Plan Review Details - Permit 06061218
Plan Review Stops For Permit 06061218
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-12 Cont ID  
Sent By kconrad Date 2007-07-12 Time 16:35 Rev Time 0.00
Received By kconrad Date 2007-07-12 Time 16:27 Sent To I
Notes
2007-07-12 16:34:48PROJECT: 219 MARLBOROUGH
  
 REVIEW: SUBMITTAL FOR GENERATOR STAND
  
  
 COMMENTS:
  
 1) PLEASE PROVIDE A HOLD HARMLESS LETTER ACKNOWLEDGING
 THAT THE REMAINING MANUFACTURER'S WARRANTY MAY BE
 VOIDED DUE TO THE USE OF THE ENGINEERED STAND.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-28 Cont ID  
Sent By alange Date 2006-08-28 Time 14:55 Rev Time 0.33
Received By alange Date 2006-08-28 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-15 Cont ID  
Sent By alange Date 2006-08-15 Time 09:02 Rev Time 0.50
Received By alange Date 2006-08-15 Time 09:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:44 Rev Time 0.50
Received By alange Date 2006-07-13 Time 08:44 Sent To  
Notes
2006-07-13 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-30 Cont ID  
Sent By jleahy Date 2007-03-30 Time 10:06 Rev Time 0.30
Received By jleahy Date 2007-03-30 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-25 Cont ID  
Sent By btrobaug Date 2006-08-25 Time 13:59 Rev Time 0.50
Received By btrobaug Date 2006-08-25 Time 13:49 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By btrobaug Date 2006-08-11 Time 07:03 Rev Time 0.50
Received By btrobaug Date 2006-08-11 Time 06:31 Sent To M
Notes
2006-08-11 00:00:00 
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3. NOTE: THE INCREASE MUST BE
 DECLAIRED TO THE PERMIT CLERK, A RECIEPT
 ISSUED AND PAYMENT MADE PRIOR TO
 RESUBMITTING.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED.
 PLEASE USE A SITE PLAN, THE ONE
 SUBMITTED IS NOT SUFFICIENT TO ACTUALLY
 LOCATE THE EQUIPMENT ON THE PROPERTY.
  
 3} 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
 NO APPLIANCES AND NO LAMPS, OTHER THAN
 THOSE SPECIFIED AS REQUIRED FOR
 EMERGENCY USE, SHALL BE SUPPLIED BY
 EMERGENCY LIGHTING CIRCUITS. PROVIDE A
 PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL. APANEL
 SCHEDULE WITH A LOAD CALCULATION FOR
 THAT PANEL.
  
 4} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH. PLEASE LOCATE ON
 RESUBMITTED SITE PLAN.
  
 6} PROVIDE A RISER DIAGRAM WITH
 CONDUCTOR AND CONDUIT SIZE AND TYPE,
 GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC. IF
 YOU ARE NOT SURE WHAT A "RISER DIAGRAM"
 CONSISTS OF, PLEASE CONTACT AN
 ELECTRICAL CONTRACTOR.
  
 PLEASE OBTAIN A SETBACK RECOMMENDATION
 FROM THE MANUFACTURER AND SUBMIT SAME.
 SOMETIMES THEIR RECOMMENDATION IS MORE
 STRINGENT THAN THE CODES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-06 Cont ID  
Sent By btrobaug Date 2006-07-06 Time 07:34 Rev Time 1.00
Received By btrobaug Date 2006-07-06 Time 07:10 Sent To P
Notes
2006-07-06 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED. USE A SITE PLAN.
  
 3} 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
 NO APPLIANCES AND NO LAMPS, OTHER THAN
 THOSE SPECIFIED AS REQUIRED FOR
 EMERGENCY USE, SHALL BE SUPPLIED BY
 EMERGENCY LIGHTING CIRCUITS. PROVIDE A
 PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL.
  
 4} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 5} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 6} PROVIDE A RISER DIAGRAM WITH
 CONDUCTOR AND CONDUIT SIZE AND TYPE,
 GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By mperson Date 2006-07-07 Time 10:38 Rev Time 0.15
Received By mperson Date 2006-07-07 Time 10:38 Sent To M
Notes
2006-07-07 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-26 Cont ID  
Sent By spalmer Date 2007-03-26 Time 18:12 Rev Time 0.00
Received By spalmer Date 2007-03-26 Time 18:12 Sent To E
Notes
2007-03-26 18:12:56TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-08-10 Time 15:00 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 15:00 Sent To E
Notes
2006-08-10 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 11:07 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 11:07 Sent To Z
Notes
2006-08-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 10:24 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 10:24 Sent To E
Notes
2006-06-27 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:44 Rev Time 0.00
Received By alange Date 2006-06-22 Time 16:15 Sent To  
Notes
2006-06-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-25 Cont ID  
Sent By tgordon Date 2006-08-25 Time 14:58 Rev Time 0.20
Received By tgordon Date 2006-08-25 Time 14:58 Sent To Z
Notes
2006-08-25 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 16:11 Rev Time 0.15
Received By tgordon Date 2006-08-11 Time 16:11 Sent To B
Notes
2006-08-11 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 09:36 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 09:36 Sent To B
Notes
2006-07-11 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-25 Cont ID  
Sent By mmclean Date 2006-08-25 Time 17:39 Rev Time 0.00
Received By mmclean Date 2006-08-25 Time 17:39 Sent To B
Notes
2006-08-25 00:00:00NOTE: THE PROPOSED GENERATOR SHALL NOT
 BE CLOSER THAN 6FT FROM SIDE PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-09 Cont ID  
Sent By mmclean Date 2006-08-08 Time 10:09 Rev Time 0.00
Received By mmclean Date 2006-08-08 Time 10:09 Sent To I
Notes
2006-08-09 00:00:00DENIED,
 1. THE SURVEY PROVIDE IS TOO OLD (1984),
 SURVEY MUST BE AT LEAST 1YR OLD.
 2. PLEASE RESUBMIT WITH CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED
 WORK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-25 Cont ID  
Sent By mmclean Date 2006-06-25 Time 16:24 Rev Time 0.00
Received By mmclean Date 2006-06-25 Time 16:24 Sent To I
Notes
2006-06-25 00:00:00DENIED,
 1. PLEASE PROVIDE A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED
 GENERATOR. (SURVEY PROVIDE IS NOT CLEAR
 TO READ FOR REVIEW OF THE REQUIRED
 SETBACKS FOR THE SIDE)
 2. NEED TO CLEARLY SHOW THE LOCATION OF
 THE PROPOSED GENERATOR WITH READABLE
 SETBACK OF THE STRUCTURE FROM SIDE
 PROPERTY LINE.
  
 NOTE:SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  