Plan Review Details - Permit 06060968
Plan Review Stops For Permit 06060968
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-29 Cont ID  
Sent By lmartine Date 2006-06-29 Time 16:58 Rev Time 0.00
Received By lmartine Date 2006-06-29 Time 16:58 Sent To  
Notes
2006-06-29 00:00:00 
  
 PROVIDE ENHANCED FASTENING FOR REVIEW
 BEFORE METAL INSPECTION
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By shill Date 2006-06-19 Time 11:52 Rev Time 0.00
Received By shill Date 2006-06-19 Time 11:52 Sent To  
Notes
2006-06-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE DESIGN PRESSURES ON SHEET S0.2
 ARE THE SAME FOR THE FLAT DECK AND FOR
 THE 5/12 PITCHED ROOF.IS THIS CORRECT?
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.PLEASE
 PRINT THE PRODUCT APPROVAL COVER SHEETS
 FOR EACH PRODUCT.
 WWW.FLORIDABUILDING.ORG
  
 3.)ENHANCED FASTENING FOR PERIMETER
 AND CORNER ZONES ARE TO BE PREPARED BY A
 DESIGN PROFESSIONAL ACCORDING TO BOTH
 PRODUCT APPROVALS.SEE LIMIATION 7 FOR
 THE FLAT DECK, LIMITATION 1 FOR THE
 METAL.