Plan Review Details - Permit 06061001
Plan Review Stops For Permit 06061001
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-08-07 Cont ID  
Sent By mperson Date 2006-08-07 Time 10:40 Rev Time 0.33
Received By mperson Date 2006-08-07 Time 10:40 Sent To PC
Notes
2006-08-07 00:00:00REFERENCE GEN/RES #06020625

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By mperson Date 2006-06-27 Time 13:36 Rev Time 0.45
Received By mperson Date 2006-06-27 Time 13:36 Sent To PC
Notes
2006-06-27 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PLEASE SEE SAMPLE OF
 ISOMETRIC DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PLEASE SEE SAMPLE ISOMETRIC DRAWING IN
 RED INK FOR REFERENCE OF THE ABOVE.
 3. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE THIS ON DRAWINGS.
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 6. IF GAS SYSTEM IS A 2LB SYSTEM PLEASE
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT(REGULATORS) TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA
 58, AND THE FBC-2004 FUEL GAS CODE SEC
 402.2.
 7. PER FBC-2004, CHAPTER 1 SECTION 106.
 THE PERSON RESPOSIBLE FOR THE DRAWING
 SHALL PRINT AND SIGN NAME, AND DATE
 DRAWING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-28 Cont ID  
Sent By adarroug Date 2006-07-28 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-07-28 Time 15:09 Sent To G
Notes
2006-07-28 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-28 Cont ID  
Sent By adarroug Date 2006-06-27 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:47 Sent To  
Notes
2006-06-19 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved