Plan Review Details - Permit 06060549
Plan Review Stops For Permit 06060549
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-15 Cont ID  
Sent By rnuquist Date 2007-01-15 Time 15:56 Rev Time 0.00
Received By rnuquist Date 2007-01-15 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-05 Cont ID  
Sent By amorse Date 2006-10-05 Time 16:04 Rev Time 0.00
Received By amorse Date 2006-10-05 Time 16:04 Sent To M
Notes
2006-10-05 00:00:00 
  
  
 DENIED
  
 PREVIOUS REVIEW NOTES NOT ADDRESSED:
  
 1) OK
  
 2) OK VALUE ADJUSTED AND INCREASED
 PERMIT FEES ARE DUE ($255.16)
  
 3) OK FEES ADDED TO PERMIT FEES
  
 4) OK
  
 5) OK
  
 6) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ******NO STATE OF FLORIDA COVER PAGES
 WERE SUBMITTED PLEASE SEE ABOVE WEB SITE
 FOR THE STATE OF FLORIDA PRODUCT
 APPROVAL COVER SHEETS*******
 PLEASE KNOW THE CITY OF WEST PALM BEACH
 REQUIRES THE FLORIDA STATE PRODUCT
 APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE
 AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 7) THE FOLLOWING INFORMATION IS NEEDED
 OR MISSING FROM THE PRODUCT APPROVALS
  
 A) WHERE APPLICABLE THE BUILDING
 OFFICIAL REQUIRES THE STATE OF FLORIDA
 PRODUCT APPROVALS COMPLETE WITH STATE
 COVER SHEET AND APPLICABLE NOA
  
 ********SEE ABOVE NOTE********
  
 B) OK
  
 C) CHOOSE ASSEMBLY THAT WILL BE USED IN
 ROOFING NOA (PG.5 OR 6) ALSO SEE THAT
 THEY WILL NOT MEET THE PRESSURES
 REQUIRED FOR ZONES 2 & 3 OF ROOF WITHOUT
 ENHANCED FASTENING. LIMITATION #7 ALLOWS
 FOR THIS BUT THE CALCULATIONS SHALL BE
 PREPARED SIGNED AND SEALED BY A DESIDGN
 PROFFESIONAL. (SEE PG. 7 LIMITATION#7)
  
 ******PROVIDE ENGINEERS CALCULATIONS FOR
 THE ENHANCED FASTENING IN THE CORNER,
 ZONE 3*******
  
 D) WINDOWS ARE IMPACT RESISTANT BUT
 DOORS ARE NOT AND WILL REQUIRE IMPACT
 PROTECTION, IF USING THESE DOORS PROVIDE
 PRODUCT APPROVAL FOR SHUTTERS
  
 ******THE JELD WEN PRODUCT APPROVAL IS
 FOR A GLAZED NON IMPACT DOOR, PLEASE
 PROVIDE AN APPROVED IMPACT RESISTANT
 PRODUCT APPROVALFOR THE DOOR
  
 E) PROVIDE PRODUCT APPROVALS FOR PRECAST
 CONCRETE LINTELS
  
 ******NOT SUBMITTED******
  
 7) OK
  
 8) PROVIDE A LINTEL SCHEDULE, TYPICAL
 DETAIL PAGE 2 WILL NOT WORK AS TOP OF
 BEAM AT 8'-0" AND DOOR AND WINDOWS AT
 6'-8" TO TOP. TOTAL 16" LESS 8" BOND
 BEAM LEAVES 8" AND DETAIL SHOWS
 16"LINTEL
  
 *******NOT CHANGED ON THE DRAWING*******
  
 9) OK, REMOVED FROM DRAWING
  
 10) PROVIDE CORRECT ROOF COVERING ON
 DRAWINGS AND SPECIFY THE NAILING PATTERN
 PER FASTENING TABLE 2304.9.1 FBC
  
 ******NOT ADDRESSED ON THE DRAWING*****
  
 11) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 ******PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC
 HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING THE NOTICE IS VOID PLEASE
 RERECORD NOC ********
  
  
 NEW NOTES:
  
 1) PER 106.1.3 FBC* THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS "NO WHITE OUT, PENCIL
 OR INK"
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By amorse Date 2006-07-03 Time 13:45 Rev Time 1.50
Received By amorse Date 2006-07-03 Time 13:45 Sent To PC
Notes
2006-07-03 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 3) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC
  
 4) IN AREAS OF QUESTIONABLE SOILS AS
 SHOWN IN THE OFFICIAL ZONING MAP ADOPTED
 BY THE CITY OF WEST PALM BEACH, A SOIL
 TEST REPORT SHALL BE SUBMITTED PER
 R401.4
  
 5) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 6) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
  
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 7) THE FOLLOWING INFORMATION IS NEEDED
 OR MISSING FROM THE PRODUCT APPROVALS
 A) WHERE APPLICABLE THE BUILDING
 OFFICIAL REQUIRES THE STATE OF FLORIDA
 PRODUCT APPROVALS COMPLETE WITH STATE
 COVER SHEET AND APPLICABLE NOA
 B) PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLIONS WHERE 2 WINDOWS ARE JOINED
 TOGETHER
 C) CHOOSE ASSEMBLY THAT WILL BE USED IN
 ROOFING NOA (PG.5 OR 6) ALSO SEE THAT
 THEY WILL NOT MEET THE PRESSURES
 REQUIRED FOR ZONES 2 & 3 OF ROOF WITHOUT
 ENHANCED FASTENING. LIMITATION #7 ALLOWS
 FOR THIS BUT THE CALCULATIONS SHALL BE
 PREPARED SIGNED AND SEALED BY A DESIDGN
 PROFFESIONAL. (SEE PG. 7 LIMITATION#7)
 D) WINDOWS ARE IMPACT RESISTANT BUT
 DOORS ARE NOT AND WILL REQUIRE IMPACT
 PROTECTION, IF USING THESE DOORS PROVIDE
 PRODUCT APPROVAL FOR SHUTTERS
 E) PROVIDE PRODUCT APPROVALS FOR PRECAST
 CONCRETE LINTELS
  
 7) PROVIDE 2 COPIES OF ENERGY CALC'S,
 ONLY ONE SUBMITTED
  
 8) PROVIDE A LINTEL SCHEDULE, TYPICAL
 DETAIL PAGE 2 WILL NOT WORK AS TOP OF
 BEAM AT 8'-0" AND DOOR AND WINDOWS AT
 6'-8" TO TOP. TOTAL 16" LESS 8" BOND
 BEAM LEAVES 8" AND DETAIL SHOWS
 16"LINTEL
  
 9) PLAN HAS BAR SINK THIS WILL REQUIRE
 PLUMBING ISOMETRIC DRAWING, APLUMBING
 PERMIT AND PLUMBING REVIEW
  
 10) PROVIDE CORRECT ROOF COVERING ON
 DRAWINGS AND SPECIFY THE NAILING PATTERN
 PER FASTENING TABLE 2304.9.1 FBC
  
 11) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-12-14 Cont ID  
Sent By btrobaug Date 2006-12-14 Time 17:28 Rev Time 0.50
Received By btrobaug Date 2006-12-14 Time 17:00 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-05 Cont ID  
Sent By btrobaug Date 2006-10-05 Time 07:02 Rev Time 0.50
Received By btrobaug Date 2006-10-05 Time 06:44 Sent To B
Notes
2006-10-05 00:00:00 
 NONCOMPLIANT
  
 THE PLANS MUST COMPLY WITH CHAPTER ONE
 OF THE ADMINISTRATIVE CODE FOR RECORD
 RETENTION AND CHAPTER 471 OF THE FLORIDA
 SATUTES. THE ENGINEER MUST DRAW NEW
 PLANS, THE CORRECTION FLUID UED IS
 UNACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By btrobaug Date 2006-06-20 Time 10:58 Rev Time 0.50
Received By btrobaug Date 2006-06-20 Time 10:10 Sent To B
Notes
2006-06-20 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE.
  
 2} KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(A), 210.52(C), AND
 210.8(A)(6) GFI. THIS IS AN ELECTRICAL
 ISSUE SEPARATE FROM ZONING. IF THE
 KITCHEN IS ON THE PLAN IT MUST COMPLY
 WITH THE NEC.
  
 3} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS. INDICATE
 THE RATING OF THE EXISTING SERVICE.
  
 4} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A)(1) AND 210.52(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 15:00 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 15:00 Sent To M
Notes
2007-10-15 15:01:45TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 15:39 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 15:39 Sent To M
Notes
2007-06-25 15:40:20TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 18:03 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 18:03 Sent To M
Notes
2007-01-29 18:04:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 18:28 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 18:28 Sent To E
Notes
2006-12-12 18:29:36TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 18:31 Sent To  
Notes
2006-11-29 18:31:42SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 12:09 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 12:09 Sent To E
Notes
2006-10-02 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-27 Cont ID  
Sent By mmclean Date 2006-09-29 Time 14:57 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 11:53 Sent To Z
Notes
2006-09-27 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 09:14 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 09:14 Sent To E
Notes
2006-06-20 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-03 Time   Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 14:04 Sent To  
Notes
2006-06-09 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-10-22 Cont ID  
Sent By tgordon Date 2007-10-22 Time 09:31 Rev Time 0.25
Received By tgordon Date 2007-10-22 Time 09:31 Sent To  
Notes
2007-10-22 09:32:31REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-28 Cont ID  
Sent By tgordon Date 2007-06-28 Time 08:00 Rev Time 0.25
Received By tgordon Date 2007-06-28 Time 08:00 Sent To  
Notes
2007-06-28 08:00:34REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-30 Cont ID  
Sent By tgordon Date 2007-01-30 Time 12:17 Rev Time 0.55
Received By tgordon Date 2007-01-30 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-15 Cont ID  
Sent By tgordon Date 2006-12-15 Time 08:38 Rev Time 0.45
Received By tgordon Date 2006-12-15 Time 08:38 Sent To B
Notes
2006-12-15 08:44:38*** DENIED ***
 1) THE MECHANICAL PLANS DUCT LAY-OUT CAN NOT BE DONE IN
 PENCIL.
  
 2) PLEASE SUBMIT TWO CORRECTED COPY'S OF THE MECHANICAL
 PLANS FOR REVIEW.
  
 3) PLEASE PROVIDE RETURN AIR FOR THE ADDITION, SEE 2004
 FBC/R M1602.4.
  
 4) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 5) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By tgordon Date 2006-10-06 Time 08:16 Rev Time 0.30
Received By tgordon Date 2006-10-06 Time 08:16 Sent To  
Notes
2006-10-06 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS CAN NOT BE ON
 FORM 600C-04 AS THE ADDITION IS OVER 600
 SQUARE FEET, PER 2004 FBC 13-600.3.C .
 PLEASE SUBMIT NEW ENERGY CALCULATIONS
 USING FORM 'A' OR 'B'.
  
 2) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, REQUIRED PER 2004 FBC
 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-12-08 Cont ID  
Sent By mmclean Date 2006-12-08 Time 11:37 Rev Time 0.00
Received By mmclean Date 2006-12-08 Time 11:37 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-29 Cont ID  
Sent By mmclean Date 2006-09-29 Time 14:52 Rev Time 0.00
Received By mmclean Date 2006-09-29 Time 14:52 Sent To I
Notes
2006-09-29 00:00:00DENIED,
 1. CITY OF WEST PALM - AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION: BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICAL
 MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROIVDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.THIS POLICY MAY INCLUDE SUCH
 THINDS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 2. CANNOT USE CORRECTION TAPE/FLUID TO
 MAKE CHANGES ON PLANS.
 3. PLEASE SUBMIT NEW PLANS WITH
 CORRECTIONS.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 19:55 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 19:55 Sent To  
Notes
2006-06-18 00:00:00DENIED.
 1. NEED TO REMOVE THE SUMMER KITCHEN
 FROM PLANS. ONLY ALLOWED TO HAVE ONE
 COOKING FACILITY WITHIN THE STRUCTURE.
 2. NEED TO SHOW THE PATIO ON 2 COPY OF
 SITEPLAN AND NEED TO INDICATE IF THERE
 WILL BE ANY FUTURE ROOF.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720