| 2006-07-02 00:00:00 | *********UNSAT ******** |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" ONLY AND HAS |
| | NOT BEEN SUBMITTED FOR PERMIT |
| | APPLICATION AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS REFLECT |
| | THE CURRENT CODES IN EFFECT. PLEASE SEE |
| | ELECTRICAL PLANS MENTIONS THE "LATEST |
| | CODES', HOWEVER PLEASE KNOW THE "LATEST |
| | CODES" 2005 NFPA-70 HAS NOT YET BEEN |
| | ADOPTEDBY THE STATE OF FLORIDA. |
| | PLEASE BE SURE ELECTRICAL PLANS LIST THE |
| | FOLLOWING AT A MIN. |
| | NFPA-72 2002, NFPA-72 2002, NFPA-101 |
| | 2003 |
| | ** PLEASE ALSO SEE COVE SHEETS "T1" |
| | WHICH MENTIONS THE 2001 FBCFOR |
| | EXISTING BUILDINS? PLEASE SEE BUILDING |
| | REVIEW COMMENTS AS THIS SHOULD ALSO BE |
| | THE 2004 FBC EXISTING BUILDINGS. |
| | MAY NOT USE SECTIONS FROM DIFFERENT |
| | CODES. |
| | |
| | 2) NOTE: PLEASE SEE ENGERGY CALCULATIONS |
| | SEEMED TO BE SIGNED BY THE SAME |
| | INDIVIDUAL. |
| | PLEASE PROVIDE SIGNED, DATED AND SEALED |
| | NOTORIZED LETTERS FOR THE LEGAL |
| | SIGNATURES OF EACH ENGINEERS. |
| | PLEASE KNOW, UNDER FLORIDA STATUES |
| | 471.025, AND FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002 NO OTHER INDIVIDUAL MAY |
| | SIGN AND SEAL DOCUMNETS FOR SOMEONE |
| | ELSE. |
| | TWO OF THE SETS ENERGY CALCULATIONS OF |
| | THE THREE SUBMITTED SETS HAVE BEEN |
| | RETAINED BY THIS OFFICE. THESE SHALL BE |
| | RETAINED IN A FILE FOR POSSIBLE REVIEW |
| | BY THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEER'S AND STATE'S LEGAL COUNSEL TO |
| | THE BOARD. |
| | |
| | 3) NOTE: PLEASE SEE "E" SHEETS ARE NOT |
| | SIGNED, SEALED.PLEASE SEE INFACT THE |
| | SHEETS CONTAIN AN "X" OVER A MARK OF |
| | SOME KIND. |
| | PLEASE SEE ALL SETS SHALL BE SIGNED, |
| | DATED AND SEALED BY THE SAID DESIGN |
| | PROFESSIONAL. FS471.025, FAC |
| | 61G15-23.002 |
| | |
| | 4) NOTE: PLEASE SEE MISSING CERTIFICATE |
| | OF AUTHORIZATION NMBER FOR ARCHITECTURAL |
| | FIRM AS REQUIRED UNDERFAC 61G1-16.004, |
| | FS 481.219. |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | SHEETS WHICH CONTAIN SAID TITLE BLOCK. |
| | THIS IS REQUIRED FOR ALL REVIEWS WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 5) NOTE: PLEASE PROVIDE SCHEDULEING OF |
| | THE EN MANG SYSTEMS AND TIME OF DAY |
| | SCHEDULES. |
| | PLEASE CLARIFY MAX TIME PERMITTED ON |
| | MANUAL OVER RIDES. PLEASE SEE MANUAL |
| | "TIMER" TYPES ARE A MAX OF 4HRS AND ANY |
| | OCCUPANCY SENSOR TYPE OVER RIDE IS |
| | 30MINS. |
| | PLEASE INDICATE THESE. |
| | FBC 13-415.1.ABC.1.1, .1.2, .1.3. |
| | |
| | 6) NOTE: PLEASE PROVIDE MORE DETAIL FOR |
| | MAX WATTS PER SQ FT/ LIGHTING POWER |
| | DENSITIES ALLOWED PER 13-415.1.AB.1, |
| | 13-415.2.ABC.1 USING EITHER TABLE |
| | 415.2.C.1,415.2.B.1. |
| | |
| | 7) NOTE: PELASE CLARIFY EXISTING MAIN |
| | LOCATION. UNABLE TO VERIFY |
| | ACCESSIBILITY, GROUPING ETC. AT THIS |
| | TIME. 230.70,230.72 |
| | |
| | 8) NOTE: IT IS NOTED THAT PROVISIONS FOR |
| | A "TEMP GENERATOR" IS BEING PROPOSED, |
| | HOWEVER PLEASE KNOW THE SCENERIO AS |
| | NOTED ON RISER IS NOT ACCEPTABLE TO THIS |
| | AHJ. PLEASE SEE 702.6 WHICH REQUIRES |
| | TRANSFER EQUIPMENT WHICH "WILL NOT" |
| | PERMIT THE POSSIBILITY OF THE POWER FROM |
| | TWO SEPARATE SOURCES AT THE SAME TIME. |
| | "TRANSFER EQUIPMENT SHALL BE SUITABLE |
| | FOR THE INTENDED USE AND DESIGNED AND |
| | INSTALLED SO AS TO PREVENT THE |
| | INADVERTENT INTERCONNECTION OF NORMAL |
| | AND ALTERNATE SOURCES OF SUPPLY IN ANY |
| | OPERATION OF THE TRANSFER EQUIPMENT." |
| | PLEASE ALSO KNOW, THE TERM "QUALIFIED |
| | PERSONNEL" CAN NOT BE USED AT THIS |
| | FACILITY DOES NOT CONTAIN 24HR |
| | "QUALIFIED PERSONNEL". 100. |
| | PLEASE PROVIDE A MTS, AND PLEASE PROVIDE |
| | ALL MANUFACTURES SPECS AND CUT SHEETS |
| | FOR PROPOSED MTS. |
| | |
| | 9) NOTE: PLEASE SEE THE ADDRESS OF THIS |
| | PROJECT SHALL BE PLACED IN THE TITLE |
| | BLOCKS AT THIS TIME. PLEASE SEE THE |
| | ADDRESS OF "7817" S DIXIE HWY. IS THE |
| | PROJECT LOCATTION. |
| | FAC 61G1-16.004 |
| | 61G15-23.002 |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND |
| | FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 10) NOTE: PLEASE SEE THAT SHOW WINDOW |
| | RECEPTS LOCATED ABOVE WINDOWS WILL BE |
| | REQUIRED AT THE SPACING AS SETFORTH IN |
| | THE NEC. 210.62. |
| | PLEASE ALSO BE SURE TO ADJUST |
| | CALCULATIONS AS NEEDED PER 220.12A |
| | |
| | ** IMPORTANT** |
| | |
| | ONCE ALL REVIEWS ARE DONE AND BEFORE |
| | RESUBMITTING PLANS FOR REVIEW. PLEASE |
| | REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE ONLY SUBMIT ONE "COPY/SET" OF THE |
| | OLD/VOIDED REMOVED SHEETS FOR REFERENCE. |
| | THIS IS REQUIRED FOR ALL TRADES. |
| | PLEASE KNOW, THIS WILL HELP TO |
| | ALLEAVIATE ANY POSSIBLE DELAYS IN THE |
| | PROCESSING AND REVIEW OF PLANS. |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |