Plan Review Details - Permit 06060994
Plan Review Stops For Permit 06060994
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 15:36 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 15:36 Sent To PC
Notes
2006-07-07 00:00:00REDLINED 230.70

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 07:20 Sent To PC
Notes
2006-06-23 00:00:00******** UNSAT **********
  
  
  
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SEE POSSIBLE "REAR" GFI
 RECEPT.
  
 3) NOTE: PLEASE SEE MISSING CU ON PLANS
 ALONG WITH DISCONNECT,AND GFI RECEPT.
 ONE GFI RECEPT IS SHOWN ON THE SIDE OF
 HOUSE, BUT NOT CLEAR WHERE CU IS GOING
 TO BE.
 440.11,210.63,210.8A
  
 4) NOTE: PLEASE SEE RISER SHOWS AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER TO MAIN/FIRST MEANS OF DISC.
 PLEASE SEE 250.6,250.24B, THE EGC IS
 ONLY INSTALED AFTER THE FIRST MEANS OF
 DISC.
  
 5) NOTE: PLEASE SEE 230.70, AS NO MORE
 THAN 8' OF UNPROTECTED CONDUCTORS ARE
 PERMITTED INSIDE THE DWELLING. PLEASE
 INDICATE HOW NEW CONDUIT OF THE SEC'S IS
 BEING ROUTED INTO PANEL. AS THIS IS AN
 EXISTIGN HOUSE, A MAIN WITH OCP MAY BE
 REQUIRED OUTSIDE.
 IF THIS IS DONE, THEN PLEASE DISREGARD
 NOTE #4.
  
 6) NOTE: PELASE SEE MISSING CWP AS PART
 OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 7) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU TO BE 125%.
 (MIN 60A).
  
 8) NOTE: PLEASE SEE MISSING LT FOR AHU
 210.70
  
 9) NOTE: PLEASE CLARIFY OF DINING RM
 CIRCUIT IS DEDICATED TO ONE OR MORE OF
 THE SM APPLIANCE CIRCUITS.
 PLEASE SEE 210.52B1,210.11,220.16, AS
 THE DINING RM MAY NOT BE ON 15A/GEN LT
 CIRCUIT(S).
  
 10) NOTE: PLEASE SEE RECEPT IN BATH IS
 REQ'D TO BE GFI.
 210.8A2
  
 ** PLEASE KNOW A RECORDED NOC WILL BE
 REQUIRED BEFORE PICKING UP PERMIT.
 FS713.13
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 08:22 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 08:22 Sent To E
Notes
2006-07-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-23 Time   Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 16:10 Sent To  
Notes
2006-06-19 00:00:00TO "E" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved