Plan Review Details - Permit 06061050
Plan Review Stops For Permit 06061050
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By jwitmer Date 2006-08-09 Time 09:40 Rev Time 2.22
Received By jwitmer Date 2006-08-09 Time 09:40 Sent To PC
Notes
2006-08-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061050
 ADD: 7817 S DIXIE HWY
 CONT: "PLAN REVIEW"
 STATEWIDE PERMITTING:
 TEL: (954)689-6405
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PROVIDE LOCATION (ADDRESS) OF THE
 PROPOSED JOBSITE.
 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 4) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 5) ADDITIONAL INFORMATION 106.1.2* T1
 BUILDING REQUIREMENTS TABLE 602 NOTE# 2,
 LANDLORD IS TO CONSTRUCT A NEW 4 HR
 DEMISSING PARTITION AT THE NORTH SIDE OF
 OFFICE DEPOT.
 THE PROPOSED 4HR RATED WALL IS BEING
 BUILT AS A FIRE WALL SEPERATING
 PROPERTIES, IS THIS PROPERTY BEING
 SEPERATED INTO A SEPERATE LOT? OTHERWISE
 THE NORTHWALL OF OFFICE DEPOT ONLY NEEDS
 TO MEET THE REQUIREMENTS OF 708 FIRE
 PARTITIONS ( TENANT SEPERATION).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-02 Cont ID  
Sent By dpalmer Date 2006-07-02 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2006-07-02 Time 09:59 Sent To  
Notes
2006-07-02 00:00:00*********UNSAT ********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND HAS
 NOT BEEN SUBMITTED FOR PERMIT
 APPLICATION AT THIS TIME.
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT
 THE CURRENT CODES IN EFFECT. PLEASE SEE
 ELECTRICAL PLANS MENTIONS THE "LATEST
 CODES', HOWEVER PLEASE KNOW THE "LATEST
 CODES" 2005 NFPA-70 HAS NOT YET BEEN
 ADOPTEDBY THE STATE OF FLORIDA.
 PLEASE BE SURE ELECTRICAL PLANS LIST THE
 FOLLOWING AT A MIN.
 NFPA-72 2002, NFPA-72 2002, NFPA-101
 2003
 ** PLEASE ALSO SEE COVE SHEETS "T1"
 WHICH MENTIONS THE 2001 FBCFOR
 EXISTING BUILDINS? PLEASE SEE BUILDING
 REVIEW COMMENTS AS THIS SHOULD ALSO BE
 THE 2004 FBC EXISTING BUILDINGS.
 MAY NOT USE SECTIONS FROM DIFFERENT
 CODES.
  
 2) NOTE: PLEASE SEE ENGERGY CALCULATIONS
 SEEMED TO BE SIGNED BY THE SAME
 INDIVIDUAL.
 PLEASE PROVIDE SIGNED, DATED AND SEALED
 NOTORIZED LETTERS FOR THE LEGAL
 SIGNATURES OF EACH ENGINEERS.
 PLEASE KNOW, UNDER FLORIDA STATUES
 471.025, AND FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 NO OTHER INDIVIDUAL MAY
 SIGN AND SEAL DOCUMNETS FOR SOMEONE
 ELSE.
 TWO OF THE SETS ENERGY CALCULATIONS OF
 THE THREE SUBMITTED SETS HAVE BEEN
 RETAINED BY THIS OFFICE. THESE SHALL BE
 RETAINED IN A FILE FOR POSSIBLE REVIEW
 BY THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S AND STATE'S LEGAL COUNSEL TO
 THE BOARD.
  
 3) NOTE: PLEASE SEE "E" SHEETS ARE NOT
 SIGNED, SEALED.PLEASE SEE INFACT THE
 SHEETS CONTAIN AN "X" OVER A MARK OF
 SOME KIND.
 PLEASE SEE ALL SETS SHALL BE SIGNED,
 DATED AND SEALED BY THE SAID DESIGN
 PROFESSIONAL. FS471.025, FAC
 61G15-23.002
  
 4) NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION NMBER FOR ARCHITECTURAL
 FIRM AS REQUIRED UNDERFAC 61G1-16.004,
 FS 481.219.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN SAID TITLE BLOCK.
 THIS IS REQUIRED FOR ALL REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 5) NOTE: PLEASE PROVIDE SCHEDULEING OF
 THE EN MANG SYSTEMS AND TIME OF DAY
 SCHEDULES.
 PLEASE CLARIFY MAX TIME PERMITTED ON
 MANUAL OVER RIDES. PLEASE SEE MANUAL
 "TIMER" TYPES ARE A MAX OF 4HRS AND ANY
 OCCUPANCY SENSOR TYPE OVER RIDE IS
 30MINS.
 PLEASE INDICATE THESE.
 FBC 13-415.1.ABC.1.1, .1.2, .1.3.
  
 6) NOTE: PLEASE PROVIDE MORE DETAIL FOR
 MAX WATTS PER SQ FT/ LIGHTING POWER
 DENSITIES ALLOWED PER 13-415.1.AB.1,
 13-415.2.ABC.1 USING EITHER TABLE
 415.2.C.1,415.2.B.1.
  
 7) NOTE: PELASE CLARIFY EXISTING MAIN
 LOCATION. UNABLE TO VERIFY
 ACCESSIBILITY, GROUPING ETC. AT THIS
 TIME. 230.70,230.72
  
 8) NOTE: IT IS NOTED THAT PROVISIONS FOR
 A "TEMP GENERATOR" IS BEING PROPOSED,
 HOWEVER PLEASE KNOW THE SCENERIO AS
 NOTED ON RISER IS NOT ACCEPTABLE TO THIS
 AHJ. PLEASE SEE 702.6 WHICH REQUIRES
 TRANSFER EQUIPMENT WHICH "WILL NOT"
 PERMIT THE POSSIBILITY OF THE POWER FROM
 TWO SEPARATE SOURCES AT THE SAME TIME.
 "TRANSFER EQUIPMENT SHALL BE SUITABLE
 FOR THE INTENDED USE AND DESIGNED AND
 INSTALLED SO AS TO PREVENT THE
 INADVERTENT INTERCONNECTION OF NORMAL
 AND ALTERNATE SOURCES OF SUPPLY IN ANY
 OPERATION OF THE TRANSFER EQUIPMENT."
 PLEASE ALSO KNOW, THE TERM "QUALIFIED
 PERSONNEL" CAN NOT BE USED AT THIS
 FACILITY DOES NOT CONTAIN 24HR
 "QUALIFIED PERSONNEL". 100.
 PLEASE PROVIDE A MTS, AND PLEASE PROVIDE
 ALL MANUFACTURES SPECS AND CUT SHEETS
 FOR PROPOSED MTS.
  
 9) NOTE: PLEASE SEE THE ADDRESS OF THIS
 PROJECT SHALL BE PLACED IN THE TITLE
 BLOCKS AT THIS TIME. PLEASE SEE THE
 ADDRESS OF "7817" S DIXIE HWY. IS THE
 PROJECT LOCATTION.
 FAC 61G1-16.004
 61G15-23.002
 ** THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 10) NOTE: PLEASE SEE THAT SHOW WINDOW
 RECEPTS LOCATED ABOVE WINDOWS WILL BE
 REQUIRED AT THE SPACING AS SETFORTH IN
 THE NEC. 210.62.
 PLEASE ALSO BE SURE TO ADJUST
 CALCULATIONS AS NEEDED PER 220.12A
  
 ** IMPORTANT**
  
 ONCE ALL REVIEWS ARE DONE AND BEFORE
 RESUBMITTING PLANS FOR REVIEW. PLEASE
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE "COPY/SET" OF THE
 OLD/VOIDED REMOVED SHEETS FOR REFERENCE.
 THIS IS REQUIRED FOR ALL TRADES.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEAVIATE ANY POSSIBLE DELAYS IN THE
 PROCESSING AND REVIEW OF PLANS.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 12:03 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 11:20 Sent To  
Notes
2006-07-11 00:00:001. SUITABLE EXIT SIGNS AND EMERGENCY
 LIGHTS SHALL BE PROVIDED TO ILLUMINATE
 AND IDENTIFY THE MEANS OF EGRESS.
 PLEASE SEE NOTE 6 ON PAGE A3.
  
 2. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS ON THE FLOOR PLAN.
 PLEASE INDICATE TYPE AND SIZE OF THESE.
 PLEASE SEE NOTE # 2 ON PAGE A11.
  
 5. PLEASE INDICATE ON THE PLANS THAT ANY
 DAMAGE TO THE RATED WALLS WILL BE
 REPAIRED TO ENSURE PROPER FIRE RATING.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM MODIFICATIONS.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT.
  
 8. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 9.GASOLINE POWERED DEMOLITION
 EQUIPMENT SHALL NOT BE USED WITHOUT
 PROPER VENTILATION TO AVOID THE RISK OF
 CARBON MONOXIDE BUILD-UP. CARBON
 MONOXIDE IS COLORLESS, ODORLESS, AND
 TASTELSS AND CAN BE DEADLY.
  
 10. ALL LOW VOLATGE SYSTEMS SHALL BE
 INSTALLED AND APPROVED BY THE ELECTRICAL
 DIVISION OF CONSTRUCTION SERVICES.
  
 11. NO COMBUSTIBLE MATERIAL ALLOWED IN
 THE RETURN AIR PLENUM AREAS. SOME AREAS
 HAVE BEEN IDENTIFIED AS RETURN AIR
 PLENUMS ON PAGE E3.
  
 12. PLEASE PROVIDE MORE DETAILS
 REGARDING THE NOTE ON PAGE E5 REGARDING
 TEMPORARY GENERATOR OR MOBILE GENRATOR.
  
 13. FIRE ALARM SYSTEM EQUIPMENT SHALL BE
 CLASS A, STYLE D OR BE FULLY
 ADDRESSABLE. THE FIRE ALARM SYSTEM SHALL
 BE MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE. COMBINATION SYSTEMS
 SHALL COMPLY WITH COMBINATION SYSTEMS
 PER NFPA 72, 2002 EDITION.
  
 PLAN REVIEW ONLY
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-09 Cont ID  
Sent By jwitmer Date 2006-08-09 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2006-06-20 Time 14:49 Sent To PC
Notes
2006-06-29 00:00:00TO "COMM" BD#49
2006-06-20 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By tgordon Date 2006-08-01 Time 08:16 Rev Time 1.45
Received By tgordon Date 2006-08-01 Time 08:16 Sent To  
Notes
2006-08-01 00:00:00FOR PLAN REVIEW AND NOT FOR PERMIT.
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 1-4,
 PLEASE CORRECT.
  
 2) SEE BATHROOM EXHAUST FANS ARE
 REMOVING 250 CFM'S FROM EACH BATHROOM,
 SUPPLY AIR TO EACH BATHROOM IS ONLY
 125-150 CFM'S THIS WILL PUT THE
 BATHROOMS AT A HIGH NEGATIVE PRESSURE,
 ONLY 50 CFM'S EXHAUST PER BATHROOM IS
 REQUIRED.
  
 3) SEE EMPLOYEE LOUNGE EXHAUST FAN
 REMOVING 514 CFM'S, SUPPLY AIR TO ROOM
 IS ONLY 550 CFM'S, IS THIS WHAT YOU WANT
 TO ACCOMPLISH.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-02 Cont ID  
Sent By kstevens Date 2006-08-02 Time 09:18 Rev Time 0.00
Received By kstevens Date 2006-08-02 Time 09:18 Sent To  
Notes
2006-08-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 MECHANICAL
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECURAL DESIGNED SHEET.
 MIMIMUM INFORMATION ON THE TITLE BLOCK
 SHALL INCLUDE THE FIRM LICENSE NUMBER.
 61G1-16.004(2) AND FS 481.219.
  
 2. SHT A5 EMPLOYEE LOUNGE SINK. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. (FORWARD
 APPROACH CLEAR FLOOR SPACE REQUIRED).
  
 3. SHT P2 DETAIL 3, WATER RISER DIAGRAM.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE", NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 4. SHT M1 CONDENSATE SHALL NOT DRAIN TO
 THE ROOF GUTTER. COND. SHALL BE PIPED TO
 THE STORM LINE, CATCH BASIN, DRYWELL, OR
 TO A PLANTED AREA. MECH. SECTION
 307.2.1.
  
 5. SHT M1 THE FOLLOWING REQUIREMENTS
 SHALL BE SUBMITTED FOR THE SEPARATE GAS
 PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 6. SHT M2 DETAIL 8 PIPE SUPPORTS SHALL
 BE INSTALLED TO WITHSTAND 140MPH PER
 FBC-2004. SUPPORTS TO BE LOCATED PER
 TABLE 308.5.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  