Plan Review Details - Permit 06060860
Plan Review Stops For Permit 06060860
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-01 Cont ID  
Sent By alange Date 2006-12-01 Time 11:02 Rev Time 0.00
Received By alange Date 2006-12-01 Time 11:02 Sent To  
Notes
2006-12-01 11:03:12DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 5.SELECT ASSEMBLY USED WITH TAMCO
 ROOFING.MAKE SPECIAL NOTE OF GENERAL
 LIMITATION #7 ON PAGE 20.CALULATIONS
 MY BE REQUIRED DEPENDING ON THE ASSEMBLY
 USED.
  
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-28 Cont ID  
Sent By alange Date 2006-09-28 Time 09:28 Rev Time 0.50
Received By alange Date 2006-09-28 Time 09:28 Sent To  
Notes
2006-09-28 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 5.SELECT ASSEMBLY USED WITH TAMCO
 ROOFING.MAKE SPECIAL NOTE OF GENERAL
 LIMITATION #7 ON PAGE 20.CALULATIONS
 MY BE REQUIRED DEPENDING ON THE ASSEMBLY
 USED.
  
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-10 Cont ID  
Sent By tgordon Date 2006-09-19 Time 10:55 Rev Time 2.00
Received By alange Date 2006-07-10 Time 08:42 Sent To  
Notes
2006-07-10 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $28,198.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 LINTELS, LAWSON STATE APPROVAL SUBMITTED
 IS NOT APPROVED.SELECT ASSEMBLY USED
 WITH TAMCO ROOFING.
  
  
 6.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 8.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.FS 472.025
  
 9.SUBMIT ONLY TWO PLANS FOR REVIEW.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By dpalmer Date 2006-09-19 Time 10:26 Rev Time 0.00
Received By dpalmer Date 2006-09-19 Time 09:03 Sent To M
Notes
2006-09-19 00:00:00CARPORT ONLY, DELETED REAR ADDITION AS
 IT DID NOT MEET SETBACKS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 14:26 Sent To P
Notes
2006-06-24 00:00:00*********UNSAT ************
  
 1) NOTE: PLEASE SEE ALL SETS OF PLANS
 ARE SIGNED, DATED OR SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD AS SHOWN
 ON TITLE BLOCKS. PER FS471.025
 PLEASE ALSO SEE ALL SHEETS NOT DONE BY
 THE PE, SHALL CONTAN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPOSIBLE
 FOR PLANS/DESIGN.
 FBC 106.1.2,106.1.3 ADMIN SECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PELASE SEE PLANS MENTIONS NEW
 SPLIT A/C SYSTEM REPLACING OLD SYSTEM,
 HOWEVE NO NEW CIRCUIT(S) OR LAODS ARE
 SHOWN ON PANEL SCHEDULE.
 PLEASE INDICATE LOAD CALCULATIONS PER
 220.31B.
 ** PLEASE SEE LOAD CALCULATIONS ALREADY
 SHOW LOAD AT 146 A'S, AND THEY DON'T
 INLCUDE NEWA/C LOADS AS SHOWN. PLEASE
 KNOW, IT APPEARS A NEW SERVICE UPGRADE
 WILL BE REQUIRED . PLEASE ALSO SEE 90.8
 AS THE CODE ALSO REQUIRES ROOM FOR
 FUTURE EXPANSION.
 3) NOTE: PLEASE SHOW SD'SIN EXISTIGN
 DWELLING EXISTING WHICH MEET CURRENT
 CODE OR NEW TO BE INSTALLED.
 FBC 2004/ RES R313, NFPA-72 11.5.1.1,
 11.8.3
  
 4) NOTE: PLEASE SEE MIN CLEARENCES SHALL
 BE INDICATED FOR CLOSET LTS. PLEASE KNOW
 A MIN OF 18" SHELVING SHALL BE USEDAND
 ASSUMED PER 410.8
  
 5) NOTE: PLEASE SEE PLANS INDICATE NEW
 COMPUTER RM, YET IS ELEC NEW OR
 EXISTING? 210.52,210.70 ETC
  
 6) NOTE: PLEASE SEE BUIDLING REVIEW
 NOTES AS THE VALUE SHALL BE UPDATED.
 108.3
  
 ** PLEASE SUBMIT TWO COMPLETE SETS WITH
 ALL SHEET ATTACHED INTO SETS AND NOT
 LOOSE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 18:53 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 18:53 Sent To B
Notes
2006-11-29 18:53:39RESUB/TO ALANGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 09:58 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 09:58 Sent To E
Notes
2006-09-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 15:28 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 15:28 Sent To Z
Notes
2006-09-09 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 10:17 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 10:17 Sent To E
Notes
2006-06-23 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-10 Cont ID  
Sent By alange Date 2006-07-10 Time 08:48 Rev Time 0.00
Received By alange Date 2006-06-16 Time 14:40 Sent To  
Notes
2006-06-16 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-09-19 Cont ID  
Sent By tgordon Date 2006-09-19 Time 10:55 Rev Time 0.15
Received By tgordon Date 2006-09-19 Time 10:55 Sent To P
Notes
2006-09-19 00:00:00NO MEAH. WORK TO BE DONE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-09-19 Cont ID  
Sent By tgordon Date 2006-07-05 Time 09:07 Rev Time 0.30
Received By tgordon Date 2006-09-19 Time 10:54 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-05 Cont ID  
Sent By jleech Date 2006-07-05 Time 08:35 Rev Time 0.00
Received By jleech Date 2006-07-05 Time 08:35 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-14 Cont ID  
Sent By mmclean Date 2006-09-14 Time 14:19 Rev Time 0.00
Received By mmclean Date 2006-09-14 Time 14:19 Sent To I
Notes
2006-09-14 00:00:00NOTE: THE PROPOSED CARPORT ONLY.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By mmclean Date 2006-06-22 Time 16:40 Rev Time 0.00
Received By mmclean Date 2006-06-22 Time 16:40 Sent To I
Notes
2006-06-22 00:00:00DENIED,
 1. THE PROPOSED ADDITION MUST MEET THE
 REAR SETBACK OF THE PROPERTY.
 NOTE MUST BE EITHER 10% OF LOT DEPT OR
 15FT, WHICHEVER IS LESS.
 2. THE EXISTING FAMILY ROOM MUST HAVE
 INTERIOR ACCESS TO THE NEW ADDITION (NEW
 BEDROOM).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720