Plan Review Details - Permit 06060985
Plan Review Stops For Permit 06060985
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-04 Cont ID  
Sent By mjacobs Date 2006-07-04 Time 09:05 Rev Time 0.00
Received By mjacobs Date 2006-07-04 Time 08:28 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 13:35 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 13:25 Sent To PC
Notes
2006-07-23 00:00:00**** REDLINED PLANS ***
  
 ENGINEER NOTED AND DATED PLANS,PLANS
 ARE NOTED AS PANEL BEING EXISTING,
 HOWEVER THIS IS TO BE VERIFIED IN FIELD.
 IF POOL PANEL IS NEW, THEN PLANS SHALL
 BE REVISED WITH INFORMATION AS
 PREVIOUSLY REQUESTED.
  
 ENG ALSO CHANGED THE #10 AWG FOR PUMP TO
 #12 AWG.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 19:40 Sent To P
Notes
2006-06-27 00:00:00***** UNSAT ***
  
 1) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM EXISTING
 SERVICE TO NEW PANEL.
 250.110,250.122, 680.6
  
 2) NOTE: PLEASE PROVIDE LOAD
 CALCULATIONS AND PANEL SCHEDULE OF
 EXISTING SERVICE WHICH INDICATE THE NEW
 OCP FOR POOL PANEL AND NEW LOAD ADDED TO
 EXISTING LOAD.
 408.4,220.31
 ** PLEASE KNOW, THIS MAY BE PROVIDED BY
 THE ELECTRICAL CONTRACTOR AND IS NOT
 REQUIRED BY CURTIS- SINCLAIR.
  
  
 3) NOTE: PLEASE VERIFY 3-#10'S TO 1HP
 POOL PUMP. *THIS IS OK, HOWEVER VERIFY
 AS IF PLANS INDICATE #10, THEN THESE
 WILL BE REQUIRED.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 11:22 Sent To  
Notes
2006-07-21 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 11:16 Sent To E
Notes
2006-06-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-04 Time   Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 16:09 Sent To  
Notes
2006-06-19 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By mperson Date 2006-06-28 Time 13:56 Rev Time 0.33
Received By mperson Date 2006-06-28 Time 13:56 Sent To B
Notes
2006-06-28 00:00:00NOTE: PLUMBING PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-25 Cont ID  
Sent By mmclean Date 2006-06-25 Time 14:06 Rev Time 0.00
Received By mmclean Date 2006-06-25 Time 14:06 Sent To I
Notes
2006-06-25 00:00:00NOTE:
 THE PROPOSED POOL EQUIPMENT SHALL NOT BE
 CLOSER THAN 4'3 FROMSIDE PROPERTY
 LINE.
 NOTE: THE PROPOSED POOL/DECK IS BEYOND
 THE 25FT FRONT SETBACK (AS SHOWN ON
 SURVEY)
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.