Plan Review Details - Permit 06060561
Plan Review Stops For Permit 06060561
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-19 Cont ID  
Sent By rnuquist Date 2006-11-19 Time 21:49 Rev Time 0.00
Received By rnuquist Date 2006-11-19 Time 21:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-10-16 Cont ID  
Sent By amorse Date 2006-10-16 Time 16:11 Rev Time 0.00
Received By amorse Date 2006-10-16 Time 16:11 Sent To PC
Notes
2006-10-16 16:24:25 
  
 DENIED
  
 1) PLEASE SEE THAT DRAWING THAT WAS SUBMITTED DOES NOT
 CONTAIN THE PREVIOUS REVISIONS AND THE NEW REVISIONS
 ARE NOT LABELLED OR CLOUDED TO SHOW ALL CHANGES
  
 2) IF GLUELAM BEAM IS TO CHANGE WHAT IS THE MAKE UP OF
 THE 2X10 GIRDER TRUSS. PLEASE BE AWARE THAT A LUMBER
 BUILT UP BEAM WILL NOT SPAN THE DISTANCE SHOWN ON THE
 DRAWING ALSO THE POST IS NO LONGER SHOWN IN THE
 INTERIOR PARTION WALL SO THE SPAN IS NOW APPROX 22'-0"
  
 3) IF NO PLUMBING OR ELECTRICAL CHANGES ARE TO BE MADE
 ONLY SUBMIT THE STRUCTURAL PAGES A/2 AND A/3
  
 4) NEXT SUBMITTAL FREE DUE TO (2 SEPERATE CHARGES)
 PREVIOUS SUBMITTALS WERE COMBINED INTO ONE AND SHOULD
 HAVE 1 FEE CHARGED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-31 Cont ID  
Sent By amorse Date 2006-08-31 Time 15:22 Rev Time 0.00
Received By amorse Date 2006-08-31 Time 15:22 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-25 Cont ID  
Sent By amorse Date 2006-07-25 Time 14:54 Rev Time 0.00
Received By amorse Date 2006-07-25 Time 14:54 Sent To PC
Notes
2006-07-25 00:00:00 
  
 DENIED
  
 1) MARK THE STORM PANEL DRAWINGS FROM
 THE NOA WITH THE MOUNTING METHOD THAT
 WILL BE USED, TYPE OF ANCHOR, ETC.
 IF ALL WINDOWS ARE TO BE SHUTTERED A KEY
 PLAN IS REQUIRED WITH OPENINGS NUMBERED
 AND SIZES PROVIDED
  
 2) PROVIDE ENGINEERED CALCULATIONS FOR
 THE ENHANCED FASTENING THAT IS REQUIRED
 BY LIMITATION #7 OF THE PRODUCT APPROVAL
  
 3) RIDGE BEAM SPAN WAS NOT CORRECTED
 FROM NOTE #6 ON THE PREVIOUS PLAN REVIEW
 PLEASE SEE THE ATTACHED TABLE FROM THE
 AF&PA WOOD FRAME CONSTRUCTION MANUAL
  
 4) UPON RESUBMITTAL SEE PERMIT CLERK AT
 DESK TO INSERT ROOFING CONTRACTOR AND
 GENERATE A PERMIT NUMBER FOR THE ROOF
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-04 Cont ID  
Sent By amorse Date 2006-07-04 Time 11:12 Rev Time 0.00
Received By amorse Date 2006-07-04 Time 11:12 Sent To PC
Notes
2006-07-04 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC
  
 3) PRODUCT APPROVALS FOR WINDOW MULLIONS
 ARE CUT OFF AND INFORMATION IS MISSING
 PLEASE RESUBMIT. PRODUCT APPROVALS FOR
 ROOFING HAVE OUTDATED FLORIDA COVER
 SHEETS, NEW FL# 735-R1, ALSO FLAT ROOF
 NOA'S REQUIRE PAGES WITH THE ALLOWABLE
 MATERIALS AND TESTS FOR THAT PRODUCT
 ALONG WITH THE SYSTEM USED (17 OR 18)
 AND THE GENERAL LIMITATION PAGE. PLEASE
 SE THAT LIMITATION #7 REQUIRES THAT THE
 ENHANCED FASTENING FOR ZONES 2 & 3 BE
 CALCULATED, SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL
  
 4) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 5) FOUNDATION SHALL BE A MIN OF 12"
 BELOW GRADE PER R403.1.4 PLEASE SEE
 SECTION DETAIL "A" ON A/3
  
 6) BEAM SPAN THAT SUPPORTS RAFTERS IS
 OVER SPAN LIMIT PER TABLE 2308.9.6 FBC
 PLEASE VERIFY AND CORRECT
  
 7) PROVIDE ROOF SHEATHING NAILING DETAIL
 THAT COMPLIES WITH TABLE 2304.9.1 FBC
  
 8) REFFERENCES TO RAFTERS HOW DIFFERING
 SIZES, ROOF FRAMING PLAN HAS 2X10, POST
 DETAIL HAS 2X8, TYPICAL WALL DETAIL HAS
 2X8 PLEASE CLARIFY
  
 9) PLEASE BE AWARE THAT NO ROOFING
 CONTRACTOR IS SIGNED ON AND A BUILDING
 CONTRACTOR CANNOT PERFORM FLAT ROOFING
 UNDER THERE SCOPE OF WORK PER
 489.113(3G) F.S.
  
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 20:08 Sent To P
Notes
2006-10-15 20:12:45****UNSAT *****
  
 1) NOTE: PLEASE SEE REVISIONS ARE NOT SHOWN OR INDICATE
 ON PLANS OR IDENTIFIED ON TITLE BLOCKS.
 FBC ADMIN SECT 106.1.2
  
 2) NOTE: PLEASE SEE PLANS ARE NOT SIGNED ETC FROM THE
 ORIGINAL DESIGNER OF RECORD.
 FBC 106.1.2, FS 481 OR 471
  
 3) NOTE: PLEASE SEE BOTH COPIES OF THE UPDATED SURVEY'S
 SUBMITTED AND STAMPED BY ZONING HAVE BEEN "VOIDED" AS
 THESE DO NOT CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED
 PER FS 472.025 AND FAC 61G17
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW , IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-15 Cont ID  
Sent By dpalmer Date 2006-08-15 Time 15:04 Rev Time 0.00
Received By dpalmer Date 2006-08-15 Time 14:29 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 14:54 Sent To B
Notes
2006-07-23 00:00:00*** UNSAT ***
  
 ** PLEASE KNOW, AS THE ELECTRICAL SHEET
 ALSO CONTAINS THE PLUMB AND PLUMB RISER,
 THE PLUMB WILL BE RE-STAMPED ONCE
 ELECTRICAL REVIEW IS OK..
  
 ** PLEASE SEE SOME NOTES ARE NEW BASED
 ON REVISED PLANS SUBMITTED ALONG WITH
 NOTE FROM PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE THAT ALL
 PLANS/DESIGN NOT REQUIRED TO BE DONE BY
 AN ARCHITECT OR ENGINEER ARE STILL
 REQUIRED TO CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN.
 106.1.2 FBC ADMIN SECT.
  
 2) NOTE: PLEASE STILL SEE MISSING LAYOUT
 FOR SD'S IN EXISTING DWELLING . PLEASE
 SEE ALL EXISTING SLEEPING RMS ARE
 REQUIRED. QUOTING THE CODE IS NOT
 PERMITTED IN LEIU OF SHOWING DETAIL.
 R313, NFPA-72 11.5.1.1
  
 3) NOTE: PLEASE SEE GFI CIRCUIT NOW
 SHOWN AS 15A, #14 WITH 1920 VA? MAX 1440
 VA PERMITTED, PLEASE ADJUST.
 240.4,310.16
  
 4) NOTE: PLEASE SEE NEW A/C WALL UNIT
 WILL ALSO REQUIRED ARC FAULT PROTECTION
 AS MANY WALL A/C UNITS DO NOT CONTAIN
 ARC FAULT PROTECTION. THERE ARE SOME
 UNITS ON THE MARKET WITH AFCI
 PROTECTION, HOWEVER CIRCUIT WILL REQUIRE
 PROTECTION.
 210.12B
 PLEASE SEE OTHER BEDRM CIRCUIT AS "FAULT
 PROTECTION" IS THIS A MISPRINT FOR ARC
 FAULT?
  
 5) NOTE: PLEASE SEE RISER INDICATES
 FEEDERS TO NEW 60A SUB PANEL THROUGH
 "OFFSET NIPPLE" , HOWEVER PLEASE SEE
 PANEL ON PLANS IS BEING SHOWN ON THE
 OTHER SIDE AND ON ANOTHER WALL. AN
 "OFFSETT NIPPLE" IS NOT POSSIBLE.
 PLEASE SEE CONDUCTORS AND MAX PIPE FILL
 IN TABLES OF CHAPETR 9. PLEASE ADJUST
 CONDUIT. (IF PVC, MUST USE SCH 80).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 13:38 Sent To P
Notes
2006-06-24 00:00:00***** UNSAT *******
  
 1) NOTE: PLEASE CORRLEATE PANEL(S) AND
 RISER.
 PLEASE SEE EXSITING 125A PANEL IS ALSO
 BEING SHOWN AS 200A'S?
 PLEASE SEE THERE ARE TWO SEPARATE PANEL
 SCHEDULES SUBMITTED ONE SEEMS TO BE THE
 EXISTING IN MAIN HOUSE, BUT THE OTHER IS
 NOT LABLED? IF IT IS THE NEW PANEL
 SCHEDULE AT METER/MAIN THEN, PLEASE SEE
 MISSING 125A SUB-FEED TO EXISTING PANEL?
 THIS SI UNCLEAR AT THIS TIME AND LOAD
 CALCULATIONS CAN NOT BE VERIFIED.
 215.5,220.31B ETC.
  
 2) NOTE: PLEASE SEE NEW BATH CIRCUIT IS
 SHOWN AS 240V /2-POLE. BRKR.?
 PLEASE ADJUST.
 215.3
  
 3) NOTE: PLEASE SEE MISSIGN RECEPT PER
 210.52 ON WALL IN BEDRM.
  
 4) NOTE: PLEASE SEE NOTES ON ELECTRICAL
 AND BUILDING SHEETS WITH RESPECT TO
 EXISTING BUILDINGS AND SD'S ARE FROM THE
 2001 FBC.
 PLEASE SEE THE NEW FBC 2004 HAS AN
 ENTIRE BOOK ON ITS OWN FOR EXISTING
 DWELLINGS. PLEASE ALSO SEE THE NEW
 RESIDENTIAL CODE 2004.
 SD'S ARE STILL REQUIRED BASED ON
 ALTERATIONS, ADDTIONS, AND THE NEW R313,
 HOWEVER PLEASE ALSO SEE REFERENCE FOR
 SD'S HAS NOW CHANGED AS THE NFPA-72
 CODES QUOTED ARE FROM THE PREVIOUS CODE.
 PLEASE SEE THESE ARE PER 11.5.1.1,
 11.8.3 2002 NFPA-72. THE 1999 WAS
 CHAPTER 8 AS STATED.
 PLEASE ADJUST AND PLEASE SHOW SD
 LOCATIONS INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
  
 5) NOTE: PLEASE SEE MIN OCP FOR 10KW
 HEAT ON AHU SHOULD BE SIZED AT 125% PER
 424.3B. (60A'S).
  
 6) NOTE: PLEASE SHOW LOCATION OF NEW
 SERVICE ON PLANS ALONG WITH PANEL
 LOCATION.
 230.70,230.2, 215.5,240.24,408.7 ETC
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ANY OLD VOIDED SHEETS AND ONLY INSERT
 NEW REVISED SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ** ONE COPY OF OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 11:35 Sent To E
Notes
2006-11-08 11:35:47TO "LMARTINEZ" DESK/REV--DOES NOT NEED "E" REVIEW PER
 "DPALMER"

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 11:35 Sent To E
Notes
2006-11-07 11:35:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 17:13 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 17:13 Sent To Z
Notes
2006-10-26 17:13:44TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 10:15 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 10:15 Sent To E
Notes
2006-10-12 10:16:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 09:42 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 09:42 Sent To Z
Notes
2006-10-06 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 09:01 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 09:01 Sent To Z
Notes
2006-10-06 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 08:10 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 08:10 Sent To E
Notes
2006-08-14 00:00:00TO "DPALMER" DESK/RESUB--ZONING ALREADY
 PASSED

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-11 Cont ID  
Sent By mmiller Date 2006-08-11 Time 10:10 Rev Time 0.00
Received By mmiller Date   Time   Sent To Z
Notes
2006-08-11 00:00:00SENT "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 09:57 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 09:57 Sent To E
Notes
2006-07-21 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 10:13 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 10:13 Sent To E
Notes
2006-06-23 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-04 Time   Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 13:27 Sent To  
Notes
2006-06-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By tgordon Date 2006-06-28 Time 09:25 Rev Time 0.15
Received By tgordon Date 2006-06-28 Time 09:25 Sent To B
Notes
2006-06-28 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-26 Cont ID  
Sent By jleech Date 2006-08-26 Time 07:44 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 07:44 Sent To  
Notes
2006-08-15 00:00:00NEW SHEETS,

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By jleech Date 2006-06-28 Time 07:07 Rev Time 0.00
Received By jleech Date 2006-06-28 Time 07:06 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-04 Cont ID  
Sent By mmclean Date 2006-11-04 Time 08:28 Rev Time 0.00
Received By mmclean Date 2006-11-04 Time 08:28 Sent To I
Notes
2006-11-04 08:32:48REVISION - ENLARGE STRUCTURE 2FT TO THE WEST OF
 STRUCTURE.THE ADDITION CANNOT BE USED AS A SEPARATE
 LIVING SPACE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-11 Cont ID  
Sent By jroach Date 2006-10-11 Time 11:44 Rev Time 0.00
Received By jroach Date 2006-10-11 Time 11:44 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-22 Cont ID  
Sent By mmclean Date 2006-06-22 Time 16:25 Rev Time 0.00
Received By mmclean Date 2006-06-22 Time 16:25 Sent To I
Notes
2006-06-22 00:00:00ADDITION.