| Plan Review Stops For Permit 06060899 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-06-23 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-06-23 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2006-06-23 00:00:00 | EXT #0006 WAS CREATED FOR UNITS A11 THRU | | | A14 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-08-08 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-08-08 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | DENIED | | | | | | 1) THE DOOR TO THE EXISTING H/C BATHROOM | | | IS REQUIRED TO HAVE A MINIMUM OF 18" OF | | | CLEARANCE AT THE LATCH SIDE OF THE DOOR | | | ON THE PULL SIDE. FBC 11-4.22.2 AND | | | FBC 11-4.13.6 MANEUVERING CLEARENCES AT | | | DOORS. MINIMUM MANEUVERING CLEARANCES AT | | | DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 2) SEE PLUMBING COMMENT #3 FOR REQUIRED | | | HEIGHT OF COUNTER AND SINK IN WORK ROOM | | | #2. SEE FBC 11-4.24 AND 11-4.32.4. | | | | | | 3)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-06-23 |
Time |
9:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-06-23 |
Time |
9:00 |
Sent To |
|
|
| Notes |
| 2006-06-23 00:00:00 | DENIED | | | | | | 1) THE EXISTING ACCESSIBLE BATHROOM MUST | | | BE MADE CODE COMPLIANT. FBC 2004 | | | EXISTING BUILDINGS 606.1 AND 2004 FBC | | | 11-4.1.6. PROVIDE DETAIL SHOWING | | | COMPLIANCE. | | | | | | 2) THE TWO DOORS IN SERIES AT THE | | | BATHROOM IN OFFICE 1 DO NOT COMPLY WITH | | | CODE. SEE FBC 11-4.13.7. | | | | | | 3) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-08-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-05 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-05 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2006-08-05 00:00:00 | *** UNSAT 2ND REVIEW *** | | | | | | 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS | | | REVIEW. PLEASE SEE FBC CHAPTER 13, AS | | | THE SPACE IS IN A BUILDING LARGER THAN | | | 5K SQ FT. PLEASE SEE 13-415.1.ABC.1.1, | | | .1.2, .1.3. | | | THIS SPACE IS NOT A BUILDING. PLEASE SEE | | | ELECTRICAL IS FED FROM A SERVICE WHICH | | | FEEDS ONE BUILDING. PLEASE SEE FBC | | | DEFINITIONS OF BUILDINGS. IF THIS SPACE | | | WAS SEPARATED BY A "FIRE WALL" ON BOTH | | | SIDES WHICH REQUIRES 4HR SEPARATION AND | | | ALSO REQUIRES COMPLETE COLLAPSE OF THE | | | ADOINING ROOFS WITH OUT AFFECTTING THE | | | STRUCTURAL INTEGRITY OF THE BUILDING | | | ETC. | | | PLEASE SEE AT THIS POINT THE SPACE WOULD | | | BE CONSIDERED A BUILDING AND A SEPARATE | | | ELECTRICAL SERVICE WOULD BE REQUIRED. | | | | | | ** PLEASE SEE SPACE #11&12 SEEM TO BE | | | EXISTINGWITH ONLY THE NEW SEPARATION | | | BEING ADDED, IF SO PLEASE LABEL ALL | | | ELECTRICAL OR CLOUD SPACE AS EXISTING. | | | PLEASE SEE SPACE #13&14 WILL REQUIRE NEW | | | CONTROLS PER CHAPTER 13 AS NOTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-21 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-21 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2006-06-21 00:00:00 | ****** UNSAT ***** | | | | | | 1) NOTE: PLEASE SEE PERMIT APPLICATION | | | MENTIONS TO SPLIT FOUR BAYS DOWN TO TWO, | | | HOWEVER FROM WHAT THE PLASN INDICATE, | | | THERE IS ONLY ONE BAY EXISTING WHICH IS | | | NOW BEING SEPARATED BY NEW PROPOSED | | | TENANT SEPARATION WALL INTO TWO NEW | | | BAYS.??? | | | PLEASE VERIFY. | | | IT WAS NOTED THAT THE UNITS MAY HAVE | | | BEEN LABELED 11,12,13 AND 14, HOWEVER | | | NEW SUITES MAY BE ASSIGNED. | | | | | | 2) NOTE: PLEASE SUBMIT LOADS ON EXISTING | | | SERVICES WITH NEW LOADS ADDED. | | | 220, 215.5 | | | | | | 3) NOTE: PLEASE SEE FBC CHAPTER 13 , | | | 13-415.1.ABC.1.1,.1.2,.1.3 | | | 13-415.1.AB.1, 13-415.2.ABC.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-08 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-08 |
Time |
14:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-27 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-27 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2006-06-27 00:00:00 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 2) A FIRE EXTINGUISHER IS SHOWN IN | | | RECEPTION (1). A 2A-10B,C RATED FIRE | | | EXTINGUISHER IS ALSO REQUIRED IN OTHER | | | TENANT SPACE DUE TO THE SEPARATION. | | | | | | 3) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-20 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-20 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2006-08-01 00:00:00 | TO "BOB"#10 | | 2006-07-20 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-27 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-15 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2006-06-21 00:00:00 | TO "BOB"#14 | | 2006-06-15 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-08-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-04 |
Time |
09:34 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-08-04 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-22 |
Time |
13:59 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-06-22 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | *** DENIED *** | | | 1) ENERGY CAL'S PAGE #1 SEE MAX TONNAGE | | | 3.7, PLANS ARE SHOWING TWO 3 1/2 TON | | | SYSTEMS= 7 TONS, PLEASE CORRECT. | | | | | | 2) ENERGY CAL'S PAGE #5 IS SHOWING THREE | | | A/C SYSTEMS, PLANS ARE SHOWING TWO | | | SYSTEMS, PLEASE CORRECT. | | | | | | 3) PROVIDE RETURN AIR FOR AHU #2. | | | | | | 4) PROVIDE RETURN AIR TO ALL OFFICES. | | | BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-08-11 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-08-11 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2006-08-11 00:00:00 | DENIED; | | | 1.WHAT TYPE OF WORK WILL BE DONE IN THE | | | WORK ROOM AND WHY IS A REFRIGERATOR | | | REQUIRED? | | | 2. MEN'S ROOM IS NOT HANDICAP COMPLIANT. | | | A)DOOR SWINGS INTO CLEAR FLOOR SPACE | | | OF THE LAVITORY. | | | B) THE URINAL AND LAVATORY IN THE | | | | | | HANDICAP BATHROOM MUST MEET ALL | | | THE REQUIREMENTS OF CHAPTER 11. | | | URINAL TO COMPLY WITH SECTIONS | | | 11-4.18.2 THRU 11-4.18.4. | | | LAVATORY TO COMPLY WITH SECTIONS | | | 11-4.19.1 THRU 11-4.19.6. | | | 3. A WATER HEATER IS SHOWN ON PAGE 2 | | | (FLOOR PLAN) BUT NO HOT WATER PIPING IS | | | SHOWN ON WATER RISER DIAGRAM. PLEASE | | | NOTE ON PLANS IF NEW BATHROOM WILL NOT | | | HAVE HOT WATER TO THE LAV. | | | 4.CUP DISPENSOR REQUIRED AT DRINKING | | | FOUNTAINS. CHAPTER 11 SECTION | | | 11-4.1.3(10). PLEASE ADD NOTE ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-06-27 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-06-27 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2006-06-27 00:00:00 | DENIED; | | | 1.BOTH BATHROOMS ARE REQUIRED TO BE | | | HANDICAPED SEE FBC-2004 CHAPTER 11 SEC. | | | 11-4.1.3(11). | | | 2.SHOW DETAILS OF H/C BATHROOMS. ALL | | | MEASUREMENTS, FOR PLUMBING FIXTURES, | | | BATHROOM SIZE, AND GRAB BAR HIGHT. | | | 3.LOUNGE SINK TO COMPLY WITH | | | SECS.11-4.24.1 THRU 11-4.24.7. SHOW | | | DETAIL ON PLAN. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|