Plan Review Details - Permit 06060807
Plan Review Stops For Permit 06060807
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By kconrad Date 2006-06-28 Time 17:49 Rev Time 0.00
Received By kconrad Date 2006-06-22 Time 08:48 Sent To I
Notes
2006-06-28 00:00:00PLAN REVIEW NOTES
 ****************************************
 PROJECT:2813 EXCHANGE COURT
  
 ROOFING CONTRACTOR:PESTANA ROOFING
 PLANS EXAMINER:KEN CONRAD
  
 *******PROVISO***************
  
 1)REQUIRE THE SUBMITTAL OF THE INCREASED
 MECHANICAL ATTACHMENT PATTERNS OF THE
 INSULATION BOARD.A QUALIFIED DESIGN
 PROFESSIONAL MUST PROVIDE
 DATA/CALCULATIONS DEPICTING THE ELEVATED
 DESIGN PRESSURES OF ROOF ZONES #2 AND #3
 AS PER THE FLORIDA STATE PRODUCT
 APPROVAL/RAS 117.
  
 2)REQUIRE THE SUBMITTAL OF A WITHDRAW
 RESISTANCE TEST OF THE MECHANICAL
 FASTENERS ATTACHED TO THE EXISTING
 DECK.A QUALIFIED DESIGN PROFESSIONAL
 SHALL REVIEW THE DATA AND DETERMINE IF
 THE TESTING RESULTS MEET THE MINIMUM
 REQUIREMENTS OF THE ROOFING SYSTEM.THIS
 TEST MUST BE PERFORMED PRIOR TO ANY
 ROOFING APPLICATIONS AND SHALL COMPLY
 WITH RAS 105.SEE LIMITATION #7 OF THE
 INSTALLATION REQUIREMENTS SHEET 4 OF 5.
  