| 2006-06-23 00:00:00 | ********* UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE ZONING COMMENTS AS |
| | NO SITE /SURVEY PLANS WERE SUBMITTED. |
| | MUST SHOW LOCATION OF GEN WITH ALL |
| | DIMENSIONS FROM HOUSE ETC. |
| | PLEASE SEE MECH COMMENTS ALSO. |
| | ** PLEASE SEE THE FOLLOWING COMMENT, AND |
| | PLEASE BE SURE MANUFACTURES SPECS/CUT |
| | SHEETS INDICATE THE MIN CLEARENCE |
| | REQUIRED AROUND EQUIPMENT IN ALL |
| | DIRECTIONS. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE SHOW LOCATION OF ALL |
| | EQUIPMENT ON A LAYOUT FOR HOUSE ETC . |
| | PLEASE SEE MISSING DISCONNECT FOR |
| | FEEDERS COMING FROM GEN AS REQUIRED PER |
| | 225.31-225.39. |
| | |
| | 3) NOTE: PLEASE PROVIDE PANEL SCHEDULE |
| | FOR NEW PANEL. 408.4. |
| | PLEASE PROVIDE ALL INTENDED LOADS FOR |
| | THIS PANEL. |
| | 220, 215.5, 702.5 |
| | |
| | 4) NOTE: PLEASE COMPLETE RISER DIAGRMA |
| | WIHT ALL NEW CONDUCTORS AND OCP DEVICES |
| | BEING INSTALLED TO FEED NEW PANEL. |
| | 215.5, 240.4,310.16 ETC. |
| | |
| | 5) NOTE: PLEASE SUBMIT ALL MANUFCATURES |
| | /SPECS/CUT SHEETS ON PANEL/ATS AND |
| | GENERATOR. |
| | |
| | 6) NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | AS NO SLAB DETAIL WAS SUBMITTED |
| | INDICATING TIE DOWN/VIBRATION ETC. |
| | |
| | 7) NOTE: PLEASE SEE VALUATION IS BASED |
| | ON ALL LABOR AND MATERIALS WHETHER OR |
| | NOT ANY EQUIPMENT IS OWNER SUPPLIED. |
| | VALUE IS BASED ON ALL NEW PERMANANTLY |
| | INSTALLED EQUIPMENT ETC. |
| | FBC 108.3, ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |