| 2006-10-01 00:00:00 | ***UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH STILL ARE IN NEED OF |
| | ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THIS IS A DIESEL |
| | GENERATOR AND THIS UNIT IS BEING SHOWN |
| | TOO CLOSE TO TO THE BUILDING AS SHOWN |
| | FOR MIN CLEARENCES REQUIRED. PLEASE SEE |
| | THERE WILL BE MECHANICAL COMMENTS. THE |
| | 10FT OR MIN MIN FOR DIESEL FUEL TYPE IF |
| | FROM ALL OPENINGS, NOT ONLY WINDOWS. |
| | (SOFFIT ETC0. PLEASE SEE DUE TO THE 10FT |
| | SETS BACK AND THE MIN REQUIRED FROM |
| | PROPERTY LINE , FROM BUILIDING, AND THE |
| | WITH OF THE GEN, A NEW LOCATION MUST BE |
| | PROPOSED. |
| | PLEASE SEE NO INFORMATION FROM |
| | MANUAFATURE WAS SUBMITTED WHICH |
| | INDICATES THE MIN REQUIRED CLEARENCE ALL |
| | THE WAY AROUND UNIT. IT IS KNOWN FROM |
| | THIS MANUFACTURE , TYPICALLY IS REQUIRES |
| | 3FT (MIN) SOME ARE 5FT). |
| | WITH THAT SAID, IF THE GEN IS 3FT FROM |
| | HOUSE AND ZONING DOES NOT PERMIT THIS |
| | UNIT CLOSER THAT 6',1" FROM PROPOERTY |
| | THIS WILL NOT WORK. |
| | |
| | |
| | ** PLEASE KNOW, SITE SURVEY AS STAMPED |
| | FROM ZONING HAS BEEN "VOIDED". |
| | |
| | 2) NOTE: PLEASE COMPLETE RISER DIAGRAM. |
| | AS SHOWN, THERE SEEM TO BE A SUB PANEL |
| | WHICH IS BEING FED FROMTHE EXISTING |
| | 200A PANEL, THROUGH THE ATS, YET THIS IS |
| | NOT SHOWN ON RISER, WITH CONDUCTORS ETC. |
| | PLEASE SEE MISSING CONDUIT, EQUIPMENT |
| | GROUNDING CONDUCTORS, ETC. |
| | PLEASE PROVIDE A COMPLETE OVERVIEW OF |
| | ALL EQUIPMENT AND LOCATIONS. |
| | PLEASE KNOW, AS PER 225.31-225.39, AND |
| | WHAT HOW THE 2005 (FUTURE) CODE INTENDS, |
| | THE BRKR ON THE GEN MUST BE WITH |
| | INSIGHT, READILY ACCESSIBLE, AND THER |
| | MUST BE A DEADFRONT WHEN ACCESSING THE |
| | GEN. 110.27. |
| | SIGNAGE FOR ALL WILL ALSO BE REQUIRED AS |
| | THESE DISONNECTING MEANS ARE NOT |
| | GROUPED. |
| | 225.34,230.72,230.2,702.8 ETC |
| | |
| | |
| | 3) NOTE: PLEASE SUBMIT PLANS DONE IN |
| | DRAFTSMAN LIKE QUALITY AS REQUIRED UNDER |
| | THE FBC 106.1. |
| | PLEASE SEE PEN/PENCIL PLANS ARE NOT |
| | PERMITTED AND WHITE OUT IS ALSO NOT |
| | ACCEPTABLE. |
| | PLEASE ALSO SEE AS PREVIOUSLY REQUESTED, |
| | PLEASE BE SURE THE PRINTED NAME AND |
| | SIGNTURE OF THE PRESON RESPONSIBLE FOR |
| | PLANS/DESIGN/LOADS ETC IS CLEARLY SHOWN |
| | ON ALL SHEETS. (EXCEPT MANUFACTURE |
| | SHEETS FOR EQUIPMENT ). |
| | |
| | 4)NOTE: PLEASE SEE THE SPECS AS |
| | SUBMITTED ON GEN DO NOT CLEARLY INDICATE |
| | WHICH UNIT IS BEING PROPOSED. |
| | PLEASE SEE LOAD IN LOAD CALCS SEEM TO |
| | EXCEED RATINGS ON SPEC SHEETS. |
| | PLEASE ALSO BE SURE THE SPECS SHEETS |
| | CORRELATE WITH THE RISER WHICH INDICATES |
| | 100A OCP AT THE GEN. |
| | 110.3,240,220,90.7 ETC. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |