Plan Review Details - Permit 06061101
Plan Review Stops For Permit 06061101
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-03-15 Cont ID  
Sent By amorse Date 2008-03-15 Time 09:24 Rev Time 0.00
Received By amorse Date 2008-03-15 Time 09:24 Sent To PC
Notes
2008-03-15 09:48:07 
  
 DENIED
  
 1)THE GLASS BLOCK MEETS THE DESIGN PRESSURES REQUIRED
 BUT IS ONLY SMALL MISSILE IMPACT RATED. PER 1609.1.4
 FBC GLAZING WITHIN THE FIRST 30 FEET FROM GRADE ARE
 REQUIRED TO MEET LARGE MISSILE IMPACT TEST REQUIREMENTS
 THEREFORE THESE OPENINGS WILL REQUIRE AN IMPACT
 PROTECTION SYSTEM. IF THIS PRODUCT IS USED SHUTTERS
 WILL BE REQUIRED. PITTSBURGH CORNING HAS A GLASS BLOCK
 SYSTEM THAT USES SILICONE RATHER THAN MORTAR THAT MEETS
 THE REQUIREMENTS OF SMALL AND LARGE MISSILE IMPACT
 RATING.
  
 2)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN
 BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN
 AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED.*******PLEASE SEE THE FL# WRITTEN AT TOP OF
 MIAMI-DADE NOA, IF SILICONE SYSTEM IS USED FL # IS
 5357-R1********
  
 3)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 4)ORIGINAL DRAWINGS DO NOT SHOW GLASS BLOCK, REVISED
 SHEET SHOWING LOCATION OF NEW GLASS BLOCK OPENING ARE
 REQUIRED WITH THE PRODUCT APPROVAL.
  
 5)THIS IS A REVISION TO THE PERMITTED SET OF DRAWING
 NOT A SUBMITTAL AND AS SUCH REQUIRES A REVISION FEE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-10-20 Cont ID  
Sent By amorse Date 2007-10-20 Time 07:23 Rev Time 0.00
Received By amorse Date 2007-10-20 Time 07:23 Sent To PC
Notes
2007-10-20 07:24:03 
  
 2 SETS OF PLANS RESTAMPED

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-06-07 Cont ID  
Sent By amorse Date 2007-06-07 Time 16:07 Rev Time 0.00
Received By amorse Date 2007-06-07 Time 16:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-04-06 Cont ID  
Sent By amorse Date 2007-04-06 Time 14:49 Rev Time 0.00
Received By amorse Date 2007-04-06 Time 14:49 Sent To PC
Notes
2007-04-06 15:09:26 
 DENIED
  
 1)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID. ****PLEASE SUBMIT A RERECORDED NOC.****
  
 2)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
 ****2 COMPLETE COPIES THAT ARE SIGNED AND SEALED BY THE
 TRUSS MANUFACTURERS ENGINEER ARE REQUIRED.****
  
 3)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. ****ONLY ONE COPY WAS SUBMITTED AND IT
 WAS NOT DATED.****
  
 4)THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE
 PRODUCT APPROVALS
  
 A) CHOOSE THE TYPE OF GAF SHINGLE THAT WILL BE USED
 FROM THE FLORIDA PAGE AND SUBMIT WITH THE CORRECT NOA
 B) CHOOSE THE TYPE OF WINDOW THAT YOU WILL USE FROM THE
 FLORIDA PAGES AND SUBMIT WITH THE ACCOMPANYING NOA C)
 TWO DIFFERENT PRODUCT APPROVALS WERE SUBMITTED FOR
 STORM PANELS PLEASE SUBMIT 2 COPIES OF THE PRODUCT YOU
 WILL BE USING.
 D) THE DOOR MANUFACTURER THAT WAS SUBMITTED DOES NOT
 CARRY ANY APPROVED STATUS IN THE 2004 FLORIDA SYSTEM OR
 ON THE MIAMI-DADE SITE. PLEASE SUBMIT 2 COPIES OF AN
 APPROVED DOOR.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-28 Cont ID  
Sent By amorse Date 2006-09-28 Time 07:57 Rev Time 0.00
Received By amorse Date 2006-09-28 Time 07:57 Sent To PC
Notes
2006-09-28 00:00:00 
  
 DENIED
  
 PREVIOUS COMMENTS WERE NOT ADDRESSED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. PLEASE MAKE CORRECTIONS TO
 DRAWINGS BEFORE SUBMITTING TO COUNTY FOR
 IMPACT FEES & STAMP
  
 ***STILL HAS NO IMPACT FEE STAMP AND
 COPY OF RECEIPT****
  
 3) PROVIDE 2 COPIES OF SURVEY
  
 *** SURVEY WAS PROVIDED BUT THE PROPOSED
 ADDITION WAS NOT INDICATED ON THE
 SURVEY***
  
 4) PROVIDE 2 OR MORE SETS OF
 CONSTRUCTION DOCUMENTS WITH PERMIT
 APPLICATION PER 106.1 (2 COPIES OF
 DRAWINGS AND PRODUCT APPROVALS)
  
 ***ONE OLD SET OF DRAWINGS AND ONE NEW
 SET WERE SUBMITTED 2 COPIES OF THE NEW
 DRAWINGS ARE REQUIRED***
  
 5) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 (PRODUCT APPROVALS REQUIRED FOR ROOFING,
 WINDOW, DOOR)
  
 ***ALL PRODUCT APPROVALS ARE INCOMPLETE
 AND MANY DO NOT HAVE THE REQUIRED
 INSTALLATION DOCUMENTS WITH THEM***
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 ***DESIGN PROFESSIONAL HAS NOT REVIEWED
 AND APPROVED THE PRODUCT APPROVALS***
  
 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 9) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. NOTE THAT THERE ARE NO
 MECHANICAL DRAWINGS SUBMITTED
  
 ***ENERGY CALC'S ARE NOT SIGNED BY THE
 OWNER/AGENT***
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-14 Cont ID  
Sent By amorse Date 2006-08-14 Time 13:17 Rev Time 0.00
Received By amorse Date 2006-08-14 Time 13:16 Sent To PC
Notes
2006-08-14 00:00:00 
  
 DENIED
  
 THE FOLLOWING PLAN REVIEW COMMENTS WERE
 NOT ADDRESSED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. PLEASE MAKE CORRECTIONS TO
 DRAWINGS BEFORE SUBMITTING TO COUNTY FOR
 IMPACT FEES & STAMP
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) PROVIDE 2 COPIES OF SURVEY
  
 4) PROVIDE 2 OR MORE SETS OF
 CONSTRUCTION DOCUMENTS WITH PERMIT
 APPLICATION PER 106.1 (2 COPIES OF
 DRAWINGS AND PRODUCT APPROVALS)
  
 5) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 (PRODUCT APPROVALS REQUIRED FOR ROOFING,
 WINDOW, DOOR)
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 8) DESIGN PARAMATER LETTER HAS WHITE
 OUT, THIS IS NOT ACCEPTABLE. PLEASE
 REPRINT WITH CORRECTIONS AND SUBMIT 2
 COPIES (ONE WITH EACH SET OF DRAWINGS)
 OR ADD TO NEW DRAWINGS
  
 9) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. NOTE THAT THERE ARE NO
 MECHANICAL DRAWINGS SUBMITTED
  
 10) DRAWINGS DO NOT ADEQUATELY SHOW THE
 FOLLOWING, WINDOW SILL DETAIL, CEILING
 INSULATION VALUE, MEAN ROOF HEIGHT, TOP
 OF BEAM ELEVATION, FIN. FLOOR ELEVATION
  
 11) PROVIDE ATTIC ACCESS ON DRAWINGS
 PER R807.1
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-05 Cont ID  
Sent By amorse Date 2006-07-05 Time 07:16 Rev Time 1.00
Received By amorse Date 2006-07-05 Time 07:16 Sent To PC
Notes
2006-07-05 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. PLEASE MAKE CORRECTIONS TO
 DRAWINGS BEFORE SUBMITTING TO COUNTY FOR
 IMPACT FEES & STAMP
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC
  
 3) PROVIDE 2 COPIES OF SURVEY
  
 4) PROVIDE 2 OR MORE SETS OF
 CONSTRUCTION DOCUMENTS WITH PERMIT
 APPLICATION PER 106.1
  
 5) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
  
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 8) DESIGN PARAMATER LETTER HAS WHITE
 OUT, THIS IS NOT ACCEPTABLE. PLEASE
 REPRINT WITH CORRECTIONS AND SUBMIT 2
 COPIES (ONE WITH EACH SET OF DRAWINGS)
 OR ADD TO NEW DRAWINGS
  
 9) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. NOTE THAT THERE ARE NO
 MECHANICAL DRAWINGS SUBMITTED
  
 10) DRAWINGS DO NOT ADEQUATELY SHOW THE
 FOLLOWING, WINDOW SILL DETAIL, CEILING
 INSULATION VALUE, MEAN ROOF HEIGHT, TOP
 OF BEAM ELEVATION, FIN. FLOOR ELEVATION
  
 11) PROVIDE ATTIC ACCESSON DRAWINGS
 PER R807.1
  
 12) PROVIDE EMERGENCY EGRESS PER R310.1
 - R310.1.4 FBC: MIN. NET CLEAR OPENING
 OF 5 SQ.FT. ON GRADE FLOOR. MIN. NET
 CLEAR OPENING ALL OTHER FLOORS OF 5.7
 SQ.FT. IN BOTH CASES THE MIN.NET CLEAR
 HEIGHT SHALL BE 24" AND THE NET CLEAR
 WIDTH SHALL BE 20" NOTE THAT NEW WINDOW
 IN MASTER BEDROOM DOES NOT MEET THESE
 REQUIREMENTS
  
 13) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-27 Cont ID  
Sent By dpalmer Date 2007-02-27 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2007-02-27 Time 14:46 Sent To M
Notes
2007-02-27 15:45:28REDLINED 2002 NEC

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-19 Cont ID  
Sent By dpalmer Date 2006-09-19 Time 08:14 Rev Time 0.00
Received By dpalmer Date 2006-09-19 Time 07:43 Sent To M
Notes
2006-09-19 00:00:00********** UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 TWO REVIEWS ARE STILL IN NEED OF
 ADDRESSING.
  
 1) NOTE: PLEASE SEE DEDICATED BATH(S) RM
 CIRCUIT(S) ARE STILL BEING SHOWN A 220V
 ON 2-POLE BREAKERS.
 210.52D,210.11C3
 BOTH PREVIOUS REVIEWS
  
 2) NOTE: PLEASE SEE THE SMALL APPLIACNE
 CIRCUIT IS BEING SHOWN ON A 220V -2-POLE
 BRKR?
  
 3) NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS STILL BEING SHOWN FOR RECEPTS ONLY AS
 NOTED FROM THE 1999 NEC. BOTH PREVIOUS
 REVIEWS.
 PLEASE SEE 210.12 2002 NEC>
  
 4) NOTE: PLEASE SEE ONLY SET OFNEW
 PLANS ARE BEING SUBMITTED.
 PLEASE SEE ONLY ONE NEW AND ONE OLD WAS
 SUBMITTED.
 PLEASE SEE FBC ADMIN SECT 106.1 AS 2 MIN
 ARE REQUIRED ALONG WITH ONE SET OF THE
 OLD/VOIDED PLANS.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE WHICH
 MENTIONED FS 553.80(2)(B) WITH RESPECT
 TO REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW, A 4X FEE HAS NOW BEEN ADDED
 FOR REPEAT COMMENTS. THE FEE FO $960.00
 IS NOW DUE BEFORE RESUBMITTING PLANS.
 PLEASE ALSO KNOW THAT THE 2ND RESUB FEE
 WAS NOT PAID WHEN PLANS WERE RESUBMITTED
 FOR THIS REVIEW AND WAS NOW BEEN ADDED
 AND IS ALSO OWED BEFORE RESUBMITTING
 PLANS.
 PLEASE SEE FS 553.80(2)(B), AS THIS
 WOULD BE REQUIRED FOR EACH TIME IF PLANS
 FAIL FOR ANY REPEAT COMMENTS.
  
 ** NEW NOTES **
  
 6) NOTE: PLEASE SE PANEL SCHEDULE SHOWS
 50A OCP FOR THE 10KW HEAT ON AHU. PLEASE
 VERIFY AS THE CODE IN 424.3B REQUIRES A
 MIN OF 125% FOR OCP.
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 A DEDICATE CIRCUIT FOR OVERHEAD GARAGE
 DOOR, HOWEVER NO GARAGE OR OVERHEAD DOOR
 IS SHOWN ON PLANS???
 PLEASE VERIFY
 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 20:03 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 20:01 Sent To M
Notes
2006-08-07 00:00:00******* UNSAT2ND REVIEW *********
  
 ** NEW NOTE**
  
 1) NOTE: PLEASE SEE THE SAME PLANS WERE
 SUBMITTED BACK FOR REVIEW. PLEASE ALSO
 SEE ONLY ONE SET WAS SUBMITTED.
 FBC 106.1
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 ** PREVIOUS REVIEW NOTES BELOW**
  
 1) NOTE: PELASE SEE MISSIGN EGRESS LT
 AND CONTROL AST REAR OF ADDTION. 210.70,
 LS101 7.8
  
 2) NOTE: PLEASE SEE BATH RM GFI RECEPT
 SHALL BE WITHIN 3' OF THE EDGE OF THE
 SINK, WITHOUT CROSSING OVER THE OTHER
 SINK. THIS SHALL BE DONE BY MOVING THE
 GFI OR ADDING ONE.
 210.52D
  
 3) NOTE: PLEASE SEE THE DEDICATED BATH
 CIRCUIT IS SHOWN AS 220V/2-POLE???
 PLEASE SEE 210.11C3
  
 4) NOTE: PLEASE SEE 250.52,210.70 AS AN
 ENTIRE RECEPT IS BEING SHOWN AS SWITCHED
 IN BEDRM WHICH IS OK, HOWEVER AN
 ADDITIONAL RECEPT WOULD BE REQUIRED TO
 MEET 210.52
 IF THIS IS A 1/2 SW DEVICE, PLEASE
 CHANGE.
  
 5) NOTE: PLEASE SEE ONLY ONE SM APPL
 CIRCUIT IS SHOWN, HOWEVER 3KW LOAD IS
 BEING SHOWN ONTHIS ONE CIR.
 PLEASE SEE 210.52B1,220.16,220.11C1
  
 6) NOTE: PLEASE SEE 210.8A AS THE RECEPT
 LOCATED OUTSIDE REQUIRED BYE 210.52E,
 SHOULD BE GFI.
  
 7) NOTE: PLEASE INDICATE AND SHOW THE
 LAYOUT OF THE REST OF THE DWELLING AS
 SD'S ARE REQ'D INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING RMS.
 R313, NFPA-72 11.5.1.1,11.8.3
  
 8) NOTE: PLEASE SEE PLANS INDICATE THE
 REQ'D ARC FAULT FOR DEVICES FROM THE
 1999 NEC. PLEASE SEE 210.12B 2002, AS
 ARC FAULT PROTECTION IS REQ'D FOR ALL
 NEW OUTLETS IN BEDRMS.
 PLEASE INDICATE THIS ON PANEL SCHEDULE,
 NOT IN A NOTE.
 408.4
  
 9) NOTE: PLEASE INDICATE THE NEW CIRCUIT
 ON PANEL SCHEDULE. 408.4.
 THIS IS THE SAME PANEL SCHEDULE WHICH IS
 BEING SUBMITTED FOR EVERY HOUSE BY THIS
 DRAFTMANS/DESIGNER AND EACH HOUSE SHALL
 BE SPECIFIC TO THAT DWELLING.
 PLEASE REVISE.
  
  
 ** IMPORTANT**
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONLY ONE COPY OF
 THE OLD/VOIDED REMOVED SHEETS SHOULD BE
 SUBMITTED WITH NEW SETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-28 Cont ID  
Sent By dpalmer Date 2006-06-28 Time 07:07 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 19:54 Sent To P
Notes
2006-06-28 00:00:00******* UNSAT *********
  
 1) NOTE: PELASE SEE MISSIGN EGRESS LT
 AND CONTROL AST REAR OF ADDTION. 210.70,
 LS101 7.8
  
 2) NOTE: PLEASE SEE BATH RM GFI RECEPT
 SHALL BE WITHIN 3' OF THE EDGE OF THE
 SINK, WITHOUT CROSSING OVER THE OTHER
 SINK. THIS SHALL BE DONE BY MOVING THE
 GFI OR ADDING ONE.
 210.52D
  
 3) NOTE: PLEASE SEE THE DEDICATED BATH
 CIRCUIT IS SHOWN AS 220V/2-POLE???
 PLEASE SEE 210.11C3
  
 4) NOTE: PLEASE SEE 250.52,210.70 AS AN
 ENTIRE RECEPT IS BEING SHOWN AS SWITCHED
 IN BEDRM WHICH IS OK, HOWEVER AN
 ADDITIONAL RECEPT WOULD BE REQUIRED TO
 MEET 210.52
 IF THIS IS A 1/2 SW DEVICE, PLEASE
 CHANGE.
  
 5) NOTE: PLEASE SEE ONLY ONE SM APPL
 CIRCUIT IS SHOWN, HOWEVER 3KW LOAD IS
 BEING SHOWN ONTHIS ONE CIR.
 PLEASE SEE 210.52B1,220.16,220.11C1
  
 6) NOTE: PLEASE SEE 210.8A AS THE RECEPT
 LOCATED OUTSIDE REQUIRED BYE 210.52E,
 SHOULD BE GFI.
  
 7) NOTE: PLEASE INDICATE AND SHOW THE
 LAYOUT OF THE REST OF THE DWELLING AS
 SD'S ARE REQ'D INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING RMS.
 R313, NFPA-72 11.5.1.1,11.8.3
  
 8) NOTE: PLEASE SEE PLANS INDICATE THE
 REQ'D ARC FAULT FOR DEVICES FROM THE
 1999 NEC. PLEASE SEE 210.12B 2002, AS
 ARC FAULT PROTECTION IS REQ'D FOR ALL
 NEW OUTLETS IN BEDRMS.
 PLEASE INDICATE THIS ON PANEL SCHEDULE,
 NOT IN A NOTE.
 408.4
  
 9) NOTE: PLEASE INDICATE THE NEW CIRCUIT
 ON PANEL SCHEDULE. 408.4.
 THIS IS THE SAME PANEL SCHEDULE WHICH IS
 BEING SUBMITTED FOR EVERY HOUSE BY THIS
 DRAFTMANS/DESIGNER AND EACH HOUSE SHALL
 BE SPECIFIC TO THAT DWELLING.
 PLEASE REVISE.
  
  
 ** IMPORTANT**
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONLY ONE COPY OF
 THE OLD/VOIDED REMOVED SHEETS SHOULD BE
 SUBMITTED WITH NEW SETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2006-06-27 00:00:00PLANS IN ELEC FOR REVIEW, WILL PROCEED
 INTO "F" STATUES, REVIEW TO CONTINUE ON
 6/28

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 16:51 Sent To B
Notes
2008-03-03 16:52:07TO "AMORSE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 10:34 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 10:34 Sent To B
Notes
2007-10-17 10:34:32TO "AMORSE" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 10:15 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 10:15 Sent To B
Notes
2007-05-15 10:15:31TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-02-26 Cont ID  
Sent By adarroug Date 2007-02-26 Time 09:08 Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 09:08 Sent To E
Notes
2007-02-26 09:09:08TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 11:43 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 11:43 Sent To Z
Notes
2007-02-16 11:43:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 09:59 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 09:59 Sent To E
Notes
2006-09-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 14:25 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 14:25 Sent To Z
Notes
2006-09-09 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 14:31 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 14:31 Sent To E
Notes
2006-08-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 13:45 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 13:45 Sent To Z
Notes
2006-08-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 11:00 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 11:00 Sent To E
Notes
2006-06-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-05 Cont ID  
Sent By tgordon Date 2006-07-05 Time 08:20 Rev Time 0.00
Received By tgordon Date 2006-06-21 Time 10:53 Sent To  
Notes
2006-06-21 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2007-02-28 Cont ID  
Sent By tgordon Date 2007-02-27 Time 16:44 Rev Time 0.20
Received By tgordon Date 2007-02-27 Time 16:44 Sent To P
Notes
2007-02-27 16:49:38MECHANICAL PERMIT #06061103 HAS BEEN VOIDED AS NO
 MECHANICAL WORK WILL BE DONE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-09-19 Cont ID  
Sent By tgordon Date 2006-09-19 Time 08:50 Rev Time 0.30
Received By tgordon Date 2006-09-19 Time 08:50 Sent To P
Notes
2006-09-19 00:00:00*** DENIED ***
 1) AS NOTED IN THE PAST TWO REVIEWS
 7-5-06 AND 8-8-06 NO MECHANICAL PLANS
 VERE SUBMITTED FOR REVIEW PLEASE SUBMIT
 MECHANICAL PLANS FOR REVIEW.
  
 PER 2004 FBC CITY OF WPB AMEND. 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS, 106.3.5.4 RESIDENTIAL #10
 MECHANICAL: ENERGY CALCULATIONS,
 EQUIPMENT SCHEDULE, DUCT LAYOUT
 SIZE/GRILL SIZE.
  
 2) SEE ATTACHED NOTICE FS 553.80(2)(B)
 REGARDING FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 08:32 Rev Time 0.20
Received By tgordon Date 2006-08-08 Time 08:32 Sent To P
Notes
2006-08-08 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 7-5-06.
 NO MECHANICAL PLANS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT MECHANICAL PLANS
 FOR REVIEW, OR YOU MAY WISH TO VOID YOUR
 MECHANICAL PERMIT NUMBER SO YOUR
 BUILDING PLANS MAY BY-PASS A MECHANICAL
 REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-05 Cont ID  
Sent By tgordon Date 2006-07-05 Time 08:15 Rev Time 0.20
Received By tgordon Date 2006-07-05 Time 08:15 Sent To  
Notes
2006-07-05 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06061103 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-03-01 Cont ID  
Sent By mperson Date 2007-03-01 Time 11:02 Rev Time 0.33
Received By mperson Date 2007-03-01 Time 11:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-09-22 Cont ID  
Sent By tgordon Date 2006-09-22 Time 15:29 Rev Time 0.33
Received By mperson Date 2006-09-22 Time 16:05 Sent To B
Notes
2006-09-22 00:00:00******DENIED 3RD TIME******
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1, A MINIMUM OF TWO (2) SETS OF
 PRINTS ARE REQUIRED FOR PLAN REVIEW.
 NOTE: ONLY ONE SET OF NEW AND ONE SET OF
 OLD PRINTS WERE SUBMITTED.
  
 2. SEE ATTACHED NOTICE FS 553.80 (2) (B)
 REGUARDING FOUR (4) TIMES THE FEE.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-14 Cont ID  
Sent By mperson Date 2006-08-14 Time 08:03 Rev Time 0.33
Received By mperson Date 2006-08-14 Time 08:02 Sent To B
Notes
2006-08-14 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. THE FOLLOWING INFORMATION IS STILL
 REQUIRED BY PLUMBING PLAN REVIEW DUE TO
 THE FACT THAT THE SAME PLANWAS
 RESUBMITTED WITH NO CORRECTIONS.
 2. ONLY ONE PLAN WAS AGAIN RESUBMITTED,
 NOTE: PER FBC-2004 CHAPTER 1, SECTION
 106.1, TWO (2) SETS OF PLANS REQUIRED.
 3. PLEASE SEE ATTACHED FLORIDA STATUTE
 533.80(2)(B) IN RESPECT WITH REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 **BELOW ARE REPEAT COMMENTS FROM 1ST
 REVIEW**
 4.PER FBC-2004 SEC, 708.3.4 BASE OF
 STACK: A CLEANOUT SHALL BE PROVIDED AT
 THE BASE OF EACH WASTE OR SOIL STACK.
 5. PER FBC-2004 TABLE 906.1: THE MAXIMUM
 DISTANCE OF A 2" TRAP WITH A 2" FIXTURE
 DRAIN IS 6', A RELIEF VENT IS REQUIRED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: PLEASE SEE CORRECTED
 ISOMETRIC SANITARY RISER DIAGRAM ON
 SHEET 2 OF 4 IN RED INK FOR RE REFERENCE
 FOR RESUBMITTAL. ONLY ONE CORRECTED
 DRAWING IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By mperson Date 2006-07-03 Time 09:54 Rev Time 0.45
Received By mperson Date 2006-07-03 Time 09:54 Sent To B
Notes
2006-07-03 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. PER FBC-2004 SEC. 708.3.4 BASE OF
 STACK: A CLEANOUT SHALL BE PROVIDED AT
 THE BASE OF EACH WASTE OR SOIL STACK.
 2. PER FBC-2004 TABLE 906.1: THE MAXIMUM
 DISTANCE OF A 2" TRAP WITH A 2" FIXTURE
 DRAIN IS 6', A RELIEF VENT IS REQUIRED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE CORRECTED ISOMETRIC
 SANITARY RISER DIAGRAM ON SHEET 2 OF 4
 IN RED INK FOR RFEERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2007-02-23 Cont ID  
Sent By adavila Date 2007-02-23 Time 13:34 Rev Time 0.00
Received By adavila Date 2007-02-23 Time 12:36 Sent To I
Notes
2007-02-23 13:35:18PER JOHN ROACH, SENIOR PLANNER.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-09-14 Cont ID  
Sent By mmclean Date 2006-09-14 Time 13:32 Rev Time 0.00
Received By mmclean Date 2006-09-14 Time 13:32 Sent To I
Notes
2006-09-14 00:00:00DENIED,
 1. MUST SHOW THE LOCATION OF THE
 PROPOSED ADDITION ON THE TWO COPY OF
 SURVEY WITH SETBACKS.
 2. THE SURVEY DOES NOT SHOW THE PROPOSED
 WORK OR SETBACKS.
 3. TWO SET OF PLANS MUST BE SUBMITTED
 WITH PERMIT APPLICATION (ONLY ONE
 ORIGNIAL IS SUBMITTED IN PACKAGE).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By mmclean Date 2006-08-05 Time 09:08 Rev Time 0.00
Received By mmclean Date 2006-08-05 Time 09:08 Sent To I
Notes
2006-08-05 00:00:00DENIED, 2ND REQUST.
 1. NEED TO PROVIDE TWO CURRENT COPY
 SURVEY, SHOWING THE PROPOSED ADDITION
 WITH SETBACK.
 2. TWO SET OF PLANS MUST BE SUBMITTED
 WITH PERMIT APPLICATION (ONLY ONE WAS
 SUBMITTED IN PACKAGE).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-24 Cont ID  
Sent By mmclean Date 2006-06-24 Time 09:33 Rev Time 0.00
Received By mmclean Date 2006-06-24 Time 09:33 Sent To I
Notes
2006-06-24 00:00:00DENIED,
 1. NEED TO PROVIDE TWO CURRENT COPY
 SURVEY, SHOWING THE PROPOSED ADDITION
 WITH SETBACK.
 2. TWO SET OF PLANS MUST BE SUBMITTED
 WITH PERMIT APPLICATION (ONLY ONE WAS
 SUBMITTED IN PACKAGE).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720