Plan Review Details - Permit 06060922
Plan Review Stops For Permit 06060922
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-04 Cont ID  
Sent By alange Date 2006-10-04 Time 11:05 Rev Time 0.33
Received By alange Date 2006-10-04 Time 11:05 Sent To  
Notes
2006-10-04 00:00:00NEW PAGES OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 13:08 Rev Time 0.33
Received By alange Date 2006-06-28 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 10:24 Sent To M
Notes
2006-10-01 00:00:00***UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL ARE IN NEED OF
 ADDRESSING.
  
  
 1) NOTE: PLEASE SEE THIS IS A DIESEL
 GENERATOR AND THIS UNIT IS BEING SHOWN
 TOO CLOSE TO TO THE BUILDING AS SHOWN
 FOR MIN CLEARENCES REQUIRED. PLEASE SEE
 THERE WILL BE MECHANICAL COMMENTS. THE
 10FT OR MIN MIN FOR DIESEL FUEL TYPE IF
 FROM ALL OPENINGS, NOT ONLY WINDOWS.
 (SOFFIT ETC0. PLEASE SEE DUE TO THE 10FT
 SETS BACK AND THE MIN REQUIRED FROM
 PROPERTY LINE , FROM BUILIDING, AND THE
 WITH OF THE GEN, A NEW LOCATION MUST BE
 PROPOSED.
 PLEASE SEE NO INFORMATION FROM
 MANUAFATURE WAS SUBMITTED WHICH
 INDICATES THE MIN REQUIRED CLEARENCE ALL
 THE WAY AROUND UNIT. IT IS KNOWN FROM
 THIS MANUFACTURE , TYPICALLY IS REQUIRES
 3FT (MIN) SOME ARE 5FT).
 WITH THAT SAID, IF THE GEN IS 3FT FROM
 HOUSE AND ZONING DOES NOT PERMIT THIS
 UNIT CLOSER THAT 6',1" FROM PROPOERTY
 THIS WILL NOT WORK.
  
  
 ** PLEASE KNOW, SITE SURVEY AS STAMPED
 FROM ZONING HAS BEEN "VOIDED".
  
 2) NOTE: PLEASE COMPLETE RISER DIAGRAM.
 AS SHOWN, THERE SEEM TO BE A SUB PANEL
 WHICH IS BEING FED FROMTHE EXISTING
 200A PANEL, THROUGH THE ATS, YET THIS IS
 NOT SHOWN ON RISER, WITH CONDUCTORS ETC.
 PLEASE SEE MISSING CONDUIT, EQUIPMENT
 GROUNDING CONDUCTORS, ETC.
 PLEASE PROVIDE A COMPLETE OVERVIEW OF
 ALL EQUIPMENT AND LOCATIONS.
 PLEASE KNOW, AS PER 225.31-225.39, AND
 WHAT HOW THE 2005 (FUTURE) CODE INTENDS,
 THE BRKR ON THE GEN MUST BE WITH
 INSIGHT, READILY ACCESSIBLE, AND THER
 MUST BE A DEADFRONT WHEN ACCESSING THE
 GEN. 110.27.
 SIGNAGE FOR ALL WILL ALSO BE REQUIRED AS
 THESE DISONNECTING MEANS ARE NOT
 GROUPED.
 225.34,230.72,230.2,702.8 ETC
  
  
 3) NOTE: PLEASE SUBMIT PLANS DONE IN
 DRAFTSMAN LIKE QUALITY AS REQUIRED UNDER
 THE FBC 106.1.
 PLEASE SEE PEN/PENCIL PLANS ARE NOT
 PERMITTED AND WHITE OUT IS ALSO NOT
 ACCEPTABLE.
 PLEASE ALSO SEE AS PREVIOUSLY REQUESTED,
 PLEASE BE SURE THE PRINTED NAME AND
 SIGNTURE OF THE PRESON RESPONSIBLE FOR
 PLANS/DESIGN/LOADS ETC IS CLEARLY SHOWN
 ON ALL SHEETS. (EXCEPT MANUFACTURE
 SHEETS FOR EQUIPMENT ).
  
 4)NOTE: PLEASE SEE THE SPECS AS
 SUBMITTED ON GEN DO NOT CLEARLY INDICATE
 WHICH UNIT IS BEING PROPOSED.
 PLEASE SEE LOAD IN LOAD CALCS SEEM TO
 EXCEED RATINGS ON SPEC SHEETS.
 PLEASE ALSO BE SURE THE SPECS SHEETS
 CORRELATE WITH THE RISER WHICH INDICATES
 100A OCP AT THE GEN.
 110.3,240,220,90.7 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 15:55 Sent To M
Notes
2006-06-23 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE SUBMIT A COMPLETE
 ELECTRICAL RISER DIAGRAM SHOWING
 LOCATIONS OF ALL ELECTRICAL EQUIPMENT.
 PLEASE SHOW A LAYOUT ON A SHEET FOR THE
 LOCATIONS OF ALL ALSO.
 215.5
 PLEASE SEE 230.70,230.72,230.76,230.79,
 225.31-225.39
 MISSING DISCONNECTS, GROUPING ETC.
  
 2) NOTE: PLEASE INDICATE IF THE PANEL
 SCHEDULE SHOWN IS A NEW EM SUB PANEL.?
 215.5
  
 3) NOTE: PLEASE SEE HEAT LOAD SHOWS
 7.5KW , YET CALCS INDICATE 6KW?
 PLEASE ALSO SEE IF THIS IS THE MAIN
 EXISTING PANEL, WHERE ARE ALL OTHER
 LOADS? IF ALL OTHERS ARE GAS OR ARE DONE
 BY LOAD SHEEDING PLEASE INDICATE.
 215.5,702.5,220.31
  
 4) NOTE: PLEASE CORRELATE RISER OCP AT
 GEN WITH SPECS OF GEN.
 215.5
 **PLEASE SEE 240.6 FOR STANDARD OCP.
  
 5) NOTE: PLEASE SUBMIT ALL SPECS FOR ALL
 , INCLUDING NEW ATS. PLEASE SEE WE ARE
 UNABLE TO VERIFY AT THIS TIME AS THE
 SPECS WERE NOTE SUBMITTED.
  
 ** PLEASE ALSO BE SURE SPECS FOR GEN
 INDICATE THE MIN CLEARENCES REQUIRED PER
 MANUFACTURE.
  
 6) NOTE: PLEASE KNOW, ALL SHEETS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 ** PLEASE KNOW, THESE ARE NOT REQUIRED
 TO BE NOTORIZED, HOWEVER "IF" THEY ARE
 NOTORIZED, THEN THEY MUST BE DONE
 CORRECTLY AS REQUIRED UNDER FS 117.05.
 PLEASE SEE THAT A RUBBER STAMP AND
 SIGNATURE FROM NOTORY IS NOT ACCEPTABLE
 NOR IS IT LEGAL TO DO SO.
 (ONCE AGAIN, THESE ARE NOT REQUIRED TO
 BE).
  
 7) NOTE: PLEASE SEE ZONING COMMENTS AND
 PLEASE PROVIDE ALL DIMENSIONS FOR GEN
 ETC WITH ALL SETBACKS ETC FROM HOUSE AND
 PROPERTY LINES.
  
  
 8) NOTE: PLEASE SEE BLDG COMMENTS AS THE
 THICKNESS OF THE GEN SLAB SHALL BE
 INDICATED.
  
 9) NOTE: PLEASE KNOW, IF IT IS TYHE
 INENT FOR THE ELECTRICAL CONT TO ALSO
 HOOK UP ALL ELECTRICAL , THEN PLEASE BE
 SURE TO SIGN ON THE ELECTRICAL LINE ON
 PERMIT APPLICATION SO THAT AN ELECTRICAL
 PERMIT CAN BE GENERATED. THIS SHOULD BE
 DONE BY THE QUALIFIER WHEN RESUBMITTING
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 10:43 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-10-01 00:00:00DIESEL GEN

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 14:14 Sent To E
Notes
2006-09-26 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-21 Cont ID  
Sent By adarroug Date 2006-09-21 Time 10:09 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 10:09 Sent To Z
Notes
2006-09-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 08:50 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 08:50 Sent To E
Notes
2006-06-20 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 13:08 Rev Time 0.00
Received By alange Date 2006-06-15 Time 16:23 Sent To  
Notes
2006-06-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 11:13 Rev Time 0.25
Received By tgordon Date 2006-10-02 Time 11:12 Sent To B
Notes
2006-10-02 00:00:00*** DENIED ***
 1) SEE ELECTRICAL AND ZONING REVIEW
 NOTES, PLEASE CORRECT.
  
 2) PLEASE BE ADVISED,
 DIESEL GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENS. PER 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 15:17 Rev Time 0.15
Received By tgordon Date 2006-06-26 Time 15:17 Sent To B
Notes
2006-06-26 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 10:43 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-10-01 00:00:00DIESEL GEN

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-23 Cont ID  
Sent By mmclean Date 2006-09-23 Time 09:49 Rev Time 0.00
Received By mmclean Date 2006-09-23 Time 09:49 Sent To I
Notes
2006-09-23 00:00:00PROVISO:THE PROPOSED GENERATOR SHALL NOT
 BE CLOSER THAN 6.1FT FROM SIDE PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 18:31 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 18:31 Sent To I
Notes
2006-06-18 00:00:00DENIED,
 1. MUST PROVIDE THE SETBACK OF THE
 PROPOSED GENERATOR FROM THE SIDE
 PROPERTY LINE & DISTANCE FROM THE
 STRUCTURE.
  
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720