Plan Review Details - Permit 06060540
Plan Review Stops For Permit 06060540
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-10 Cont ID  
Sent By alange Date 2006-07-10 Time 08:39 Rev Time 0.00
Received By alange Date 2006-07-10 Time 08:39 Sent To  
Notes
2006-07-10 00:00:00REVIEWED AND STAMPED NEW PAGES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-20 Cont ID  
Sent By alange Date 2006-06-20 Time 14:45 Rev Time 0.00
Received By alange Date 2006-06-20 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 20:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-05 Cont ID  
Sent By dpalmer Date 2006-07-05 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2006-07-05 Time 15:33 Sent To  
Notes
2006-07-05 00:00:00*** UNSAT ***
  
 1) NOTE: PER CONVERSATION WITH
 CONTRACTOR SCOPE OF WORK FOR ELECTRICAL
 STTOD AT ONE WALL AND TWO OR SO LT
 FIXTURES IN THE REAR OF UNIT SPACE.
 PLEASE SEE PLANS INDICATE THE ENTIRE
 REAR AREA AND WHAT APPEARS TO BE
 "SQUARES" FOR NOTES, HOWWER NOTES COULD
 NOT BE LOCATED.
 PLEASE SEE GENERAL NOTE MENTIONS TO
 REPAIR AND REPLACE ITEMS AS REQUIRED.
 PLEASE ALSO SEE BUILDING SHEETS INDICATE
 RECONSTRUCTION OF SOFFITS ETC WHICH
 WOULD REQUIRE ELECTRICAL WORK IT SEEMS
 OF SOME SORT.
  
 ** PLEASE INDICATE SCOPE OF WORK. CONT
 ALSO MENTIONED NO ELECTRICAL PANELS, ETC
 WERE DAMAGED, YET THESE ARE BEING SHOWN
 ON PLANS.?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-18 Cont ID  
Sent By dpalmer Date 2006-06-18 Time 13:42 Rev Time 0.00
Received By dpalmer Date 2006-06-18 Time 13:34 Sent To  
Notes
2006-06-18 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE SEE THE NEW SCOPE PF
 WORK INCLUDING 277/480V INSTALLATION
 SHALL BE SIGNED, DATED AND SEALED BY A
 FL P.E.
 471.003(2)(H).
  
 2) NOTE: PLEASE SEE NEW SCOPE OF WORK
 BEING PROPOSED UNDER THE 2004 FBC.
 PLEASE SEE CHAPTER 13,
 13-415-.1.ABC.1.1, .1.2,1.3.
 PLEASE PROVIDE THE CORRECT TYPE OF TC AS
 REQUIRED, PLEASE SUBMIT SCHEDULING,
 LOCAATION OF ALL REQUIRED OVER -RIDE
 DEVICES LOCATED A ENTRNACES TO SPACE, AS
 LIGHTING IS VISABLE TO OCCUPANTS.
 PLEASE KNOW, DEPENDING ON DEVICE CHOSEN,
 EITHGER 30 MAX OR 4HRS MAX ALLOWED FOR
 OVERIDING.
 PLEASE SEE 13-415.1.ABC.3,
 13415.1.AB.1, 13-415.2.ABC.1
 PLEASE PROVIDE LIGHTING CALCS/ENERGY
 CALCS AS REQUIRED ABOVE.
  
 ** IMPORTANT**
 WHEN RESUBMITTING PLANS,PLEASE BE SURE
 TO COMPLETELY REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF THE REMOVED OLD/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 15:08 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 13:59 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 13:53 Sent To  
Notes
2006-06-19 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED THE SITE
 DAILY.
  
 3. EXITS ARE TO REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 4. WRONG LIFE SAFETY CODE NOTED ON PAGE
 6 OF 6. SHOULD READ THE FLORIDA FIRE
 PREVENTION CODE.
  
 5. ENSURE THAT AN EMERGENCY LIGHT
 FIXTURE IS PRESENT IN THE STORAGE OR
 EXIT ACCESS TO THE REAR EXIT DOOR.
  
 6. SEPARATE PLANS AND PERMIT REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 7. INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL MEET APPLICABLE FIRE CODE
 REQUIREMENTS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 14:50 Sent To E
Notes
2006-07-27 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 14:53 Sent To  
Notes
2006-07-03 00:00:00TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By jleech Date 2006-06-21 Time 08:55 Rev Time 0.00
Received By jleech Date 2006-06-12 Time 13:22 Sent To  
Notes
2006-06-16 00:00:00TO "BOB"#5
2006-06-12 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 15:18 Rev Time 0.25
Received By tgordon Date 2006-06-20 Time 15:18 Sent To  
Notes
2006-06-20 00:00:00*** PROVISO ***
 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-07-12 Cont ID  
Sent By jleech Date 2006-07-12 Time 14:36 Rev Time 0.00
Received By jleech Date 2006-07-12 Time 14:36 Sent To  
Notes
2006-07-12 00:00:00PLANS SHOW NO PLUMBING WORK IS TO BE
 DONE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By jleech Date 2006-06-21 Time 07:48 Rev Time 0.00
Received By jleech Date 2006-06-21 Time 07:48 Sent To  
Notes
2006-06-21 00:00:00DENIED;
 1.DRINKING FOUNTAIN REQUIRED BY FBC-2004
 PLUMBING TABLE 403.1. DRINKING FOUNTAIN
 IS SHOWN ON PAGE 1 ONLY.
 2.THE D/F SHALL BE 36" TO SPOUT AND A
 CUP DISPENSOR IS REQUIRED BY FBC-2004
 CHAPTER 11 SEC. 11-4.1.3(10) PLEASE NOTE
 ON PLAN.
 3.SHOW ON PLANS THAT RESTROOM IS H/C AND
 SHOW DETAIL OF HIGHTH OF LAVATORY, W/C,
 GRAB BARS, ETC PER CHAPTER 11.
 4.CORRECT RISER DIAGRAMS TO INCLUDE THE
 DRINKING FOUNTAIN.
 5.PAGE 6 CODE COMPLANCE NOTE SHOULD BE
 FBC-2004 AND THE 2002 NATIONAL ELECTRIC
 CODE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695