| Plan Review Stops For Permit 06060807 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2006-06-28 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-06-28 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2006-06-22 |
Time |
08:48 |
Sent To |
I |
|
| Notes |
| 2006-06-28 00:00:00 | PLAN REVIEW NOTES | | | **************************************** | | | PROJECT:2813 EXCHANGE COURT | | | | | | ROOFING CONTRACTOR:PESTANA ROOFING | | | PLANS EXAMINER:KEN CONRAD | | | | | | *******PROVISO*************** | | | | | | 1)REQUIRE THE SUBMITTAL OF THE INCREASED | | | MECHANICAL ATTACHMENT PATTERNS OF THE | | | INSULATION BOARD.A QUALIFIED DESIGN | | | PROFESSIONAL MUST PROVIDE | | | DATA/CALCULATIONS DEPICTING THE ELEVATED | | | DESIGN PRESSURES OF ROOF ZONES #2 AND #3 | | | AS PER THE FLORIDA STATE PRODUCT | | | APPROVAL/RAS 117. | | | | | | 2)REQUIRE THE SUBMITTAL OF A WITHDRAW | | | RESISTANCE TEST OF THE MECHANICAL | | | FASTENERS ATTACHED TO THE EXISTING | | | DECK.A QUALIFIED DESIGN PROFESSIONAL | | | SHALL REVIEW THE DATA AND DETERMINE IF | | | THE TESTING RESULTS MEET THE MINIMUM | | | REQUIREMENTS OF THE ROOFING SYSTEM.THIS | | | TEST MUST BE PERFORMED PRIOR TO ANY | | | ROOFING APPLICATIONS AND SHALL COMPLY | | | WITH RAS 105.SEE LIMITATION #7 OF THE | | | INSTALLATION REQUIREMENTS SHEET 4 OF 5. | | | |
|
|
|