Plan Review Details - Permit 06060693
Plan Review Stops For Permit 06060693
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By rmcdouga Date 2006-06-22 Time 07:05 Rev Time 0.00
Received By rmcdouga Date 2006-06-22 Time 07:04 Sent To  
Notes
2006-06-22 00:00:00DENIED
  
 1) FBC 1019.1.5 STATES THAT AN EXIT
 ENCLOSURE SHALL NOT BE USED FOR ANY
 PURPOSE OTHER THAN MEANS OF EGRESS.
 FBC 1019.1.5 ENCLOSURES UNDER STAIRWAYS.
 THE WALLS AND SOFFITS WITHIN ENCLOSED
 USABLE SPACES UNDER ENCLOSED AND
 UNENCLOSED STAIRWAYS SHALL BE PROTECTED
 BY 1-HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION, OR THE FIRE-RESISTANCE
 RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER. ACCESS TO THE
 ENCLOSED USABLE SPACE SHALL NOT BE
 DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 2) THE OWNER OF RECORD ON THE
 APPLICATION DOES NOT CORRESPOND WITH
 CITY RECORDS. PLEASE SUBMIT PROOF OF
 OWNERSHIP, SO THAT RECORDS CAN BE
 UPDATED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 14:05 Sent To  
Notes
2006-06-19 00:00:001. PLANS DO NOT INDICATE THAT THE DOOR
 TO THE NEW STORAGE AREA IS FIRE RATED.
 PLEASE REVISE THE PLANS TO ILLUSTRATE
 THAT THE DOOR IS FIRE RATED TO MATCH NEW
 WALL AREA.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-22 Cont ID  
Sent By rmcdouga Date 2006-06-22 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2006-06-14 Time 11:10 Sent To  
Notes
2006-06-19 00:00:00TO "BOB"#6
2006-06-14 00:00:00WAITING FOR "BOB"