAN THE CODES. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-07-06 |
Time |
07:34 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-07-06 |
Time |
07:10 |
Sent To |
P |
|
| Notes |
| 2006-07-06 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE COST OF LABOR AND MATERIAL | | | FOR THE INSTALLATION OF ALL COMPONENTS | | | UNDER THE SCOPE OF THIS PERMIT. FBC | | | 108.3. | | | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, GENERATOR, | | | TRANSFER SWITCH, DISCONNECTS AND PANELS, | | | SO THAT COMPLIANCE WITH ARTICLES 225 AND | | | 230 CAN BE REVIEWED. USE A SITE PLAN. | | | | | | 3} 700.15 LOADS ON EMERGENCY BRANCH | | | CIRCUITS. | | | NO APPLIANCES AND NO LAMPS, OTHER THAN | | | THOSE SPECIFIED AS REQUIRED FOR | | | EMERGENCY USE, SHALL BE SUPPLIED BY | | | EMERGENCY LIGHTING CIRCUITS. PROVIDE A | | | PANEL SCHEDULE FOR THE | | | EMERGENCY/GENERATOR PANEL. | | | | | | 4} PROVIDE SPECIFICATIONS FOR THE | | | TRANSFER SWITCH. | | | | | | 5} THERE MUST BE A DISCONNECT FROM THE | | | GENERATOR WHERE THE CONDUCTORS ENTER THE | | | BUILDING. IF ALL DISCONNECTS CANNOT BE | | | GROUPED PER 230.72, SEE THAT ALL | | | ARTICLES FROM 225.31 THROUGH 225.39, ARE | | | COMPLIED WITH. | | | | | | 6} PROVIDE A RISER DIAGRAM WITH | | | CONDUCTOR AND CONDUIT SIZE AND TYPE, | | | GROUNDING DETAILS, LOAD CALCULATIONS, | | | PANEL SCHEDULES, SERVICE EQUIPMENT AND | | | PANEL LOCATIONS PER 106.3.5.4 FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-07-07 |
Time |
10:38 |
Rev Time |
0.15 |
| Received By |
mperson |
Date |
2006-07-07 |
Time |
10:38 |
Sent To |
M |
|
| Notes |
| 2006-07-07 00:00:00 | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL GEN/RES INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-03-26 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-03-26 |
Time |
18:12 |
Sent To |
E |
|
| Notes |
| 2007-03-26 18:12:56 | TO BILL TROBAUGH |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-10 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-10 |
Time |
15:00 |
Sent To |
E |
|
| Notes |
| 2006-08-10 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-08-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-03 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-03 |
Time |
11:07 |
Sent To |
Z |
|
| Notes |
| 2006-08-03 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-27 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-27 |
Time |
10:24 |
Sent To |
E |
|
| Notes |
| 2006-06-27 00:00:00 | TO "GEN-RES" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-13 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-13 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-06-22 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-08-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-25 |
Time |
14:58 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-08-25 |
Time |
14:58 |
Sent To |
Z |
|
| Notes |
| 2006-08-25 00:00:00 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE | | | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | FOLLOW MANUFACTURE'S RECOMMENDED | | | CLEARANCES AROUND EQUIPMENT FOR | | | SERVICING,AND PROVIDE MANUFACTURE'S | | | INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-11 |
Time |
16:11 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-08-11 |
Time |
16:11 |
Sent To |
B |
|
| Notes |
| 2006-08-11 00:00:00 | *** DENIED *** | | | 1) SEE ZONING REVIEW, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-11 |
Time |
09:36 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-07-11 |
Time |
09:36 |
Sent To |
B |
|
| Notes |
| 2006-07-11 00:00:00 | *** DENIED *** | | | 1) SEE ZONING REVIEW, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-08-25 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-08-25 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-08-25 |
Time |
17:39 |
Sent To |
B |
|
| Notes |
| 2006-08-25 00:00:00 | NOTE: THE PROPOSED GENERATOR SHALL NOT | | | BE CLOSER THAN 6FT FROM SIDE PROPERTY | | | LINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-08-08 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-08-08 |
Time |
10:09 |
Sent To |
I |
|
| Notes |
| 2006-08-09 00:00:00 | DENIED, | | | 1. THE SURVEY PROVIDE IS TOO OLD (1984), | | | SURVEY MUST BE AT LEAST 1YR OLD. | | | 2. PLEASE RESUBMIT WITH CURRENT SURVEY | | | SHOWING THE LOCATION OF THE PROPOSED | | | WORK. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-06-25 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-06-25 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-06-25 |
Time |
16:24 |
Sent To |
I |
|
| Notes |
| 2006-06-25 00:00:00 | DENIED, | | | 1. PLEASE PROVIDE A CURRENT SURVEY | | | SHOWING THE LOCATION OF THE PROPOSED | | | GENERATOR. (SURVEY PROVIDE IS NOT CLEAR | | | TO READ FOR REVIEW OF THE REQUIRED | | | SETBACKS FOR THE SIDE) | | | 2. NEED TO CLEARLY SHOW THE LOCATION OF | | | THE PROPOSED GENERATOR WITH READABLE | | | SETBACK OF THE STRUCTURE FROM SIDE | | | PROPERTY LINE. | | | | | | NOTE:SEC 94-303 MECHANICAL/POOL | | | EQUIPMENT/GENERATOR MAY NOT PROJECT MORE | | | THAN FOUR FEET INTO A SETBACK. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 | | | |
|
|