Plan Review Details - Permit 06060814
Plan Review Stops For Permit 06060814
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-10 Cont ID  
Sent By jwitmer Date 2006-10-10 Time 14:59 Rev Time 2.22
Received By jwitmer Date 2006-10-10 Time 14:59 Sent To  
Notes
2006-10-24 08:43:36NO SUBPERMITS APPLIED FOR.
 ROOFING : STEEL TILE CO.
 FL APPROVAL # 4865
 UPLIFT -67.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-02 Cont ID  
Sent By jwitmer Date 2006-08-02 Time 15:47 Rev Time 2.22
Received By jwitmer Date 2006-08-02 Time 15:47 Sent To Z
Notes
2006-08-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06060814
 ADD: 1041 45TH ST
 CONT: ATLANTIC GENNERAL CONT
 TEL: (561)718-2668
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEET 1& 2 BOTH MAKE REFRENCE TO THE
 FBC 2001, PLANS SUBMITTED AFTER
 SEPT.30TH, 2005 FOR PERMIT ARE REQUIRED
 TO BE DESIGNED TO THE 2004 FBC FL S S
 553.
  
 3)SHEET# 1 INDICATES THE DESIGNED THIS
 STRUCTURE TO ASCE 7-02, EXP "B".MISSING
 THE ITEM # 4 PRESSURE COEFFICIENT.
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) SHEET# 2 BEAM DETAIL INDICATES BEAM
 SIZE AND (9)# 5 BARS BUT NO INFORMATION
 AS TO STIRRUP SIZE OR SPACING.
  
 5) PLANS ARE MISSING TEMITE
 TREATMENT.1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE
 SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF
 THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE
 ISSUED TO THE BUILDING DEPARTMENT BY THE
 LICENSED PEST CONTROL COMPANY THAT
 CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF
 SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 6) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G ) SQ. FT. FOOTPRINT
 H) FLOOD ZONE (AH)
 I) FLOOD ELEVATION(17.5')MINIMUM
  
 7)NOTE:PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".(17.5')
  
 8) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
  
 11) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 12) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 13) PLANS DO NOT INDICATE WHAT TYPE OF
 PAPER BACK LATH WILL BE USED ON THE
 CEILING OR LENGTH OR TYPE OF NAIL.
 2510 LATHING FOR CEMENT PLASTER (STUCCO)
  
 2510.3 INSTALLATION.
 INSTALLATION OF THESE MATERIALS SHALL BE
 IN COMPLIANCE WITH ASTM C 926 AND ASTM C
 1063.
  
 14) PLANS DO NOT INDICATE COMPLIANCE
 WITH ATTIC VENTILATION, 1203.2.
  
 15) PLANS INDICATE THAT THIS PAVILION IS
 LOCATED IN A ISLAND OF A PARKING LOT.
 PLEASE PROVIDE THE ACCESSIBLE ACCESS TO
 THE PAVILION, INDICATE AN ACCESSIBLE
 CROSS WALK, CURB CUTS AND DETECTABLE
 WARNING AT CROSSWALKS.
  
 11-4.3.2 (2)AT LEAST ONE ACCESSIBLE
 ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, FACILITIES, ELEMENTS, AND
 SPACES THAT ARE ON THE SAME SITE.
  
 11-4.3.8AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDINGS,
 FACILITIES, ELEMENTS, AND SPACES THAT
 ARE ON THE SAME SITE.
  
 11-4.3.6 SURFACE TEXTURES.
 THE SURFACE OF AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH SECTION 11-4.5 .
  
 11-3.5 MARKED CROSSING. A CROSSWALK OR
 OTHER IDENTIFIED PATH INTENDED FOR
 PEDESTRIAN USE IN CROSSING A VEHICULAR
 WAY.
  
 11-4.7.1 LOCATION.
 CURB RAMPS COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED WHEREVER AN ACCESSIBLE
 ROUTE CROSSES A CURB.
 CURB RAMPS MUST BE LOCATED OUTSIDE OF
 DISABLED PARKING SPACES AND ACCESS
 AISLES.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-15 Cont ID  
Sent By dpalmer Date 2006-09-15 Time 20:53 Rev Time 0.00
Received By dpalmer Date 2006-09-15 Time 20:45 Sent To  
Notes
2006-09-15 00:00:00**** PLEASE SEE NOTES FROM PREVIOUS
 WHICH STATED THE ENGINEER ON TRUSS
 PACKAGE MUST SIGNED, DATE AND SEAL TRUSS
 PACKAGE WITH THE ORIGINAL SIGNATURE AS
 REQUIRED. PLEASE SEE THESE NOW CONTAIN A
 "RUBBER STAMP" ON SAID PLANS.
 PLEASE SEE FAC 61G15-23.002, FS 471.025.
 PLEASE ALSO SEE SURVEY ALSO DOES NOT
 CONTAIN AN ORIGINAL SIGNATURE.
 FAC 61G17, FS 472.025.
 THESE ARE NOT FOR ELECTRICAL.
  
 ** ELECTRICAL PLANS REDLINED FOR TC
 /CONTROL OF THE OUTSIDE FLOOD LTS.
 THIS TIME CLOCK SHALL BE AT THE
 STRUCTURE.
 225.31,250.32

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 18:13 Sent To  
Notes
2006-06-29 00:00:00********** UNSAT **********
  
 1) NOTE: PLEASE SEE PLANS SPECIFICALLY
 STATE THE 2001 FBC IN MANY LOCATIONS
 WHERE-AS WE ARE CURRENTLY UNDER THE 2004
 FBC.
 PLEASE ALSO NOTE ELECTRICAL PER
 NFPA-70(NEC) 2002.
  
 2) NOTE: PLEASE SEE A MEANS OF
 DISCONNECT IS REQUIRED FOR CIRCUIT AT
 NEW STRUCTURE. THIS CAN BE A TOGGLE/SNAP
 SWITCH. 225.31-225.39
  
 3) NOTE: PLEASE SEE 250.32, AS NEW
 FOOTER STEEL IS REQUIRED TO BE BONDED
 UNLES MEETING EXCEPTION OF A SINGLE 120V
 CIRCUIT W/ GFI PROTECTION. PLEASE EITHER
 ADD THE GROUNDING ELECTRODE SYSTEM, OR
 INDICATE THE GFI PROTECTION FOR THE ONE
 CIRCUIT.
  
 4) NOTE: PLEASE SEE BUIDLING REVIEW
 COMMENTS, AS THE TRUSS SUBMITTIAL
 PACKAGE INCLUDE CLEARLY TWO DIFFERENT
 SIGNATURES FOR THE ENGINEER.
 PLEASE ALSO SEE SET WHICH IS
 PHOTO-COPIED. PLEASE KNOW, ALL SETS
 SHALL BE SIGNED, DATED AND SEAL WITH
 ORIGINAL SIGNATURE AND RAISED SEAL.
 FAC 61G15-23.002, FS 471.025
 THIS IS ONLY NOTED BY THIS REVIEWER AND
 IS NOT PART OF THE REVIEW OF THE
 ELECTRICAL SHEETS BY THE ARCHITECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By mwennerg Date 2006-10-23 Time 16:44 Rev Time 0.00
Received By mwennerg Date 2006-10-23 Time 16:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 12:15 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 12:12 Sent To  
Notes
2006-07-11 00:00:001. PLEASE EXPLAIN PURPOSE OF PAVILLION.
  
 2. WILL THE CONSTRUCTION OF THE
 PAVILLION INTERFERE WITH FIRE AND
 PARAMEDICAL ACCESS TO THE TWO BUILDINGS.
  
 3. IT IS DIFFICULT TO DETERMINE IF ANY
 CURBING IS PRESENT THAT WOULD INTERFERE
 WITH EMERGENCY VEHICLES.IT DOES APPEAR
 THAT A HEADER CURB IS PRESENT. CAN A
 DETAIL BE PROVIDED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 16:24 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 16:24 Sent To  
Notes
2006-09-13 00:00:00TO "COMM" BD#11
2006-09-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-08-03 Time 16:18 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 13:27 Sent To  
Notes
2006-06-26 00:00:00TO "COMM" BD#41
2006-06-15 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-20 Cont ID  
Sent By lfranco Date 2006-10-20 Time 19:19 Rev Time 0.00
Received By lfranco Date 2006-10-20 Time 19:19 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-03 Cont ID  
Sent By lfranco Date 2006-08-03 Time 19:02 Rev Time 0.00
Received By lfranco Date 2006-08-03 Time 18:41 Sent To I
Notes
***NONE***