Plan Review Details - Permit 06061209
Plan Review Stops For Permit 06061209
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-01 Cont ID  
Sent By btrobaug Date 2006-12-01 Time 11:10 Rev Time 0.50
Received By btrobaug Date 2006-12-01 Time 11:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-11-09 Cont ID  
Sent By dpalmer Date 2006-11-09 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2006-11-09 Time 14:47 Sent To PC
Notes
2006-11-09 15:20:11**** UNSAT ****
  
 *** PLEASE SEE COMMENTS BASED ON NEW REVISED RISER
 SUBMITTED.
  
 1) NOTE:PLEASE SEE RISER NOW SHOWS A MAIN BREAKER
 PANEL WITH A 125A MAIN, WITH #6'S ON RISER???
 PLEASE ALSO SEE RISER SHOWS A 60A MAIN??
 PLEASE CORRELATE.
  
 2) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDIGN CONDUCTOR"
 IS ALSO BEING SHOWN FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED.
 250.6, 250.24.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-17 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 07:46 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 07:22 Sent To PC
Notes
2006-10-17 07:46:04*** UNSAT 3RD REVIEW *****
  
 *** PLEASE SEE NOTES FROM PREVIOUS REVIEW.
 *** PLEASE SUBMIT AND COMPLETE A RISER DIAGRAM FOR NEW
 SERVICE MEETING 2002 NEC FOR CODE COMPLIANCE.
  
  
 1) NOTE: PLANS STILL DO NOT CONTIAN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE FOR PLANS.
 FBC ADMIN SECT 106.1.2
  
 2) NOTE: GROUNDING ELECTRODE SYSTEM NOT COMPLETE.
 250.50, 250.56
  
 3) NOTE: RISER SHOWS 30A BREAKER TO 20A GFI.
 240.4, 310.16, 210.21
  
 4) NOTE: PLEASE SEE RISER SHOWS2-"PO" BREAKER FROM
 FPL????
  
 5) NOTE: PLEASE INDICATE MAIN. 230.70, 230.71.
  
 6) NOTE: RISER NOT COMPLETE WITH CONDUCTORS. HOW MANY ?
 TO EACH ? EQUIPMENT GROUNDING? ETC ETC
 240.4,310.16,250.110, 250.24B.
  
 7) NOTE: HOW AND WHAT IS THIS UNIT /RISER BEING BUILT
 ON.
  
  
 ** PLEASE KNOW, ONE SET OF EACH OF THE PLANS HAVE BEEN
 RETAINED.
  
  
 PLEASE SUBMIT FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-02 Cont ID  
Sent By dpalmer Date 2006-08-02 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2006-08-02 Time 07:10 Sent To PC
Notes
2006-08-02 00:00:00******** UNSAT *******
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW
 NOTES AND COMPLETE RISER DIAGRAM.
 PLEASE SEE RISER SHOWS #10-12AWG?? FOR
 BOTH THE FEED TO PANEL AND THE FEED TO
 EXISTING IRRIGATION SYSTEM.
 PELASE SEE PANEL IS SHOWN AS 2X30A
 BREAKER PANEL?? THIS IS UNCLEAR AT THIS
 TIME. IS THIS A 2-POLE 30A BREAKER FOR
 MAIN? OR DOES THIS CONTAIN 2-30A
 BREAKERS/ IF SO WHAT DO THESE TWEO
 BREAKERS FEED. THE DUPLEX RECEPTS DO NOT
 APPEAR TO BE 30A?
 PLEASE ALSO SEE NOTE AT LOWER LEFT HAND
 SIDE OF PANEL SHOWS 2-POLE FUSE PANEL?
 PLEASE VERIFY IF PANEL IS GOING TO BE A
 FUSE PANEL OR BREAKER PANEL.
 PLEASE SEE 240.4.310.16,215.5, ETC
  
 2) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM.
 250.50,250.66
  
 3) NOTE: PLEASE BE SURE THE PLANS/DESIGN
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 FBC 106.1.21
  
 ** PLEASE SEE COMMENTS ALSO ATTACHED
 FROM PREVIOUS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 11:45 Sent To PC
Notes
2006-06-27 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE COMPLETE ELECTRICAL
 RISER DIAGRAM SHOWING ALL MIN CONDUCTOR
 SIZES, FOR SEC'S , FEEDERS, BRANCH
 CIRCUIT(S). PLEASE INDICATE OCP FOR EACH
 OF THE ABOVE.
 PLEASE COMPLETE RISER DIAGRAM.
 PLEASE SUBMIT AIC RATINGS OF NEW MAIN.
 PLEASE SEE RECEPT IS BEING SHOWN BEING
 FED THROUGH METER WHICH IS NOT
 PERMITTED.
  
 215.5,310.16,240.4,230.7,250.50 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-06 Cont ID  
Sent By btrobaug Date 2006-11-06 Time 13:03 Rev Time 0.00
Received By btrobaug Date 2006-11-06 Time 13:03 Sent To E
Notes
2006-11-06 13:05:14TO DVP./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 18:03 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 18:03 Sent To E
Notes
2006-10-10 18:04:12TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 13:18 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 13:18 Sent To E
Notes
2006-08-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-27 Time   Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 14:35 Sent To  
Notes
2006-06-22 00:00:00TO "E" BOX