Plan Review Details - Permit 06061002
Plan Review Stops For Permit 06061002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-21 Cont ID  
Sent By lmartine Date 2006-09-21 Time 13:01 Rev Time 0.00
Received By lmartine Date 2006-09-21 Time 13:01 Sent To  
Notes
2006-09-19 00:00:00NEW STRUCTURAL ENGINEERING SHEETS,
 SIGNED AND SEALED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 15:06 Rev Time 0.33
Received By alange Date 2006-06-29 Time 16:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-19 Cont ID  
Sent By dpalmer Date 2006-09-19 Time 19:26 Rev Time 0.00
Received By dpalmer Date 2006-09-19 Time 19:08 Sent To  
Notes
2006-09-19 00:00:00OK, STAMPED,
 NEW RTSE WHICH CONTAINS BOTH
 DISCONNECTS.
  
 PLANS HAND ROUTED BACK TO LUIS MARTINEZ.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-27 Cont ID  
Sent By dpalmer Date 2006-08-27 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2006-08-27 Time 11:43 Sent To P
Notes
2006-08-27 00:00:00******* UNSAT3RD REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS WHICH STILL ARE IN NEED OF
 ADDRESSING.
 PLEASE SEE NEW NOTE ADDED.
  
  
 1) NOTE: OK.
  
 2) NOTE: NO, SAME NOTE>, SPEC SHOW MORE
 THAN ONE ATS.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW **
 SAME, PLEASE BE SURE TO HIGH-
 LIGHT UNIT.
  
 ** PREVIOUS REVIEW NOTE1ST REVIEW **
 PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAINING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 PLEASE "HIGHLIGHT" THE ATS.
 230.70,230.76,230.79
  
 3) NOTE: NO, PLEASE SEE NO DISCONNECT IS
 BEING SHOWN AND GROUPED WITH THE NEW
 MAIN. **PLEASE SEE THAT GENERAC NOW
 MAKES A SE RATED ATS WHICH MEETS CODE
 COMPLIANCE FOR THE THE DISCONNECITNG OF
 THE FPL POWER AND THE FEEDERS FROM THE
 GEN. (RTSE WHICH CONTAINS TWO-200A
 BREAKERS) THIS IS ONLY NOTED AS THE RTSE
 IS NOT THE ONLY WAY TO MEET CODE
 COMPLIANCE FOR THE DISCONNETING OF
 FEEDERS.225.34, 230.72
 THE BREAKER INSIDE THE GEN CAN NOT BE
 USED AS IT DOES NOT MEET CODEAND THE
 ATS SUBMITTED ONLY DISCONNECTS THE POWER
 FROM FPL. THE TOGGLE SWITCH IN THIS TYPE
 OF ATS DOE NOT MEET CODE FOR DISCONNECT
 RATED FOR THE LOAD SERVED.
  
 ** PREVIOUS REVIEW NOTES 2ND REVIEW **
 SAME, PLEASE SEE NO DISCONNECT
 SHOWN.
 ** PLEASE KNOW, GENERAC NOW HAS A NEW SE
 RATED ATS ON THE MARKET WHICH WOULD MEET
 THIS AS IT CONTAINS A MANUAL MEANS OF
 DISCONNECT FOR THE NORMAL (FPL) SIDE AND
 THE EM/GEN FEEDER SIDE. THIS IS NO WAY
 SAYING THIS NEW UNIT HAS TO BE USED.
 THIS ONLY REQUIRES A DISCONNECTING MEANS
 AND DOES NOT REQUIRED OCP. CAN BE A
 KNIFE TYPE SWITCH ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN GROUPED WITH NEW
 MAIN. BRKR INSIDE GEN MAY NOT SERVE AS
 THIS DISCONNECT MEANS
 225.31-225.39
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 SAME, PLEASE SEE ABOVE NOTE
 WITH RESPECT TO THE ATS BEING INSTALLED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 ** NEW NOTES **
  
 11) NOTE: PLEASE SEE A 4X FEE FOR THE
 PLAN REVIEW PORTION OF THE PERMIT FEE
 HAS NOW BEEN ASSESSED AS REQUIRED PER FS
 553.80(2)(B). PLEASE KNOW THE FEE OF
 $520.68 IS DUE BEFORE PLANS MAY BE
 RESUBMITED.
  
 12) NOTE: PLEASE KNOW THE PERMIT
 APPLICATION WAS NOT IN PACKAGE. PLEASE
 BE SURE THE APPLICATION IS BROUGHT BACK
 IN. PLEASE ALSO BE SURE THAT THE
 ELECTRICLA PERMIT LINE IS SIGNED SO AN
 ELECTRICAL PERMIT (GEN-ELEC) PERMIT
 NUMBER CAN BE GENERATED FOR THE
 ELECTRICALPORTION OF THE GENERATOR
 INSTALLATION.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2006-08-03 Time 14:44 Sent To B
Notes
2006-08-03 00:00:00******* UNSAT2ND REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL ARE IN NEED OF
 ADDRESSING.
  
  
 1) NOTE: OK.
  
 2) NOTE:SAME, PLEASE BE SURE TO HIGH-
 LIGHT UNIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAINING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 PLEASE "HIGHLIGHT" THE ATS.
 230.70,230.76,230.79
  
 3) NOTE: SAME, PLEASE SEE NO DISCONNECT
 SHOWN.
 ** PLEASE KNOW, GENERAC NOW HAS A NEW SE
 RATED ATS ON THE MARKET WHICH WOULD MEET
 THIS AS IT CONTAINS A MANUAL MEANS OF
 DISCONNECT FOR THE NORMAL (FPL) SIDE AND
 THE EM/GEN FEEDER SIDE. THIS IS NO WAY
 SAYING THIS NEW UNIT HAS TO BE USED.
 THIS ONLY REQUIRES A DISCONNECTING MEANS
 AND DOES NOT REQUIRED OCP. CAN BE A
 KNIFE TYPE SWITCH ETC.
  
 ** PREVIOUS REVIEW NOTE ** PLEASE SEE
 MISSING DISCONNECT
 FOR FEEDERS FROM GEN GROUPED WITH NEW
 MAIN. BRKR INSIDE GEN MAY NOT SERVE AS
 THIS DISCONNECT MEANS
 225.31-225.39
  
 4) NOTE: OK.
  
 5) NOTE: SAME, HOWEVER PLEASE SEE A NEW
 SURVEY IS NOW SHOWN. IF NOT USING THE
 ODL ONE, PLEASE REMOVE FROM SETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SITE SURVEY SEEMS TO
 INDICATE "EASTVIEW ELEC" ?? PLEASE
 CLARIFY AND KNOW THAT ALL PLANS AND
 PAPERWORK UNDER DARRYL SCHMIDT ELEC
 SHALL BE SO STATED.
 PLEASE SEE THAT ALL PLANS/DESIGNS
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE ELECTRICAL CONTRACTOR WHO IS
 RESPONSIBEL FOR SAID
 DESIGNS.106.1.2,106.3.4.3
  
 6) NOTE:OK.
  
 7) NOTE: ** OK, VALUE WAS CHANGED ON
 APPLICATION AND FEES ARE OWED BEFORE
 PERMIT CAN BE ISSUED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE VALUE ON PERMIT
 APPLICATION SHALL INCLUDE ALL LABOUR AND
 MATERIALS EVEN IF ANY
 MATERIALS/EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE THIS WOULD ALSO INCLUDE THE
 VALUE OF THE GAS WORK AS THE GAS
 CONTRACTOR IS SIGNED ON.
 ** PLEASE KNOW, IF AN APPROPRIATE VALUE
 IS NOT STATED, THEN ONE WILL BE ADJUSTED
 BY THIS OFFICE USING THE "MARSHALL'S&
 SWIFT " GUIDE AS ADOPTED BY THE FBC
 ADMINISTRATIVE SECTION 108.3
  
 8) NOTE: SAME, PLEASE SEE ABOVE NOTE
 WITH RESPECT TO THE ATS BEING INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 18:02 Sent To M
Notes
2006-06-23 00:00:00******* UNSAT ********
  
  
 1) NOTE: PLEASE SEE THAT AN "EQUIPMENT
 GROUNDING CONDUCTOR" SHALL NOT BE
 INSTALLED UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE
 250.6,250.24B,250.122.
  
 2) NOTE: PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAINING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 PLEASE "HIGHLIGHT" THE ATS.
 230.70,230.76,230.79
  
 3) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN GROUPED WITH NEW
 MAIN. BRKR INSIDE GEN MAY NOT SERVE AS
 THIS DISCONNECT MEANS
 225.31-225.39
  
 4) NOTE: PLEASE INDICATE THE OCP AT GEN
 ON RISER AND PLEASE SHOW GEN.
 215.5.
  
 5) NOTE: PLEASE SEE SITE SURVEY SEEMS TO
 INDICATE "EASTVIEW ELEC" ?? PLEASE
 CLARIFY AND KNOW THAT ALL PLANS AND
 PAPERWORK UNDER DARRYL SCHMIDT ELEC
 SHALL BE SO STATED.
 PLEASE SEE THAT ALL PLANS/DESIGNS
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE ELECTRICAL CONTRACTOR WHO IS
 RESPONSIBEL FOR SAID
 DESIGNS.106.1.2,106.3.4.3
  
 6) NOTE: PLEASE SEE THAT THE GEN
 LOCATION STILL NEEDS TO BE VERIFIED.
 ALL CLEARENCES SHALL BE INDICATED FROM
 HOUSE, WALL, ETC
 PLEASE SEE MECH COMMENTS AND PLEASE ALSO
 BE SURE THE MANUFACTURES SPECS/CUT
 SHEETS INCLUDE THE MIN CLEARENCES AROUND
 EQUIPMENT.
 215.5
  
 7) NOTE: PLEASE SEE THE VALUE ON PERMIT
 APPLICATION SHALL INCLUDE ALL LABOUR AND
 MATERIALS EVEN IF ANY
 MATERIALS/EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE THIS WOULD ALSO INCLUDE THE
 VALUE OF THE GAS WORK AS THE GAS
 CONTRACTOR IS SIGNED ON.
 ** PLEASE KNOW, IF AN APPROPRIATE VALUE
 IS NOT STATED, THEN ONE WILL BE ADJUSTED
 BY THIS OFFICE USING THE "MARSHALL'S&
 SWIFT " GUIDE AS ADOPTED BY THE FBC
 ADMINISTRATIVE SECTION 108.3
  
 8) NOTE: PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: PLEASE INCLUDE ALL CONDUCTORS
 IN RACEWAYS, INCLUDING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.24B,250.122,240.4,310.16
  
 10) NOTE: PLEASE PROVIDE A LAYOUT FOR
 ALL EQUIPMENT AND LOCATIONS AT DWELLING.
 PLEASE SEE ATS DOES NOT INDICATE FEED TO
 WHAT IS ASSUMED TO BE AN EXISTING PANEL
 SOMEWHERE.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-09-20 Cont ID  
Sent By mperson Date 2006-09-20 Time 10:05 Rev Time 0.33
Received By mperson Date 2006-09-20 Time 10:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-09-01 Cont ID  
Sent By mperson Date 2006-09-01 Time 16:48 Rev Time 0.00
Received By mperson Date 2006-09-01 Time 16:48 Sent To M
Notes
2006-09-01 00:00:00REFERENCE: GAS PERMIT #06061005

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By mperson Date 2006-08-03 Time 09:14 Rev Time 0.00
Received By mperson Date 2006-08-03 Time 09:14 Sent To B
Notes
2006-08-03 00:00:00REFERENCE: GAS PERMIT #06061005

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By mperson Date 2006-06-29 Time 08:21 Rev Time 0.00
Received By mperson Date 2006-06-29 Time 08:21 Sent To B
Notes
2006-06-29 00:00:00NOTE: REFERENCE GAS PERMIT APPLICA-
 TION #06061005 FOR DENIED COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 13:50 Sent To Z
Notes
2006-09-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 14:05 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 14:05 Sent To E
Notes
2006-08-24 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 16:03 Sent To Z
Notes
2006-08-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 15:44 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 15:44 Sent To Z
Notes
2006-08-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 10:02 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 10:02 Sent To E
Notes
2006-06-23 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-11 Cont ID  
Sent By rbrown Date 2006-06-29 Time 12:53 Rev Time 0.00
Received By rbrown Date 2006-06-20 Time 09:34 Sent To  
Notes
2006-06-20 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-20 Cont ID  
Sent By tgordon Date 2006-09-20 Time 10:40 Rev Time 0.15
Received By tgordon Date 2006-09-20 Time 10:40 Sent To B
Notes
2006-09-20 00:00:00RETURNED TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-09-05 Cont ID  
Sent By tgordon Date 2006-09-05 Time 08:16 Rev Time 0.15
Received By tgordon Date 2006-09-05 Time 08:16 Sent To  
Notes
2006-09-05 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL AND GAS REVIEW
 NOTES AND CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-03 Cont ID  
Sent By tgordon Date 2006-08-03 Time 11:09 Rev Time 0.15
Received By tgordon Date 2006-08-03 Time 11:09 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 15:34 Rev Time 0.15
Received By tgordon Date 2006-06-26 Time 15:34 Sent To P
Notes
2006-06-26 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 5 Status P Date 2006-09-18 Cont ID  
Sent By mmclean Date 2006-09-18 Time 17:03 Rev Time 0.00
Received By mmclean Date 2006-09-18 Time 17:03 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-08-23 Cont ID  
Sent By mmclean Date 2006-08-23 Time 18:01 Rev Time 0.00
Received By mmclean Date 2006-08-23 Time 18:01 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-08-03 Cont ID  
Sent By lmartine Date 2006-08-03 Time 15:45 Rev Time 0.00
Received By lmartine Date 2006-08-03 Time 15:45 Sent To  
Notes
2006-08-03 00:00:00SUBMIT PREVIOUSLY APPROVED
 SURVEYS/SITEPLANS
  
  
  
 L.MARTINEZ
 805-6710

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-22 Cont ID  
Sent By mmclean Date 2006-06-22 Time 16:06 Rev Time 0.00
Received By mmclean Date 2006-06-22 Time 16:06 Sent To I
Notes
2006-06-22 00:00:00NOTE: GENERATOR WILL BE 3.6FT FROM SIDE
 PROPERTY LINE AND MUUST BE LANDSCAPE
 BUFFER AROUND GENERATOR.
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By mmclean Date 2006-06-22 Time 10:42 Rev Time 0.00
Received By mmclean Date 2006-06-22 Time 09:50 Sent To I
Notes
2006-06-22 00:00:00NOTE: WAITING FOR HOA APPROVAL & SETBACK
 INFORMATION.WILL BE FAXED TODAY.
 CALLED TO CLARIFY ON THE SETBACK, LEFT
 MSG.
 DENIED,
 1. MUST PROVIDE COPY OF THE HOA APPROVAL
 FOR THE GENERATOR
 2. THE PROPOSED GENERATOR WILL BE 4.6FT
 FROM SIDE PROPERTY LINE.
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  