| 2006-06-23 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)NOTE THAT I AGREED TO EXPEDITE THIS |
| | REVIEW BECAUSE YOU HAD INFORMED ME THAT |
| | THE WINDOWS IN THE HOUSE WERE BROKEN AND |
| | THAT YOU NEEDED TO OCCUPY THE HOUSE. |
| | THIS IS NOT ONLY A WINDOW PERMIT, IT |
| | ALSO INCLUDES ALTERATIONS. |
| | |
| | 2.)NO ANCHOR SCHEDULE PROVIDED ON THE |
| | HURRICANE SHUTTER INSTALLATION SCHEDULE. |
| | REQUIRED TO SHOW CODE COMPLIANCE. |
| | |
| | 3.)FBC EB 501.2, CANNOT REDUCE SAFETY. |
| | FBC R308.4.5, THE WINDOW AT THE TUB IS |
| | TO BE SAFETY GLASS UNLESS YOU CAN |
| | PROVIDE DOCUMENTATION SHOWING THAT THIS |
| | WAS NOT SAFETY GLASS PREVIOUSLY.PLEASE |
| | SCHEDULE A PREINSPECT OF EXISTING |
| | CONDITIONS IF THIS WILL ASSIST IN |
| | DETERMINING SAFETY GLASS REQUIREMENTS. |
| | |
| | 4.)THE APPLICATION CONFLICTS WITH THE |
| | PLAN.THE APPLICATION STATES THAT YOU |
| | ARE REMOVING A KNEE WALL IN THE KITCHEN. |
| | AREA OF DEMOLITION NOT SHOWN ON THE |
| | PLAN. |
| | |
| | 5.)OWNER INFORMATION CONFLICTS WITH |
| | OUR RECORDS.PROVIDE A COPY OF THE DEED |
| | SHOWING PROOF OF OWNERSHIP. |
| | |
| | 6.)OWNER CANNOT GET AN OWNER/BUILDER |
| | PERMIT AS THIS PROPERTY IS RENTED.TO |
| | AVOID A CODE ENFORCEMENT COMPLAINT, |
| | PLEASE APPLY FOR A RENTAL LICENSE |
| | IMMEDIATELY. |
| | |
| | |