Plan Review Details - Permit 06060845
Plan Review Stops For Permit 06060845
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By lursu Date 2006-06-21 Time 09:03 Rev Time 0.00
Received By lursu Date 2006-06-14 Time 10:34 Sent To AD
Notes
2006-06-21 00:00:00TEMP PCN= 74 43 43 19 13 B00 0000 WAS
 CREATED FO RTHE COMMON
 AREA
2006-06-14 00:00:00ROUTED TO LILI FOR A PCN # WAS GIVEN A
 TEMP # FOR THE TIME BEING MAY NEED TO
 SEE A SURVEY BLDG POSSIBLY ON PROPERTY
 LINE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-19 Cont ID  
Sent By alange Date 2006-07-19 Time 13:29 Rev Time 0.25
Received By alange Date 2006-07-19 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-12 Cont ID  
Sent By rmcdouga Date 2006-07-12 Time 12:30 Rev Time 0.00
Received By rmcdouga Date 2006-07-12 Time 12:30 Sent To  
Notes
2006-07-12 00:00:00CONTRACTOR WILL BRING IN 2 SETS OF
 SIGNED AND SEALED ENGINEERING TO REPLACE
 THE COPIES THAT WERE SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By rmcdouga Date 2006-06-15 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2006-06-15 Time 09:15 Sent To  
Notes
2006-06-15 00:00:00DENIED
  
 1) SPEICFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE ON THE PERMIT APPLICATION.
  
 2) SYSTEM SPECIFIED IN NOA HAS A DESIGN
 PRESSURE OF -75 PSF. PROVIDE RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION
 #7 ON PAGE 16 OF THE NOA.
  
 3) BASE SHEET MUST BE ATTACHED USING ONE
 OF THE FASTENERS SPECIFIED IN THE NOA.
 THE OLYLOK FASTENER IS NOT ONE OF THEM.
 SEE FASTENING ON PAGE 12 OF NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  