| 2006-06-20 00:00:00 | *********** UNSAT ************** |
| | |
| | ** PLEASE SEE 2002 NEC, NFPA-72 2002 |
| | |
| | |
| | 1) NOTE: PLEASE SEE MIN VA FOR SMALL |
| | APPLIANCES SHALL BE PER 210.11C1,220.16 |
| | |
| | 2) NOTE: PLEASE SEEM MIN VA FOR DRYER TO |
| | BE PER 220.18 |
| | |
| | 3) NOTE: PLEASE SEE |
| | 210.52B1,210.11,220.16 FOR DINING AREA |
| | RECEPTS TO BE ON ONE OR MORE OF THE |
| | REQUIRED DEDICATED SM APPL BRANCH |
| | CIRCUITS. |
| | |
| | 4) NOTE: PLEASE SEE 2002 NEC 210.12B FOR |
| | REQUIRED ARC FAULT PROTECTION REQUIRED. |
| | NOTES ON PLANS MENTIONS RECEPTS, HOWEVER |
| | ALL OUTLETS IN BEDRMS REQUIRE |
| | PROTECTION, NOT ONLY RECEPTS. |
| | |
| | 5) NOTE: PLEASE SEE MISSING SD'S |
| | REQUIRED PER NFPA-72 11.5.1.1,11.8.3.5. |
| | PLEASE SEE MISSING INSIDE AND OUTSIDE |
| | ALL SLEEPING RMS. PLEASE ALSO SEE TYPE |
| | OF SD'S WHICH ARE REQUIRED WHEN |
| | INSTALLED WITHIN 20' OF COOKING |
| | APPLIANCES. |
| | |
| | 6) NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROL AND LT FIXTURE PER |
| | 210.70, LS101 7.8 |
| | (LAUNDRY RM). |
| | |
| | 7) NOTE: PLEASE SEE MISSING GFI RECEPT |
| | FOR CU. PER 210.63,210.8 |
| | |
| | 8) NOTE: PLEASE SEE PLANS SHALL INDICATE |
| | THE CURRENT CODES. 2002 NFPA-70, 2002 |
| | NFPA-72, 2003 NFPA-101 |
| | |
| | 9) NOTE: PLEASE CLARIFY USE OF RECEPT IN |
| | WIC IN MAST BEDRM. |
| | PLEASE KNOW, THIS IS A RECEPT TO PLUG IN |
| | ANY TYPE OF LV TRANSFORMER, THEN THE |
| | RECEPT SHALL NOT BE PLACED IN LOCATION |
| | OF STORAGE OR SHELVING. THE RECEPT MAY |
| | BE PLACED ABOVE DOOR. |
| | 240.24, 110.26 |
| | |
| | 10) NOTE: PLEASE SEE PLANS INDICATE A |
| | NEW RISER SERVICE , YET NOTE BELOW LOAD |
| | CALCULATIONS MENTIONS EXISTING?? |
| | PLEASE CLARIFY |
| | 215.5 |
| | |
| | 11) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 12) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN DISC TO |
| | PANEL. |
| | 250.110,250.24B,250.122 ETC |
| | |
| | 13) NOTE: PLEASE SEE GROUNDING RISER |
| | SHOWS THE GEC GOING TO FOOTER/FOUNDATION |
| | STEEL? PLEASE KNOW, ON AN EXISTING OLDER |
| | BUILDING THIS IS NOT REQUIRED, HOWEVER |
| | IF SHOWN ON RISER THEN IT WILL BE |
| | REQUIRED. |
| | PLEASE KNOW, IN EXISTING BLDGS, THERE |
| | MAY OR MAY NOT BE FOOTER STEEL, AND TO |
| | CAN BE MORE DETRIMENTAL TO THE |
| | STRUCTURAL INTEGRITY OF AN EXISTIGN |
| | BUILDING TO DO SO. |
| | 250.50,215.5 |
| | |
| | 14) NOTE: PLEASE SEE 424.3B,240.4,310.16 |
| | FOR MIN SIZE FOR OCP AND MIN AWG FOR THE |
| | AHU AND THE 10KW LOAD SHOWN. |
| | MININUM OCP SHALL BE 125% AND CONDUCTOR |
| | SIZES SHALL BE ADJUSTED ACCORDINGLY. |
| | |
| | 15) NOTE: PLEASE SEE WATER HEATER IS |
| | SHOWING 5400VA ON 2-POLE 20A BRKR. |
| | PLEASE SEE MIN OCP SHALL BE 125%,PLEASE |
| | ADJUST OCP AND AWG. |
| | 422.13, 240.4, 310.16 |
| | |
| | 16) NOTE: PLEASE SEE 408.4 AS PANEL |
| | SCHEDULE SHALL BE SPECIFIC TO CICUITING |
| | OF AREAS AND ROOMS. |
| | |
| | 17) NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES A 26 CIR PANEL. PLEASE KNOW, |
| | THIS NOT A COMMON SIZE AND VERIFICATION |
| | SHOULD BE MADE AND PANEL SHOULD BE |
| | CORRECTED. |
| | 215.5 |
| | |
| | 18) NOTE: PLEASE SUBMIT MIN LOAD |
| | CALCULATIONS PER 220 OF THE NEC 2002 |
| | 215.5 |
| | |
| | 19) NOTE: PLEASE SEE RISER SHOWS NEW |
| | OVER HEAD AND NEW UNDER GROUND FROM FPL. |
| | PLEASE SEE THAT ONE OR OTHER SHOULD BE |
| | INDICATED. |
| | THIS CAN BE REVISED AT A LATER DATE IF |
| | IT IS CHANGED. |
| | 215.5 |
| | |
| | 20) NOTE: PLEASE SEE THE LIGHTING |
| | CONTROL FOR THE LIGHTS IN THE MASTER |
| | BEDRM SHOULD BE AT NEAREST POINT OF |
| | ENTRANCE TO THE BEDRM. SHOWN ON THE |
| | OTHER SIDE OF THE RM AWAY FROM THE |
| | ENTRANCE DOOR.?? |
| | PLEASE ALSO SEE THE SW FOR MAST BATH IS |
| | OUTSIDE THE BATHRM, WHERE THE SW |
| | LOCATION IS REQUIRED INSIDE. |
| | LS 101 7.8, 210.70 |
| | |
| | 21) NOTE: PLEASE VERIFY CIRCUITING SHOWN |
| | FOR LIGHTING AS THE FRONT PORCH LT IS |
| | BEING SHOWN ON A DEDICATE LT CIRCUIT, |
| | AND THE REST OF THE ENTIRE HOSUE IS |
| | SHOWN ON ONE CIRCUIT??? |
| | PLEASE SEE 220 FOR MAX VA PERMITED ON |
| | ONE CIRCUIT, PLEASE SEE A MAX OF 1440VA. |
| | 240.4,310.16 ETC. |
| | 215.5 |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |