Plan Review Details - Permit 06060788
Plan Review Stops For Permit 06060788
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-13 Cont ID  
Sent By mjacobs Date 2006-09-13 Time 16:03 Rev Time 0.00
Received By mjacobs Date 2006-09-13 Time 16:03 Sent To PC
Notes
2006-09-08 00:00:00NEW SHEETS , NEEDS STAMPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2006-07-26 Cont ID  
Sent By mjacobs Date 2006-07-26 Time 07:28 Rev Time 0.00
Received By mjacobs Date 2006-07-24 Time 14:29 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By mjacobs Date 2006-07-03 Time 09:50 Rev Time 0.00
Received By mjacobs Date 2006-07-03 Time 07:49 Sent To PC
Notes
2006-07-03 00:00:00 
 1) THE ZONING ISSUES SHALL BE ADDRESSED
 BEFORE THE APPLICATION CAN BE APPROVED
 BY THE STRUCTUAL REVIEWER.
  
 2) NOTE: THE SLAB FOR THE EQUIPEMENT
 TIE-DOWN SHALL BE SOLID CONCRETE.
 ?1820.3. CONCRETE FLOOR SLABS PLACED
 DIRECTLY ON THE SUPPORTING SOIL
 SHALL BE A MINIMUM OF 4 INCHES IN
 THICKNESS, REINFORCED WITH NOT LESS THAN
 0.028 SQUARE INCHES OF REINFORCING PER
 LINEAR FOOT OF SLAB IN EACH
 DIRECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 19:41 Sent To Z
Notes
2006-09-08 00:00:00ATTACHED ELECTRICAL RISER TO PLANS.
  
 PLANS ROUTED TO ZONING FOR NEW
 SITE/SURVEY SHEETS WHICH DO NOT CONTAIN
 PERVIOUS STAMPS.
 ADDED NOTES FOR ZONING.
  
 NEEDS PLUMB AND BLDG FOR NEW SHEETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 09:15 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 09:03 Sent To P
Notes
2006-07-23 00:00:00*** UNSAT ***
  
 ** NOTE FROM PREVIOUS REVIEW WHICH STILL
 NEEDS TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE WIRING DIAGRAM SHOWS
 A NEW PANEL BEING ADDED, HOWEVER NO OCP
 AND CONDUCTOR SIZES ETC ARE SHOWN.
 PLEASE KNOW, HAND DRAWN WIRE SIZES ARE
 NOW ON SAIDS PLANS WHICH ARE NOT
 PERMITTED AS THESE PLANS ARE SIGNED AND
 SEALED BY AN ENGINEER.
 FS 471.025
 PLEASE KNOW, APART FROM THE ELECTRICAL
 WIRING DIAGRAM, PLEASE KNOW, THE
 ELECTRICAL INFORMATION MAY BE SUBMITTED
 SEPARATELY ON AN 8 1/2 BY 11 AND IS NOT
 REQUIRED TO BE DONE BY THE ENGINEER.
 PLEASEKNOW, AS LONG AS THE PRINTED
 NAME AND SIGNATURE OF THE PERSON TAKING
 RESPONSIBILTY OF SAID PLANS/DESIGN, THEN
 THIS WILL BE OK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By dpalmer Date 2006-06-22 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2006-06-22 Time 19:02 Sent To P
Notes
2006-06-22 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE COORELATE PLANS, AS
 PLUMB INDICATES A GAS HEATER AND THE
 ELECTRICAL INDICATES AN ELECTRICAL HEAT
 PUMP?
 215.5
 IF ELEC HEAT PUMP, SUBMIT LOAD
 CALCULATIONS FOR INCREASED LOADS WITH
 LOAD ON EXISTING SERVICE. PLEASE KNOW
 ALL CONTINUOUS LAODS AT 125%, THIS
 INCLUDE PUMPS AND HEATER.
 220, 215.3,230.42, 680.9 ETC
  
 2) NOTE: PLEASE SEE PLUMB INDICATES TWO
 PUMPS AND ONLY ONE SHOWN ON ELECTRICAL ,
 PLEASE ADJUST AND CORRELATE RISER.
 215.5
  
 3) NOTE: PLEASE SPECIFY IF PANEL SHOWN
 IS NEW OR EXSITING. IF NEW, PLEASE
 INDICATE THE OCP, FEEDERS ETC FOR NEW
 PANELS.; IF EXISTING, INDICATE OCP ,
 CONDUCTORS AND BRANCH CIRCUITS FOR NEW
 LAODS.
 215.5,240.4,310.16 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By mperson Date 2006-06-23 Time 15:01 Rev Time 0.00
Received By mperson Date 2006-06-23 Time 15:01 Sent To B
Notes
2006-06-23 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 15:29 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 15:29 Sent To E
Notes
2006-09-05 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-20 Cont ID  
Sent By adarroug Date 2006-07-20 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 14:53 Sent To Z
Notes
2006-07-20 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 08:39 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 08:39 Sent To E
Notes
2006-06-20 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-03 Time   Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 10:37 Sent To  
Notes
2006-06-15 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-12 Cont ID  
Sent By mperson Date 2006-09-12 Time 14:51 Rev Time 0.15
Received By mperson Date 2006-09-12 Time 14:51 Sent To B
Notes
2006-09-12 00:00:00NOTE: NEW SHEETS ONE SET ONLY NEEDED
 STAMPS.
2006-09-08 00:00:00NEW SHEETS, NEEDS STAMPS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-24 Cont ID  
Sent By mperson Date 2006-07-24 Time 09:15 Rev Time 0.33
Received By mperson Date 2006-07-24 Time 09:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By mperson Date 2006-06-23 Time 14:36 Rev Time 0.45
Received By mperson Date 2006-06-23 Time 14:36 Sent To G
Notes
2006-06-23 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBC-2004 RESIDENTIAL SEC. R4101 SWIMMING
 POOLS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PUMBING PLAN REVIEW:
  
 1) PLEASE CORRELATE THE VENT SIZE ON
 PRINT. THE MAIN DRAIN DETAIL INDICATES
 1-1/2" AND THE PIPING SCHEMATIC
 INDICATES 1" PLEASE SEE CORRECTED
 DRAWING IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 2) FBC-2004 SEC. 424.2.7.2, OR FBCR-2004
 SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL
 BE MOUNTED ON A SUBSTANTIAL BASE IN A
 MANNER THAT WILL ELIMINATE STRAIN ON
 PIPING.SLAB SHALL BE A NOMINAL 4"
 THICK. (DETAIL)
 3) PLEASE CHANGE SPECIFICATION NOTE #9
 ON THE GAS TO READ AS THE FOLLOWING.
 FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS.SEPARATE PLANS AND
 PERMIT REQUIRED.
 4) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2006-09-13 Cont ID  
Sent By mmclean Date 2006-09-13 Time 15:57 Rev Time 0.00
Received By mmclean Date 2006-09-13 Time 15:57 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2006-09-12 Cont ID  
Sent By mmclean Date 2006-09-12 Time 14:21 Rev Time 0.00
Received By mmclean Date 2006-09-12 Time 14:21 Sent To  
Notes
2006-09-12 00:00:009/12/06 - DENIED - RESUB
 1.CITY OF WEST PALM - AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION: BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICAL
 MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROIVDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.THIS POLICY MAY INCLUDE SUCH
 THINDS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 2. PLEASE SUBMIT TWO NEW COPY OF SURVEY
 SHOWING THE PROPOSED WORK (WORK MUST NOT
 BE MARKED IN PENCIL, WITH SETBACKS.
 3. PLEASE SHOW THE LOCATION OF THE
 PROPSED POOL EQUIPMENT ON TWO COPIES OF
 SURVEYS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
2006-09-08 00:00:00NEW SITE/SURVEY SUBMITTED, NOTES TO
 ZONING TECH AS PLANS CONTAIN PENCIL AND
 PEN DRAWN ITEMS ON PLANS WHICH IS NOT
 PERMITTED.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-07-30 Cont ID  
Sent By mmclean Date 2006-07-30 Time 17:25 Rev Time 0.00
Received By mmclean Date 2006-07-30 Time 17:25 Sent To I
Notes
2006-07-31 00:00:00NOTE:
 THE PROPOSED POOL EQUIPMENT SHALL NOT BE
 CLOSER THAN 1FT FROMREAR PROPERTY
 LINE.
  
 NOTE: THE PROPOSED POOL SHALL BE 5FT
 FROM THE SIDE & 5.6FT IN THE REAR. THE
 PROPOSED DECK SHALL BE 3FT ON THE SIDE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-28 Cont ID  
Sent By mmclean Date 2006-07-28 Time 08:00 Rev Time 0.00
Received By mmclean Date 2006-07-28 Time 08:00 Sent To  
Notes
2006-07-28 00:00:00DENIED,
 1. CITY OF WEST PALM - AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION: BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICAL
 MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROIVDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.THIS POLICY MAY INCLUDE SUCH
 THINDS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. THE PROPOSED WORK
 CANNOT BE SUBMITTED IN PENCIL.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 18:11 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 18:11 Sent To I
Notes
2006-06-18 00:00:00DENIED,
 1. NEED TO PROVIDE THE FINAL APPROVAL
 FROM THE HOA FOR THE PAVERS LOCATION (AS
 REQUESTED BY THE HOA LETTER DATED
 5/18/06)
 2. MUST SHOW CLEARLY THE LOCATION OF THE
 POOL EQUIPMENT WITH THE SETBACK FROM THE
 EXISTING STRUCTURE & PROPERTY LINE.
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 3. IF THE HOA DOES NOT APPROVE THE
 PAVERS, THE PAVERS CANNOT BE BUILT IN
 THE 5FT MAINTENANCE EASEMENT IN THE REAR
 OF PROPERTY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720