Plan Review Details - Permit 06060615
Plan Review Stops For Permit 06060615
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By btrobaug Date 2006-06-19 Time 18:18 Rev Time 0.50
Received By btrobaug Date 2006-06-19 Time 17:58 Sent To PC
Notes
2006-06-19 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE CIRCUIT NUMBERS AND PANEL
 DESIGNATION ON THE HOME RUNS OR AT THE
 LIGHTS.
  
 2} PROVIDE A CALCULATION FOR THE PANEL
 FEEDING THE NEW LOADS, INCLUDE THE NEW
 LOADS. 220.3(A)(4) RECESSED LUMINAIRES
 (LIGHTING FIXTURES). AN OUTLET SUPPLYING
 RECESSED LUMINAIRE(S) [LIGHTING
 FIXTURE(S)] SHALL BE COMPUTED BASED ON
 THE MAXIMUM VOLT-AMPERE RATING OF THE
 EQUIPMENT AND LAMPS FOR WHICH THE
 LUMINAIRE(S) [FIXTURE(S)] IS RATED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 4} ONE PLAN HAS AN ARCHITECTS TITLE
 BLOCK. IF SUBMITTING THE ARCHITECTS
 PLANS , THEY MUST BE SIGNED AND SEALED
 PER 481 FS. THE CONTRACTOR MAY DRAW THE
 PLANS UNDER THE EXEMPTION IN CHAPTER
 481, FS. SEE NOTEE #3.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  