Plan Review Details - Permit 06061083
Plan Review Stops For Permit 06061083
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-07-27 Cont ID  
Sent By mperson Date 2006-07-27 Time 09:16 Rev Time 0.33
Received By mperson Date 2006-07-27 Time 09:16 Sent To PC
Notes
2006-07-27 00:00:00REVISION: CHANGED GAS METER LOCATION AND
 RUN GALVANIZED PIPE ALONG WALL DELETE
 UNDERGROUND PE.
  
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By mperson Date 2006-06-28 Time 10:51 Rev Time 0.33
Received By mperson Date 2006-06-28 Time 10:51 Sent To PC
Notes
2006-06-28 00:00:00 
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-24 Cont ID  
Sent By adarroug Date 2006-07-24 Time 10:36 Rev Time 0.00
Received By adarroug Date 2006-07-24 Time 10:36 Sent To G
Notes
2006-07-24 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By mperson Date 2006-06-28 Time 10:54 Rev Time 0.00
Received By mperson Date 2006-06-21 Time 10:41 Sent To  
Notes
2006-06-21 00:00:00TO "G" BOX