Plan Review Details - Permit 06061005
Plan Review Stops For Permit 06061005
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-09-20 Cont ID  
Sent By mperson Date 2006-09-20 Time 10:25 Rev Time 0.33
Received By mperson Date 2006-09-20 Time 10:25 Sent To  
Notes
2006-09-20 00:00:00REFERENCE: GEN/RES PERMIT #06061002

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-09-01 Cont ID  
Sent By mperson Date 2006-09-01 Time 16:06 Rev Time 0.55
Received By mperson Date 2006-09-01 Time 16:06 Sent To M
Notes
2006-09-01 00:00:00******DENIED 3RD TIME******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW:
  
 1. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). NOTE: THIS INCLUDES THE
 EXISTING BTU LOAD, PLEASE INDICATE THE
 EXISTING BTU LOAD AS WELL AS THE NEW BTU
 LOAD ON THE DRAWING.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). NOTE: THIS
 INCLUDES THE EXISTING SYSTEM AS WELL AS
 THE NEW PROPOSED SYSTEM TO THE
 GENERATOR.
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. NOTE: PLEASE SEE A 4X FEE FOR THE
 PLAN REVIEW PORTION OF THE PERMIT FEE
 HAS NOW BEEN ASSESSED AS REQUIRED PER FS
 553.80(2)(B).
 6. NOTE: PLEASE KNOW THE GAS PERMIT
 APPLICATION WAS NOT IN THE PACKAGE.
 PLEASE BE SURE THE APPLICATION IS
 BROUGHT BACK IN.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By mperson Date 2006-08-03 Time 08:26 Rev Time 0.33
Received By mperson Date 2006-08-03 Time 08:26 Sent To B
Notes
2006-08-03 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW:(NOTE: COM-
 MENTS NOT ADDRESSED FROM PREVIOUS GAS
 PLAN REVIEW)
  
 1. PLEASE CLEARLY INDICATE ON THE
 ISOMETRIC DRAWING IF THE GALVANIZED PIPE
 IS ABOVE GROUND STRAPPED TO THE WALL.
 (NOTE) GALVANIZED PIPE UNDERGROUND IS
 UNACCEPTABLE PER FBC-2004 FUEL GAS, SEC-
 TION 404.8.
 2. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE THI ON THE ISOMETRIC DRAWING.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON
 THE ISOMETRIC DRAWING. (NOTE: IF SYSTEM
 IS 0.5 PSI PIPING IS SIZED WRONG PER
 FBC-2004 TABLE 402.4 (2), SEE ATTACHED
 TABLE FOR REFERENCE FOR RESUBMITTAL.)
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By mperson Date 2006-06-29 Time 08:29 Rev Time 0.33
Received By mperson Date 2006-06-29 Time 08:29 Sent To B
Notes
2006-06-29 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. PLEASE INDICATE ON DRAWING IF
 GALVANIZED PIPE IS ABOVE GROUND ON
 DRAWING, STRAPPED TO THE WALL.
 (NOTE: GALVANIZED PIPE BELOW GROUND IS
 UNACCEPTABLE PER FBC-2004 SEC.404.8)
 2. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE GAS TYPE ON DRAWING.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 (NOTE: IF SYSTEM IS .5 PSI PIPING IS
 SIZED WRONG PER FBC-2004 TABLE 402.4(2),
 SEE ATTACHED TABLE FOR REFERENCE FOR
 RESUBMITTAL)
 4. THE PERSON RESPONSIBLE FOR THE DESIGN
 OF THE PLANS SHALL CLEARLY PRINT AND
 SIGN NAME, AND DATE DRAWING PER FBC-2004
 CHAPTER 1, SECTION 106.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved