| 2006-07-28 00:00:00 | **** UNSAT **** |
| | |
| | |
| | ** PLEASE SEE SOME NOTE FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES. |
| | |
| | 1) NOTE: NO, SAME, ONLY CONTAINS A |
| | PRINTED NAME. PLEASE KNOW,PLANS SHALL BE |
| | SIGNED BY THE PERSON WITH THE PRINTED |
| | NAME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE THE PRINTED NAME |
| | AND SIGNATURE IS ON PLANS FOR THE PERSON |
| | REPSONSIBLE FOR PLANS. |
| | FBC 106.2.1 |
| | |
| | 2) NOTE:NO, UNCLEAR AS THE FLOOD |
| | ELEVATION COULD NOT BE FOUND. AN ELEV OF |
| | 6.02 IS SHOWN BUT IT IS UNCLEAR WHAT |
| | THIS IS. ? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, LOCATION OF |
| | HOUSE/GEN IS IN A "A" FLOOD ZONE AND |
| | PLANS SHALL INDICATE EQUIPMENT AT 6" |
| | MIN ABOVE THE BFE. |
| | |
| | 3) NOTE: NO, THE LAYOUT IS STILL UNCLEAR |
| | AS SITE PLANS SHOW THE NEW EM PANEL |
| | OUTSIDE AND THE PTHER PANELS INSIDE. |
| | PLEASE SEE SPECS INDICATE THE EM PANEL |
| | AS NEMA 1 AND PLANS PLACE THIS PANEL |
| | OUTSIDE?? |
| | PLEASE ALSO KNOW THAT THE DISCONNECTING |
| | MEANS FOR THE FEEDERS COMING FROM THE |
| | GEN SHALL BE GROUPED WITH THE EXISTING |
| | MAIN(S). 225.34, 230.72 |
| | PLEASE INDICATE THE OCP FEEDIGN THE EM |
| | PANEL. PLEASE CLARIFY THE 200 A MAIN. IT |
| | IS BEING ASSUMED IT IS A MCB PANEL? |
| | 240.4,310.16,110.3,90.7, ETC |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE A LAYOUT FOR ALL |
| | EQUIPMENT AS VERIFICATION OF THE |
| | GROUPING OF THE MAINS AND DISCONECT CAN |
| | NOT BE DONE AT THIS TIME. |
| | 230.72,225.34 |
| | |
| | ** SAME NOTE, NO SLAB DETAIL PROVIDED |
| | FOR GEN UNIT. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE BLDG COMMENTS AS SLAB DETAIL |
| | FOR GEN IS MISSING. |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONALS |
| | RESPONSIBLE FOR PLANS AND REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY GIVEN AS A NOTICE AT THIS |
| | TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |